x Commonwealth Edison O ;) ~ Address Reply to. Post Office Box 767 O
one First Nitiorutt Plata, Chicitgo, tilinois Chicago, Illinois 60690 December-30, 1983 Mr. Harold R. Denton, Director Of fice of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, DC 20555
Subject:
Byron Generating Station Units 1 and 2 Braidwood Generating Station Units 1 and 2 Environmental Qualification of Equipment NRC Docket-Nos. 50-454,-50-455, 50-456-and 50-457
..J
References:
1)
July 20, 1983 letter from B. J. Youngblood to D. L. Farrar 2)
May 20, 1983 letter from B. J.
Youngblood to D. L. Farrar 3)
January 14, 1983 letter from T. R. Tramm to H.
R. Denton
Dear Mr. Denton:
This is to provide summary information regarding the
. environmental qualification of mechanical equipment at Byron and Braidwood stations.
We understand that the NRC intends to review in detail three items of mechanical equipment.
Detailed qualification information will be provided as soon as possible on the items selected.
Reference 3 transmitted our description of the
. Byron /Braidwood Mechanical Equipment Environmental Qualification Program.
Three methods for demonstrating qualification of mechanical equipment were discussed in this program.
In References 1 and 2, the NRC requested-a list of all mechanical equipment included in our program and indicated that 3 pieces of equipment would be selected to audit. is the list of all equipment in our program.
Our. list contains active safety related mechanical equipment. explains the qualification established for all BOP equipment on the list except 8 valves.
Almost half of the BOP equipment has been qualified by the first method described in Reference 3.
Specifications were reviewed and the appropriate environmental parameters were specified originally when the equipment was procured.
The remainder of the BOP equipment, excluding the 8 valves, has been investigated and qualification has been established uy analysis per method 2 of Reference 3.
The remaining 8 valves are still under review.
Prior to fuel loa'd, these 8 valves will be qualified or a justification for interim operation will be prepared.
8401100311 831230 PDR ADOCK 05000454 1
A PDR
.O
.g
, - explains the Westinghouse position for environmental qualification of NSSS mechanical equipment.
Please direct questions regarding this matter to this office.
One signed original and fifteen copies of this letter and the attachments are provided for NRC review.
1 Very truly yours, T. R.
Tramm Nuclear Licensing Administrator Attachments 7900N 1
ATTACHMENT 1 BYRON /BRAIDWOOD MECHANICAL ~EOUIPMENT QUALIFICATION LIST EQUIPMENT ENV NUMBER EQUIPMENT NAME
' SPEC.
BLDG.
COL'. - ROW EL..
ZONE
- 1CV0lPA CENTRIFUGAL CilARGING PUMP 1A F/L-2702 AUX.
16V 364 A139-ICV 0lPB CENTRIFUGAL CHARGING PUMP 1B F/L-2702 N "<.
14Z 364 A13g 2CV0lPA CENTRIFUGAL CHARGING PUMP 2A F/L-2702 AUX.
20V 364 A13g 2CV0lPB CENTRIFUGAL CHARGING PUMP 2B F/L-2702 AUX.
22Z
~364 A13g 1RH0lPA RESIDUAL HEAT REMOVAL PUMP 1A F/L-2702 AUX.
13U 346 A13c 1RH0lPB RESIDUAL HEAT REMOVAL PUMP 1B F/L-2702 AUX.
13Y 346 A13c F/L-2702 AUX.
23U 346 A13c 2RH0lPA RESIDUAL HEAT REMOVAL PUMP 2A 2 RH0lPB RESIDUAL HEAT REMOVAL. PUMP 2B F/L-2702 AUX.
23Y 346 A13c 1SI0lPA SAFETY INJECTION PUMP 1A F/L-2702 AUX.
160 364 A13c 1SIOIPB SAFETY INJECTION PUMP 1B F/L-2702 AUX.
13Y 364 A13c 2SI0lPA SAFETY INJECTION PUMP 2A F/L-2702 AUX.
210 364 A13c 2SI0lPB SAFETY INJECTION PUMP 2B F/L-2702 AUX.
23Z 364 A13c OAB8473 2.00 CHECK F/L-2702 AUX.
17N 401 A8 1AB8487 2.00 CHECK F/L-2702
- AUX, 16N 401 A8 2AB8487 2.00 CHECK F/L-2702
- AUX, 17N 401 A8 OCC9432 0.75 X 1 RELIEF F/L-2702 AUX.
180 378 A8 OCC9464 12.00 CHECK F/L-2702 AUX.
18L 366 A8 2CC9416 6.00 GATE ISO MO F/L-2702 CNT.
26S 390 C6 2CC9422A 2 X 1 RELIEF F/L-2702 AUX'
- 19S, 377 A13c 2CC9422B 2 X 1 RELIEF F/L-2702 AUX.
19V 378 A13e 2CC9437A 3.00 GLOBE ISO AO F/L-2702 AUX.
21V 3R3 A13c 2CC9437B 3.00 GLOBE ISO AO F/L-2702 AUX.
24U 383 A13c 2CC9438 4.00 GATE ISO MO F/L-2702 CNT.
24V 390 C6 2CC9486 6.00 CHECK ISO -
F/L-2702 CNT.
24V 395 C6 zu'95L8 0.75 Cill:CK ISO -
F/L-2702 CUT.
24V 395 C6 2rC9534 0.75 CIIFCK ISO -
F/r,-2702 CNT 24V 395 C6 2CC9463A 12.00 CHECK F/L-2702 AUX 19L 366 A8 2CC9463B 12.00 CHECK F/L-2702 AUX 20L 366 A8 2CC9473A 16.00 GATE MO F/L-2702 AUX 19M 364 A8 2CC9473B 16.00 GATE MO F/L-2702 AUX 18L 364 A8 1CVll2B 4.00 GATE MO F/L-2702 AUX.
170 426 A13h ICV 112C 4.00 GATE MO F/L-2702 AUX.
170 426 A13h ICV 112D 8.00 GATE MO F/L-2702 AUX.
14U 380 A13c 1CVll2E 8.00 GATE MO F/L-2702 AUX.
14U 375 A13c
BYRON /QRAIDWOOD MECHANICAL ~ EQUIPMENT QUALIFICATION LIST EQUIPMENT ENV NUMBER EQUIPMENT NAME SPEC.
BLDG.
COL. - ROW EL.
ZONE' 1CV8100 2.00 GLOBE ISO MO F/L-2702 AUX.
