ML20083L912

From kanterella
Jump to navigation Jump to search
Deficiency Rept Re Failure of Type Cfd Differential Relays on Emergency Diesel Generator Control Panels During Seismic Testing.Info Conveyed to Tdi.Texas Utils Will Replace Relays.Cpc Has Not Responded
ML20083L912
Person / Time
Site: Comanche Peak, Midland, 05000000
Issue date: 07/19/1983
From: Mietz G
ASCO/DELTA (FORMERLY DELTA CONTROLS & RTE-DELTA CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
Shared Package
ML20083L887 List:
References
NUDOCS 8404170404
Download: ML20083L912 (2)


Text

,

)

3 l,-RTE DELTA sJdEiji 705 N. Cirtton Av2. I TLX 359-447 July 19, 1983 Director Office of Inspection and Enforcement Region IV United States Nuclear Regulatory Commission 611 Ryan Plaza Drive Arlington, Texas 76012

Dear Sir:

RTE Delta Co'rp is located in Stockton, California and is the manufacturer of generator control panels which cnnermi generators in nuclear power stations a h "U N Utilitie )the emergency Glen Rose, Texas and Consumers Power, Midland, Michigan.

Each power station has four such panels in place.

For generator differential protection, the specifications for these contracts stipulated that G.E. Type 12CFD22BIA relays be used, and they were so furnished.

During the seismic test portion of the operational life qualifica-tion test program for the Texas Utilities contract, the CFD relays exhibited excessive contact chatter as indicated by the operation of the lockout relay, which coil is controlled by the CFD fault sensing contacts.

This information was reported to our cuctomar, Transamerica Delaval, Inc.

Their analysis of the control system functional design caused them to inform us that this condition must bc considered a failure, since the differential relays remain active during a "LOCA" and must not misoperate should the "LOCA" be accompanied by a seismic event.

A review of the records for all the generator control panels we have supplied to nuclear stations revealed that the Consumers Power, Mid-land, Michigan station also was specified to use the G.E. Type 12CFD 22BlA differential relays and they were furnished.

We so informed 4

Transamerica Delaval, Inc.

Subsequently, we were requested to recommend a replacement for the i

differential relays that would be able to undergo the seismic SSE specified.

A review by us of several alternatives identified the G.E. Type 12 IJD52A as a suitable replacement.

It has the same weight, dimensions j

and connections and is available as a Class lE prequalified device.

l Furthermore, its published seismic response spectrum envelopes those j

recorded for the differential relays during the seismic portion of the operational life qualification tests for Texas Utilities and for Consumers Power.

cgtific

CD, US Nuclocr Rngulctory Commission July 19, 1983 Arlington, TX Page 2 1

This information has been conveyed to Transamerica Delaval by RTE Delta.

We have been informed by Transamerica Delaval that Texas Utilities plans to replace the failed Type CFD differential relays with the pre-qualified Type IJD, as recommended by us.

To date, we have no official notification of this intention, and we have not documented such action into our permanent records or the Operational Life Qualification Test Report.

Transamerica Delaval advises that they are persuing this matter with Texas Utilities and we should be receiving a request to update our records to reflect this change in the near future.

In the case of Consumers Power, we have heard nothing.

Our Operational Life Qualification Test Report indicates that the CFD relays failed the seismic portion of the test.

We have not yet received the com-ments to this report from the design engineer but feel certain that he will address this failure in his response.

We have asked Trans,

america Delaval to keep us informed in this matter._

Your office will be advised as each of these failures is resolved.

Sincerely, RTE DELTA CORP 2/

G.

. Mietz General Manager PH/ sis cc:

V. Dilworth (TDI)

J. Witt (TDI)

C. Alford (RTE)

G. Kidwell (RTE)

.