Final Deficiency Rept Re HPCS Diesel Generator Electrical Panels Supplied by Ge.Initially Reported on 830615. Nonconforming Items for Unit 1 Repaired.Nonconforming Items for Unit 2 Will Be Repaired & Completed by 840808
ML20083K432
Person / Time
Site: Perry  
Issue date: 04/05/1984
From: Edelman M
CLEVELAND ELECTRIC ILLUMINATING CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
RDC-75(83), NUDOCS 8404160170
Download: ML20083K432 (2)


Text

p i

yno m m :m "z

r 1

P.o. box 5000 - CLFVELAND, oHlo 44101 - TELEPHONE (21*) 622-9800 - ILLUMINATING BLDG - 55 PUBLICSQUARE Serving The Best loca' ion w the Nation April 5, 1984 MURRAY R. EDELMAN VICE PRESIDENT NUCLEAR Mr. James G. Keppler Regional Administrator, Region III Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 RE:

Perry Nuclear Power Plant Docket Nos. 50-440; 50-441 HPCS Local Panels E22-S001

[RDC 75(83)]

Dear Mr. Keppler:

This letter serves as the final report pursuant to 10CFR50.55(e) on the potential significant deficiency concerning the High Pressure Core Spray (HPCS) Diesel Generator Electrical Panels supplied by the General Electric Company (GE) to Perry Nuclear Power Plant. This item was originally identified to Mr. F. Jablonski of your office on June 15, 1983, by Mr. M. Kritzer for The Cleveland Electric Illuminating Company (CEI). An interim report on this subject was submitted July 15, 1983.

This report contains a description of the deficiency, an analysis of safety implication, and the corrective action taken.

Description of Deficiencg A number of nonconforming conditions attributed to poor workmanship were identified in the HPCS Diesel Electrical Panels. Some exarples of nonconforming items identified in the two panels (1 per unit) are improperly crimped ring lug terminations, temporary wire labels still present, missing inspection covers, no I.D. on terminal strips, paint overspray, broken wire strands and/or no insulation of the barrel to connection point, use of unapproved cable cleats, and the use of unapproved tape. A complete description of the nonconforming conditions is available on Project Nonconformance Report (NR)

P033-1650 and GE Field Deviation Disposition Request (FDDR) KL1-735 for the Unit 1 panel and Project NR P033-1651 and GE FDDR KL2-591 for the Unit 2 panel.

Analysis of Safety Implication It can be postualated that if some of the items' listed abov,e had gone uncorrected the HPCS Diesel Generator would have failed to start. The failure to start would prevent power _from being supplied to the HPCS pump motor if offsite powe was unavailable.

8404160170 840405 PDR ADOCK 05000440

~ S PDR APR 1019g.; g0

wa Mr. : James G. Keppler 2-April 5, 1984 Corrective Action a

The nonconforming items for Unit 1, identified on NR P033-1650, were repaired in accordance with FDDR KL1-735. All work has been completed for the Unit 1 panels. Documentation review and approval for. the Unit I work will be completed by May 7, 1984.

The nonconforming items for the Unit 2 panels, identified on NR P033-1651, will be repaired in accordance with.FDDR KL2-591. All work for the Unit 2 panels will~be. completed by August 8, 1984.

~

'Please' call if there are any additional questiens.

Sincerely, f k. Yb Murray R. Edelman Vice-President Nuclear Group

'MRE':pab cc: ME.: M. L. Gildner

. NRC l Site Of fice Director Office of Inspection and Enforcement-

~U.S. Nuclear. Regulatory Commission

' Washington,iD.C. 20555-U.S.iNuclear; Regulatory Commission sc/o. Document' Management. Branch

Washington; D.C.-

20555 :

[

Records' Center,;.SEE-IN

~

l

_ Institute of -Nuclear Power. Operations l

1100 circle 75 Parkway,-Suite 1500 L

Atlanta,' Georgia 30339:

1 i

.j-}

5 3

E "A

e

-.