13X 383 A13c 1CV8104 2.00 GLOBE MO F/L-2702 AUX.
160 427 A13h ICV 8105 3.00 GATE MO F/L-2702 AUX.
13W 381 A13c l
ICC0685 4.00 GATE ISO MO F/L-2702 AUX.
13V 383 A13c l
1CC9412A 12.00 GATE MO F/L-2702 AUX.
17S 364 A13c 1CC9412B 12.00 GATE MO F/L-2702
- AUX, 19V 364 A13e ICC9413A 6.00 GATE MO F/L-2702 AUX.
13V 383 A13c 1CC9413B 6.00 GATE ISO MO F/L-2702 AUX.
13V 383 A13c 1CC9414 6.00 GATE ISO MO F/L-2702 AUX.
12U 383 A13e ICC9416 6.00 GATE ISO MO F/L-2702 CNT.
10S 390 C6 1CC9422A 2 X l RELIEF F/L-2702 AUX.
16S 377 A13c 1CC9422B 2 X 1 RELIEF F/L-2702 AUX.
17V 378 A13e ICC9437A 3.00 GLOBE ISO AO F/L-2702 AUX.
12V 383 A13c ICC9437B 3.00 GLOBE ISO AO F/L-2702 - AUX.
12U 383 A13c 1CC9438 4.00 GATE ISO MO F/L-2702 CNT.
12U 390 C6 1CC9486 6.00 CllECK ISO -
F/L-2702 CNT 12V 395 C6 1CC9518 0.75 CIIECK ISO -
F/L-2702 CNT 12V 395 C6 1CC9534 0.75 CilECK ISO -
F/L-2702 CNT 12V 398 C6 1CC9463A 12.00 CIIECK F/L-2702 AUX 17L 366 As ICC9463B 12.00 CIIECK F/L-2702 AUX 17Il 3G6 A8 F/L-2702 AUX 17M 364 A8 ICC9473A 16.00 GATE MO 1CC9473B 16.00 GATE MO F/L-2702 AUX 16M 364 A8 l
l l
2CC0685 4.00 GATE ISO MO F/L-2702 AUX'.
23V 383 A13c F/L-2702 AUX.
19S 364 A13c l
2CC9412A 12.00 GATE MO 2CC9412B 12.00 GATE MO F/L-2702 AUX 18V 364 A13e 2CC9413A 6.00 GATE MO F/L-2702 AUX.
23V 383 A13c 23V 383 A13c 2CC9413B 6.00 GATE ISO MO F/L-2702 AUX.
2CC9414 6.00 GATE ISO MO F/L-2702 AUX.
24U 383 A13c
-lCVU 106 3.00 GATE ISO MO F/L-2702 AUX.
13W 381 A13c 1CV8110 2.00 GLOBE MO F/L-2702 AUX.
15S 370 A13c 1CV8111 2.00 GLOBE MO F/L-2702 AUX.
13S 370 A13c ICV 8112 2.00 GLOBE ISO MO F/L-2702 CNT 12X 390 C6 1CV8113 0.75 CIIECK ISO F/L-2702 CNT SR 395 C6 1CV8152 3.00 GLOBE ISO AO F/L-2702 AUX.
12X 383 A13c 1CV8160 3.00 GLOBE ISO AO F/L-2702 CNT.
12X 390 C6
BYRON /BRAIDWOOD MECHANICAL' EQUIPMENT QUALIFICATION LIST
'y EQUIPMENT ENV.
NUMBER EQUIPMENT NAME SPEC.
BLDG.
COL. - ROW EL.
2ONE.
1CV8348 2.00 CHECK ISO -
F/L-2702 CNT.
12V 391 C6 l
1CV8355A 2.00 GLOBE ISO MO F/L-2702
. AUX.
13U 391
.A13c I
ICV 8355B 2.00 GLOBE ISO MO F/L-2702 AUX.
13Y 387 A13c ICV 8355C 2.00 GLOBE ISO MO F/L-2702 AUX.
13Y 387 A13c ICV 8355D 2.00 GLOBE ISO MO F/L-2702 AUX.
13U 391 A13c j
1CV8368A 2.00 CIIECK ISO -
F/L-2702 CNT.
BU 386 C6 ICV 8368B 2.00 CIIECK ISO -
F/L-2702 CNT.
10Y 388 C6 1CV8368C 2.00 CllECK ISO -
F/L-2702 CNT.
12X 391 C6 1CV8368D 2.00 CHECK ISO -
F/L-2742 CNT.
12V 392 C6 1CV8378A 3.00 CilECK -
F-L-2702 CNT 8X 379 C2 1CV8378B 3.00 CIIECK -
F/L-2702 CNT.
8X 379 C2 3CV8379A 3.00 CHECK -
F/L-2702 CNT.
8V 379 C2 1CV8379B 3.00 CIIECK -
F/L-2702 CNT.
8V 379 C2 1CV8381 3.00 CIIECK ISO -
F/L-2702 CNT llY 413 C6 1CV8442 2.00 CIIECK F/L-2702 AUX 17S
~
428 A13h 1CV8481A 4.00 CllECK -
F/L-2702 AUX.
15V 369 A13g ICV 8481B 4.00 CIIECK -
F/L-2702 AUX.
15Z 370 A13g ICV 8546 8. 0 0 CIIECK -
F/L-2702 AUX.
15U 373 A13c 1CV8804A 8.00 GATE MO F/L-2702 AUX.
13S 375 A13c 2CV8100 2.00 GLOBE ISO MO F/L-2702 AUX.
23X 391 A13c 2CV8104 2.00 GLOBE MO F/L-2702 AUX.
19S 427 A13h 2CV8105 3.00 GATE MO F/L-2702 AUX.
23W 364 A13c 2CVll2B 4.00 GATE MO F/L-2702 AUX.
190 426 A13h 2CV112C 4.00 GATE MO F/L-2702 AUX.
190 426
-A13h 2CVll2D 8.00 GATP.MO F/L-2702 AUX.
22U 364 A13c 2CVll2E 8.00 GATE MO F/L-2702 AUX.
22U 364 A13c 2CV8106 3.00 GATE ISO MO F/L-2702 AUX.
23W 364 A13c 2CV8111 2.00 GLOBE MO F/L-2702 AUX.
22S 364 A13c 2CV8110 2.00 GLOBE MO F/L-2702 AUX.
22S 364 A13c 2CV8112 2.00 GLOBE ISO MO F/L-2702 CNT.
24X 390 C6 2CV8113 0.75 CIIECK ISO F/L-2702 CNT 28R 395 C6 2CV8152 3.00 GLOBE ISO AO F/L-2702 AUX.
24X 383 A13c 2CV8160 3.00 GLOBE ISO AO F/L-2702 CNT.
24X 390 C6 2CV8348 2.00 CIIECK ISO -
F/L-2702 CNT.
24V 391 C6 O
~
BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST ENV J'
EQUIPMENT NUMBER EQUIPMENT NAME SPEC.
D,LDG.
COL.'- ROW EL.
ZONE 2CV8355A 2.00 GLOBE ISO MO F/L-2702 AUX.
23U 391 A13c 2CV8355B 2.00 GLOBE ISO MO F/L-2702 AUX.
23Y 387 A13c 2CV8355C 2.00 GLOBE ISO MO F/L-2702 AUX.
23Y 387 A13c 2CV8355D 2.00 GLOBE ISO MO F/L-2702 AUX.
23U 391 A13c 2CV8368A 2.00 CHECK ISO -
F/L-2702 CNT.
200 386 C6 2Cv8368B 2.00 CHECK ISO -
F/L-2702 CNT.
26Y 388 C6 2CV8368C 2.00 CIIECK ISO -
F/L-2702 CNT.
24X 391 C6 2CV8368D 2.00 CHECK ISO -
F/L-2702 CNT.
24V 392 C6 2CV8378A 3.00 CI!ECK -
F/L-2702 CNT.
28X 379 C2 2CV8378B 3.00 CHECK -
F/L-2702 CNT.
28X 379 C2 2CVB379A 3.00 CHECK -
F/L-2702 CNT.
28V 379 C2 2CV8379B 3.00 CIIECK -
F/L-2702 CNT.
28V 379 C2 2CV8381 3.00 CIIECK ISO -
F/L-2702 CNT.
25Y 413 C6 2CV8442 2.00 CI!ECK F/L-2702 AUX 19S 428 A13h 2CV8481A 4.00 CIIECK F/L-2702 AUX 21V 364 A13g 2CV8481B 4.00 CilECK F/L-2702 AUX 21Z 364 A13g 2CV8546 8.00 CilECK F/L-2702 AUX 21U 373 A13c 2CV8804A 8.00 GATE MO F/L-2702 AUX 21S 364 A13c IPR 066 1.00 GLOBE AO F/L-2702 AUX.
13X 387 A13c 2PR066 1.00 GLOBE AO F/L-2702 AUX.
24X -
387 A13c IPS9354A 0.375 GLOBE ISO AO F/L-2702 CNT.
12V 377 C6 1PS9354B 0.375 GLOBE ISO AO F/L-2702 AUX.
13V 379 A13c IPS9355A 0.375 GLOBE ISO AO F/L-2702 CNT.
12V 377 C6 1PS9355B 0.375 GLOBE ISO AO F/L-2702 AUX.
13V 379 A13c IPS9356A 0.375 GLOBE ISO AO F/L-2702 CNT.
12V 377 C6 IPS9356B 0.375 GLOBE ISO AO F/L-2702 AUX.
13V 379 A13c IPS9357A 0.375 GLOBE ISO AO F/L-2702 CNT.
12V 377 C6 1PS9357B 0.375 GLOBE ISO AO F/L-2702 AUX.
13V 379 A13c 2PS9354A 0.375 GLOBE ISO AO F/L-2702 CNT.
24V 377 C6 2PS9354B 0.375 GLOBE ISO AO F/L-2702 AUX.
23V 379 A13c 2PS9355A 0.375 GLOBE ISO AO F/L-2702 CNT.
24V 377 C6 2PS9355B 0.375 GLOBE ISO AO F/L-2702 AUX.
23V 379 A13c 2PS9356A 0.375 GLOBE ISO AO F/L-2702 CNT.
24V 377 C6 2PS9356B 0.375 GLOBE ISO AO F/L-2702 AUX.
23V 379 A13c 21'S 9 3 57A 0.375 GLOBE ISO AO F/L-2702 CNT.
24V 377 C6 2PS9357B 0.375 GLOBE ISO AO F/L-2702 AUX.
23V 379 A13c
BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST 4
EQUIPMENT ENV NUMBER EQUIPMENT NAME SPEC..
BLDG.
COL. - ROW EL.
ZONE' 1RE1003 3.00 DIAPH. ISO AO F/L-2702 CNT.
80 377 C6 1RE9157 1.00 DIAPH. SEAT AO F/L-2702 AUX.
12U 364 A13c 1RE9159A 0.75 DIAPil. ISO AO F/L-2702 CNT.
12U 377 C6 1RE9159B 0.75 DIAPH. ISO AO F/L-270'2 AUX.
12U 379 A13c 1RE9160A 1.00 DIAPH. ISO AO F/L-2702 CNT.
12U 377 C6 1RE91603 1.00 DIAPH. ISO AO F/L-2702 AUX.
12U 379 A13c 1RE9170 3.00 DIAPH. ISO F/L-2702 AUX 13W 401 A13c 2RE1003 3.00 DIAPII. ISO AO F/L-2702-CNT.
28U 388 CG 2RE9157 1.00 DIAPII. SEAT AO F/L-2702 TUX.
24U-379 A13c 2RE9159A 0.75 DIAPH. ISO AO F/L-2702 CNT.
25V 377 C6 2RE9159B 0.75 DIAPH. ISO AO F/L-2702 AUX.
24U 364 A13c 2RE9160A 1.00 DIAPH. ISO AO F/L-2702 CNT.
25V 377 C6 2RE9160B l.00 DIAPH. ISO AO F/L-2702 AUX.
24U 364 A13c 2RE9170 3.00 DIAPH. ISO F/L-2702~ AUX.
24W 363 A13c 1Ril8701A 12.00 GATE ISO MO F/L-2702 CNT.
10V 377 C6 1Ril870ln 12.00 GATE MO F/L-2702 CNT.
10V 390 C2 1RI!8702A 12.00 GATE ISO MO F/L-2702 CNT.
12X 377 C6 1Rl!87023 12.00 GATE MO F/L-2702 CNT.
10W 390 C2 1Ril8716A 8.00 GATE MO F/L-2702 AUX.
14U 378 A13c 1R!!871611 8.00 GATE MO F/L-2702 AUX.
14U 377 A13c 1R!!8730A 8.00 Cl!ECK F/L-2702 AUX 13U 359 A13c liul8730B 8.00 CllECK -
F/L-2702
- AUX, 13Y 352 A13c 2RI!8701A 12.00 GATE ISO MO F/L-2702 CNT.
26V 377 C6 2RH8701B 12.00 GATE MO F/L-2702 CNT.
26V 377 C2 2RII8702A 12.00 GATE ISO MO F/L-2702 CNT.
24X 377 C6 2Ril8702B 12.00 GATE MO F/L-2702 CNT.
26W 390 C2 2Ril8716A 8.00 GATE MO F/L-2702 AUX.
21U 364 A13c
,2 RII8716B 8.00 GATE MO F/L-2702 AUX.
210
- 364 A13c 2RH8730A 8.00 CllECK -
F/L-2702 AUX.
23U 349 A13c 2RII8730B 8.00 CIIECK -
F/L-2702 AUX.
23Y 347 A13c 1RY8000A 3.00 GATE MO F/L-2702 CNT.
IlV 465 C5 1RY8000B 3.00 GATE MO F/L-2702 CNT.
31V 465 C5 1RY8025 0.375 GLOBE ISO AO F/L-2702 AUX.
13W 394 A13c 1FYR026 0.375 GLOBE ISO AO F/L-2702 CNT.
12W 401 C6 114'8028 3.00 DIAPH. ISO AO F/L-2702 AUX.
120 383 A13c lHY3033 0.75 DIAPil. ISO AO F/L-2702 AUX.
13V 394 A13c 1RYB046
'3.00 CIIECK ISO -
F/L-2702 CNT.
12W 395 C6
~
~
~
BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST
- N" EQUIPMENT NUMBER EQUIPMENT NAME
- ' SPEC.
" BLDG.
COL. - ROW EL.
b[
1RY8047 0.75 CHECK ISO -
F/L-2702 CNT.
llU 395 C6 2RY8000A 3.00 GATE MO F/L-2702 CNT.
25V 465 C5 2RY8000B 3.00 GATE MO F/L-2702 CNT.
25V 465 C5 23W' 393 A13c 2RY8025 0.375 GLOBE ISO AO F/L-2702 AUX.
2RH8026 0.375 GLOBE ISO AO F/L-2702 CNT.
24W 401 C6 2Rh8028 3.00 DIAPH. ISO AO F/L-2702 AUX.
24U 383 A13c l
2RY8033 0.75 DIAPH. ISO AO F/L-2702 AUX.
23V 394 A13c 2RY8046 3.00 CIIECK ISO -
F/L-2702 CNT.
24V 395 C6 2RII8047 0.75 CHECK ISO -
F/L-2702 CNT.
25U 395 C6 ISI8801A 4.00 GATE ISO MO F/L-2702 AUX.
13V 383 A13c 1SI8801B 4.00 GATE ISO MO F/L-2702 AUX.
13V 383 A13c 1SI8802A 4.00 GATE ISO MO F/L-2702 AUX.
13V 383 A13c 1SI8802B.
4.00 GATE ISO MO F/L-2702 AUX.
12X 364 A13c l'SI8804B 8.00 GATE MO F/L-2702 AUX.
13Y 364 A13c 1SI8806 8.00 GATE MO F/L-2702 AUX.
13Z 364 A13c ISI8807A 6.00 GATE MO F/L-2702 AUX.
150 364 A13c 1SI8807B 6.00 GATE MO F/L-2702 AUX.
150 364 A13c 1SI8809A 8.00 GATE ISO MO F/L-2702 AUX.
13W 383 A13c 1SI8809B 8.00 GATE ISO MO F/L-2702 AUX.
13X 383 A13c 1SI8812A 12.00 GATE ISO MO F/L-2702 AUX.
15'V.
346 A13c 1SI8812B 12.00 GATE ISO MO F/L-2702 AUX.
14Y 343 A13c 1SI8814 1.50 GLOBE MO F/L-2702 AUX.
15S 364 A13c 1S18815 3.00 CHECK ISO -
F/L-2702 CNT.
12V
.395 C6 ISI8818A 6.00 CIIECK ISO -
F/L-2702 CNT.
7V 422 C6 ISI8818B 6.00 CIIECK ISO -
F/L-2702 CNT.
7X 417 C6 ISI8818C 6.00 CHECK ISO -
F/L-2702 CNT.
12X 385 C6 1SI8818D 6.00 CIIECK ISO -
F/L-2702 CNT.
12V 390 C6 ISI8819A 2.00 CIIECK ISO -
F/L-2702 CNT.
7V 415 C6 ISI8819B 2.00 CHECK ISO -
F/L-2702 CNT.
7X 415 C6 ISI8819C 2.00 CllECK ISO -
F/L-2702 CNT.
12X 381 C6 ISI8819D 2.00 CHECK ISO -
F/L-2702 CNT.
12V 387 C6 ISI8821A 4.00 GATE MO F/L-2702 AUX.
150 380 A13c ISI8823B 4.00 GATE MO F/L-2702 AUX.
ISU 380 A13c l
l I
BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST EQUIPMENT NUMBER EQUIPMENT NAME SPEC.
BLDG.
COL. - ROW EL.
E 1SI8835 4.00 GATE ISO MO F/L-2702 AUX.
13W 383 Ala ISI8840 12.00 GATE ISO MO F/L-2702 AUX.
12U 385 A13c 1SI8841A 8.00 CHECK ISO -
F/L-2702 CNT.
12V 384 C6 ISI8841B 8.00 CHECK ISO -
F/L-2702 CNT.
12W 379 C6 ISI8871 0.75 GLOBE ISO AO F/L-2702 CNT.
12V 383 C6 ISI8880 1.00 GLOBE AO F/L-2702 AUX.
120 364 A13c 1SI8888 0.75 GLOBE ISO AO F/L-2702 AUX.
13V 386 A13c 1SI8900A 1.50 CllECK -
F/L-2702 CNT.
8D 393 C2 l
1SI8900B 1.50 CilECK -
F/L-2702 CNT.
8F 393 C2 ISI8900C
- 1. 50 CIIECK -
F/L-2702 CNT.
10F 393 C2 ISI8900D 1.50 CllECK -
F/L-2702 CNT.
12W 393 C2 ISI8905A 2.00 CIIECK ISO -
F/L-2702 CNT.
12V 381 C6 ISI8905B 2.00 CllECK ISO -
F/L-2702 CNT.
12X 378 C6 ISI8905C 2.00 CllECK ISO -
F/L-2702 CNT.
12X 378 C6 ISI8905D 2.00 CIIECK ISO -
F/L-2702 CNT.
12V 378 C6 ISI8920 1.50 GLOBE MO F/L-2702 AUX.
13Z 364 A13c 1SI8922A 4.00 CilECK -
F/L-2702 AUX.
ISS 367 A13c 1SI8922B 4.00 CilECK F/L-2702 AUX.
13Z 367 A13c 1SI8923A 6.00 GATE MO F/L-2702 AUX.
15Q 364 A13C ISI8923B 6.00 GATE MO F/L-2702 AUX.
13Z' 364 A13c 1SI8924 6.00 GATE MO F/L-2702 AUX.
150 366 A13c 1SI8926 8.00 CllECK -
F/L-2702, AUX.
13Z 376 A13c 1SI8948A 10.00 CilECK -
F/L-2702 CNT; 8W 394 C2 ISI8948B 10.00 CIIECK -
F/L-2702 CNT.
8X 394 C2 ISI8948C 10.00 CilECK -
F/L-2702 CNT.
10X 394 C2
]SI8948D 10.00 CllECK -
F/L-2702 CNT.
~10V 394 C2 ISI8949A 6.00 CIIECK -
F/L-2702 CNT.
10V 385 C2 F/L-2702 CNT.
8W 396 C2 ISI8949B 6.00 CilECK -
ISI8949C 6.00 CIIECK -
F/L-2702 CNT.
10X 385 C2 ISI8949D 6.00 CIIECK -
F/L-2702 CNT.
10V 396 C2 ISI8956A 10.00 CIIECK -
F/L-2702 CNT.
8V 385 C2 ISI8956B 10.00 CilECK -
F/L-2702 CNT.
7N 386 C2 ISI8956C 10.00 CllECK -
F/L-2702 CNT.
IlX 386 C2 ISI8956D 10.00 CilECK -
F/L-2702 CNT.
IlV 396 C2
. ~.
BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST ENV EQUIPMENT.
NUMBER EQUIPMENT NAME SPEC.
BLPG.
COL. - ROW EL.
ZONE 2SI8801A 4.00 GATE ISO MO F/L-2702 AUX.
23V 383 A13c i
2SI8801B 4.00 GATE ISO MO F/L-2702 AUX.
23V 383 A13c 2SI8802A 4.00 GATE ISO MO F/L-2702 AUX.
23V 383 A13c 2SI8802B 4.00 GATE ISO MO F/L-2702 AUX.
24X 364 A13c 2SI8804B 8.00 GATE MO F/L-2702 AUX.
23Y 364 A13c 2SI8806 8.00 GATE MO F/L-2702 AUX.
23Z 364 A13c 2SI8807A 6.00 GATE MO F/L-2702 AUX.
21Q 364 A13c 2SI8807B 6.00 GATE MO F/L-2702 AUX.
21Q 364 A13c 2SI8809A 8.00 GATE ISO MO F/L-2702 AUX.
23V 383 A13c 2SI8809B 8.00 GATE ISO MO F/L-2702
- AUX, 23X 383 A13c I
2SI8812A 12.00 GATE ISO MO F/L-2702 AUX.
23V 346 A13c l' 2SI8812B 12.00 GATE ISO MO F/L-2702 AUX.
21Y 343 A13c 2SI8814 1.50 GLOBE MO F/L-2702 AUX.
210 364 A13c 2SI8815 3.00 GLOBE ISO -
F/L-2702, CNT.
24V 395 C6 2SI8818A 6.00 CIIECK ISO -
F/L-2702 CNT.
29V 422 C6 2SI8818B
- 6. 00 CilECK ISO --
F/L-2702 CNT.
29X 417 C6 2SI8818C 6.00 CllECK ISO -
'F/L-2702 CNT.
24X 385 C6 2SI8818D 6.00 CIIECK 7SO -
F/L-2702 CNT.
24V 390 C6 2SI8819A 2.00 CIIECK ISO -
F/L-2702 CNT.
29V 415 C6 2SI8819B 2.00 CIIECK ISO -
F/L-2702 CNT.
29X 415 C6 F/L-2702 CNT.
24X 381 C6 2SI8819C 2.00 CIIECK ISO -
2SY8819D 2.00 CIIECK ISO -
F/L-2702 CNT.
24V 387 C6 2SI8821A 4.00 GATE MO F/L-2702 AUX; 21U 364 A13c 2SI8821B 4.00 GATE MO F/L-2702 AUX.
21U 364 A13c 2SI8835 4.00 GATE ISO MO F/L-2702 AUX.
21W 383 A13c 2SI8840 12.00 GATS ISO MO F/L-2702 AUX.
21U 364 A13c 2SI8841A 8.00 CIIECK ISO -
F/L-2702 CNT.
24V 384 C6 2SI8841B 8.00 CIIECK ISO -
F/L-2702 CNT.
24W 379 C6 2SI8880 1.00 GLOBE AO F/L-2702 AUX.
240
'364 A13c 2SI8871 0.75 GLOBE ISO AO F/L-2702 CNT.
24U 383 C6 2SI8888 0.75 GLOBE ISO AO F/L-2702 AUX.
23V 386 A13c 2SI8900A 1.50 CIIECK -
F/L-2702 CNT.
28D 393 C2 2SI8900B 1.50 CllECK -
F/L-2702 CNT.
28F 393 C2 2SI8900C 1.50 CIIECK -
F/L-2702 CNT.
26F 393 C2 2SI8900D 1.50 CilECK -
F/L-2702 CNT.
25W 393 C2 2SI8905A 2.00 CIIECK -
F/L-2702 CNT.
24V 381 C6 2SI8905B 2.00 CIIECK -
F/L-2702 CNT.
24X 378 C6 2SI8905C 2.00 CilECK -
F/L-2702 CNT.
24X 378 C6 2SI8905D 2.00 CIIECK -
F/L-2702 CNT.
24V 378 C6 m
r p
y 2
v3;
-g fy BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST'
'.f 'f y j
~
)
'} y
~
!X'UIPMENT NUMBER EOUIPMENT NAME SPEC.
BLDG.
COL. - ROW EL.
2SI8920 1.50 GLOBE MO F/L-2702 AUX.
2'3Z 364 A13 <
2SI8922A d.00 CHECK,-
F/L-2702 AUX.
21Q 367 A13 -
2SI8922B 4.00 CHECK F/L-2702 AUX.
23Z 367 A13c 2SI8923A 6.00 GATE MO F/L-2702 AUX.
210 364 A13c 2 SIB 923B 6.00 GATE MO F/L-2702 AUX.
23Z 364 A13c 2S18924 6.00 GATE MO F/L-2702 AUX.
219 364 A13c 2SI8926 8.00 CilECK -
F/L-2702 AUX.
23Z 376 A13c 2SI8948A 10.00 CHECK -
F/L-2702 CNT.
28W 394 C2 2SI8948B 10.00 CHECK -
F/L-2702 CNT.
28X 394 C2 2SI8948C 10.00 CIIECK -
F/L-2702 CNT.
26X 394 C2 2 SIB 948D 10.00 CilECK F/L-2702 CNT.
26V 394 C2 2SI8949A 6.00 CilECK -
F/L-2702 CNT.
26V 385 C2 2SI8949B -
6.00 CIIECK -
F/L-2702 CNT.
28W 396 C2 7SI8949C 6.00 CHECK ~
F/L-2702 CNT.
26X 385 C2 2SI8949D 6.00 CilECK -
F/L-2702 CNT.
26V 396 C2 2SI8956A 10.00 CIIECK -
F/L-2702 CNT.~
28V 385 C2 2SI8956B 10.00 CilECK -
F/L-2702 CNT.
29W 386 C2 2ST8956C 10.00 CIIECK -
F/L-2702 CNT.
25X 386 C2 2SI8956D 10.00 CllECK -
F/L-2702 CNT.
25V 396 C2 2SI8958A 12.00 CHECK -
F/L-2702 AUX 21V 350 A13c 2SI8958B 12.00 CilECK -
F/L-2702 AUX 21X 350 A13c 1RY4 55A 3.00 GLOBE AO F/L-2702 CNT.
IlV 462 C5 1RY456 3.00 GLOBE AO F/L-2702 CNT.
llV 45'7 C5 2RY455A 3.00 GLOBE AO F/L-2702 CNT.
25V 462 CS
_ 2Ril4 56
_3.00_ GLOBE AO_
F/L-2702 CNT.
25V 457 C5 1MS030743 IlYDRAULIC SNUBBER F'L-2771 TUN 364 T3
/
i JMS01079S IlYDRAULIC SNUBBER F/L-2771 TUN 364 T3 JMS01083S IIYDRAULIC SNUBBER F/L-2771 TUN 364 T3 IMS01038S IIYDRAULIC SNUBBER F/L-2771 TUN 364 T3 1MS01092S IlYDRAULIC SNUBBER F/L-2771 TUN 364 T3 IMS01097S HYDPAULTC SNUBBER F/L-2771 TUN 361 T3 1MS0110lS IlYDRAULIC SNUBBER F/L-2771 TUN 364 T3 1MS01106S HYDRAULIC SNUBBER F/L-2771 TUN 364 T3 11'S2 2 8 A VALVE F/L-2928-2 AUX 13X 403 A13c 11'S22 8B VALVE F/L-2928-2 AUX 13X 395 A13c 1l'S229A VALVE F/L-2928-2 AUX 13X 403 Al3c 1PS??9B VAINE F/L-2928-2 A.UX
]3X 395 A13c
BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST POUIPMENT ENV.
dBER EQUIPMENT NAME SPEC.
BLDG.
COL. - ROW EL._
ZONE-1PS230A VALVE F/L-2928-1 AUX.
13X 403 A13c IPS230B VALVE F/L-2928-1
- AUX, 13X 395 A13c 2PS230A VALVE F/L-2928-1 AUX.
23X 403 A13c 2PS230B VALVE F/L-2928-1 AUX.
23X 395 A13c 2PS228A VALVE F/L-2928-2 AUX.
23X 403 A13c 2PS228B VALVE F/L-2928-2 AUX.
23X 395 A13c 2PS229A VALVE F/L-2928-2 AUX.
23X 403 A13c 2PS2 2 'J B VALVE F/L-2928-2 AUX.
23X 395 A13c IPR 032 VALVE F/L-2794-1 CNT.
12X 387 C6 1PS231A VALVE F/L-2794-1 CNT.
13X 403 C6 1PS231B VALVE F/L-2794-1 CNT.
13X 395 C6 2PR032 VALVE F/L-2794-1 CNT.
24X 387 C6 2PS231A VALVE F/L-2794-1 CNT.
23X 403 C6 2rS231B VALVE F/L-2794.-l CNT.
23X 495 C6 1AF003A CIIECK VALVE F/L-2718-1 AUX 17L 383 All IAF003B CIIECK VALVE F/L-2718-1 AUX 15L 383 All 2AF003A CIIECK VALVE F/L-2718-1 AUX 18L 383 All 2AF003B CIIECK VALVE F/L-2718-1 AUX lgn 3G3 311 1AF014A CIIECK VALVE F/L-2718-1 TUN 7p 23:1 7;n JAP 014B CIIECK VALVE F/L-2718-1 TUN d
3G3
.p e.,
1 AFO IAC CIIECK VALVU F/L--2710-1 TUN 7Z 363
'23d
]AF014D CIIECK VALVE F/L-2718-1 TUN 70 3GD T3a IAF014E CIIECK VALVE F/L-2718-1 TUN 70 3G9 T3a 1AF014F CllECK VALVE F/L-2719-1 TUN 6z 363 T3a lAF014G CIIECK VALVE F/L-2718-1 TUN 7z 363 T3a 368 T3a 1 AP 01411 CIIECK VALVE F/L-2718-1 TUN 7Q 368 T3a 2AP014A Cl!ECK VALVE F/L-2718-1 TUN 29Q 2AF014B CHECK VALVE F/L-2718-1 TUN 29Z 363 T3a
~2AF014C CIIECK VALVE F/L-2718-1 TUN 292 363 T3a 2AF014D C'dJCK VALVE F/L-2718-1 TUN 29g 368 T3a 2AP014E C "CK VALVE F/L-2718-1 Tuli 2 ? r' 3GO T S '.
2 M'014 F CK VAT,VE F/L-27.18-1 ra y !
q;,
353-T 3:-
2AP014G DECK VAINE F/1.-2718-1
'7U71
- . n.
c;,
2 APO 14 3I CIll'CK VAINE F/L-2718-1 TJ' f
.m 15 9 7;a
QYRON/BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST EQUIPMENT ENV NUMBER EQUIPMENT NAME
- SPEC.
BLDG.
COL. - ROW EL.
ZONE-lW0007A CHECK ISO VALVE - 10" F/L-2718-1 CNT llX 407 C6 lW0007B CHECK ISO VALVE - 10" F/L-2718-1 CNT llX 407 C6 2W0007A CIIECK ISO VALVE - 10" F/L-2718-1 CNT 25X 407 C6 2W0007B CHECK ISO VALVE - 10" F/L-2718-1 CNT 25X 403 C6 1FWO36A CHECK VALVE F/L-2718-1 TUN 6S 385 T3 IFWO36B CIIECK VALVE F/L-2718-1 TUN 6S 387 T3 IFWO36C CIIECK VALVE F/L-2718-1 TUN 7Z 387 T3 IFWO36D CIIECK VALVE 2FWO36A CHECK VALVE F/L-2718--l TUN 7Z 387 T3 F/L-2718-1 TUN 30S_
385 T3-2FWO36B CHECK VALVE F/L-2718-1 TUN 30s 387 T3 2FWO36C CIIECK VALVE F/L-2718-1 TUN 29X 337 T3 2FWO36D CHECK VALVE F/L-2718-1 TUN 29X 387-T3 1AF006A GATE VALVE F/L-2718-2 AUX 16N 383 A8 3AF006B GATE VALVE F/L-2718-2 AUX 16L 383 A8 2AF006A GATE VALVE F/L-2718-2 AUX, 18L 383 A8 2AF006B GATE VALVE F/L-2718-2 AUX 19L 383 A8 1AF017A GATE VALVE F/L-2718-2 AUX 16N 383 A8 lAF017B GATE VALVE F/L-2718-2 AUX 16L 383 A8 2AF017A GATE VALVE F/L-2718-2 AUX 19L 383 A8 2AF017B GATE VALVE F/L-2718-2 AUX 19L 392 All lW0006A GATE ISO VALVE - 10" F/L-2718-2 AUX 12X 383 A13c IW0006B GATE ISO VALVE - 10" F/L-2718-2 AUX 13W 401 A13c IWOO20A GATE ISO VALVE - 10" F/L-2718-2 AUX 12X 383 A13c IWOO20B GATE ISO VALVE - 10" F/L-2718-2 AUX 12V 401 A13c 2W0006A
' GATE ISO VALVE - 10" F/L-2718-2 AUX 22Y 383 A13c 2W0006B GATE ISO VALVE - 10" F/L-2718-2 AUX.
23W 401 A13c 2 WOO 20A GATE ISO VALVE - 10" F/L-2718-2 AUX.
24Y 383 A13c 2 WOO 20B GATE ISO VALVE - 10" F/L-2730-2 AUX 24Y 383 A13c
'lW0056A GATE VALVE - 10" F/L-2718-2 CNT 5R 407 C6 lW0056B
%TE VALVE - 10" F/L-2718-2 CNT 7R 403 C6 2Wn956A GATE VALVE - 10" F/L-2718-2 CNT 28R 407 C6 21."'056B GATE VALVE - 10" F/L-2718-2 CNT 26R 403 C6 ISX173 GATE VALVE -
6" F/L-2718-2 AUX 16f t 391 All 2SX173 GATE VALVE -
6" F/L-2718-2 AUX 1 914 391 All ISX178 GATE VALVE -
6" F/L-2718-2 AUX 16t4 389 All 2SX178 GATF VALVE -
6" F/L-2718-2 AUX 19ft 391 All
SYRON/BRAIDWOOD MECHANICAL EQtJIPMENT QUALIFICATION LIST aDIPMENT
- C.DG.
COL. - ROW EL.
ZG NUMBER EQUIPMENT NAME SPEC.
4 0'.CA Primary Cnt. Vent System RCFC Fan F/L-2733 CNT 7V 390 C6
/P01CB Primary Cnt. Vent System RCFC Fan F/L-2733 CNT 7X 364 C6
! W0lCC Primary Cnt. Vent System RCFC Fan F/L-2733 CNT llX 387 C6 VP01CD Primary Cnt. Vent System RCFC Fan F/L-2733 CNT llU 377 C6 2VP01CA Primary Cnt. Vent System RCFC Fan -
F/L-2733 CNT 29V 364 C6 2VP01CB Primary Cnt. Vent System RCFC Fart F/L-2733 CNT 29X 364 C6
'VP01CC Primary Cnt.' Vent System RCFC Fan F/L-2733 CNT 25Y 364 C6 EVP01CD Primary Cnt. Vent System RCFC Fan F/L-2733 CNT 25U 364 C6
.it1S001A Gate ISO Valve F/L-2756 TUN 6S 377 T3
'1MS001B Gate ISO Valve F/L-2756 TUN 6Z 394 T3 1MS001C Gate ISO Valve F/L-2756
- TUN 7Z 394 T3
.lMS001D Gate ISO Valve F/L-2756 TUN 7S 377 T3 2MS001A Gate ISO Valve F/L-2756i TUN 305 377 T3 2MS001B Gate ISO Valve F'/L-2756!
TUN 29Z 377 T3 2MS00lc Gate ISO Valve F/L-2756' TUN 29%
377 T3 2MS 001D Gate ISO Valve F/L-2756 i TUN 30s 377 T3 llCS0lPA Containment Spray Pump (Motor Driven)
F/L-2758 AUX 14V 346 A13C
'ICS0lPB Containment Spray Pump ((Motor Driven)
F/L-2758 AUX 14X 343 A13C
- 2CS0lPA Containment Spr7y Pump Motor Driven)
F/L-2758 AUX 22V 346 A13C
!2CS0lPB Containment Spray Pump (Motor Driven)
F/L-2758 AUX 22X 343 A13C
.1MS013A Relief ISO Val"e F/L-2761 TUN 60 405 T3 1MS013B Relief ISO Valve F/L-2761 TUN GY A05 T3
' lMS 013C.
Relief ISO Valve F/L-2761 TUN 6Y 405 T3 1MS013D
' Relief ISO Valve F/L-2761 TUN 60 405 T3
- 1MS014A Relief ISO Valve F/L-2761 TUN 60 405 T3
.lMS034B Relief ISO Valve
< F/L-2761 TUN 6Y 405 T3
- 1MS014C Relief ISO Valve F/L-2761 TUN 6Y 405 T3
'lMS014D Relief ISO Valve F/L-2761 TUN 60 405 T3 1MS015A Relief ISO Valve F/L-2761 TUN 60 405 T3 LMs015B Relief ISO Valve F/L-2761 TUN 6Y-405 T3
'1MS015C Relief ISO Valve F/L-2761 TUN 6Y 405 T3 IMS015D Relief ISO Valve F/L-2761 TUN 60 405 T3 LMS016A Relief ISO Valve F/L-2761 TUN 60 405 T3
- 1MS016B Relief ISO Valva F/L-2761 TUN 6Y 405 T3 iIMS016C Relief ISO Valve F/L-2761 TUN 6Y 405 T3 jlMS016D Relief ISO Valve F/I./2761 TUN 60 405 T3 h
e
LYRON/BRAIDWOOD MECHANICAL EQUIPMENT-QUALIFICATIfN LIST EQUIPMENT NUMBER EQUI? MENT NAME SPEC.
- BLDG.
COL.'~- ROK EL.
~
1MS017A Relief ISO Valve F/L-2761 TUN 6Q 405
.T3 1MS017B Relief ISO Valve F/L-2761 TUN 6Y 405 T3 1MS017C Relief ISO Valve F/L-2761 TUN 6Y-405 T3 1MS017D Relief ISO Valve F/L-2761 TUN 60 405 T3 2MS013A Relief ISO Valve F/L-2761 TUN 30s 405 T3 2MS013B Relief ISO Valve-F/L-2761 TUN 30Z 405 T3 l
2MS013C Relief ISO Valve F/L-2761 TUN 29Z 405 T3 2MS013D Relief ISO Valve F/L-2761 TUN 29S 405 T3 2MS014A Relief ISO Valve F/L-2761 TUN 30S 405 T3 2MS014B Relief ISO Valve F/L-2761 TUN 30Z 405 T3 2MS014C Relief ISO Valve F/L-2761 TUN 29Z 405 T3 2MS014D Relief ISO Valve F/L-2761 TUN 29S 405 T3 2MS015A Relief ISO Valve F/L-2761 TUN 30s 405 T3 2MS015B Relief ISO Valve F/L-2761 TUN 30Z 405 T3 2MS015C Relief ISO Valve F/L-2761 TUN 29Z 405
.T3 2MS015D Relief ISO Valve F/L-2761 TUN 29s 405 T3 2MS016A Relief ISO Valve F/L-2761 TUN 30s 405 T3 2MS016B Relief ISO Valve F/L-2761 TUN
. 30Z 405 T3 2MS016C Relief ISO Valve F/L-2761 TUN 29Z 405
'T3 2MS016D Relief ISO Valve F/L-2761 TUN 29S 405 T3 2MS017A Relief ISO Valve F/L-2761 TUN 30S
.405 T3 2MS017B Relief ISO Valve F/L-2761 TUN-30Z 405 T3 2MS017C Relief ISO Valve F/L-2761 TUN' 29Z 405 T3 2MS017D Relief ISO Valve F/L-2761 TUN 29S 405 T3 OVA 01CA Aux. Bldg. HVAC Fan F/L-2774 AUX 15S 451 A13D OVA 01CB Aux. Bldg. HVAC Fan F/L-2774 AUX 150 451 A13D OVA 01CC Aux. Bldg. HVAC Fan F/L-2774 AUX
'21S 451 A13D OVA 01CD Aux. Bldg..HVAC Fan F/L-2774 AUX 21Q 451 A13D OVA 02CA Aux. Bldg. HVAC Fan F/L-2774 AUX 16S 476 A13D OVA 02CB Aux. Bldg. HVAC Fan F/L-2774 AUX 17S 476 A13D OVA 02CC Aux. Bldg. IIVAC Fan F/L-2774 AUX 19S 476 A13D OVA 02CD Aux. Bldg. HVAC Fan F/L-2774 AUX 20S 476 A13D OVA 03CA Aux. Bldg. HVAC Fan F/L-2774 AUX 15V 476 A13D OVA 03CB Aux. Bldg. HVAC Fan F/L-2774 AUX 15V 476 A13D OVA 03CC Aux. Bldg. HVAC Fan F/L-2774 AUX 17V 476 A13D
( >VA0 3CD Aux.~ Bldg. HVAC Fan F/L -2774 AUX 18V 476 A13D OVA 03CE Aux. B3dg. HVAC Fan F/L-2774 AUX 19V 476 A13D
. OVA 03CF Aux. Bldg. HVAC Fan F/L-2774 AUX
' 21V 476 A13D
%g w
LYRON/BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST EQUTPMENT I!~
~
NP" a ECUIPMENT NAME SPEC.
- BLDG.
COL'. - ROW EL.
i DVA04CA Aux. Bldg. HVAC Fan F/L-2774 AUX 18V 476 A13D OVA 04CB Aux. Bldg. HVAC Fan F/L-2774 AUX 19V 476 A13D IMS018A Angle ISO Valve F/L-2785 TUN 60 405 T3 1MS018B Angle ISO Valve F/L-2785 TUN 6Y 405 T3 lMS018C Angle ISO Valve F/L-2785 TUN 6Y 405 T3 1MS018D Angle ISO Valve F/L-2785 TUN 60 405 T3 2MS01nA Angle ISO Valve F/L-2785 TUN 30S 405 T3 2MS018B Angle ISO Valve F/L-2785 TUN 30Y 405 T3 2MS018C Angle ISO Valve F/L-2785 TUN 29Z 405*
T3 2MS018D Angle ISO Valve F/L-2785 TUN 29S 405 T3 1FWO43A Control ISO Valve F/L-2793 TUN 7S 377 T3 1FWO43B Control ISO Valve F/L-2793 TUN 7Y 38d T3 1FWO43C Control ISO Valve F/L-2793 TUN 8Z 390 T3 IFWO43D Control ISO Valve F/L-2793 TUN 7S 377 T3 2FWO43A Control ISO Valve F/L-2793 TUN 30S 377 T3 2FWO43B Control ISO Valve F/L-2793 TUN 29Z 377 T.3 2FWO43C Control ISO Valve F/L-2793 TUN 29Z 377 T3 2FWO43D Control ISO Valve F/L-2793 TUN 29Z 377 T3 1CS010A Control Valve F/L-2793 AUX 15W 346 A13C ICS010B Control Valve F/L-2793 AUX 13X 343 A13C 1FWO35A Control Valve F/L-2793 TUN 7S 377 T3 1FWO35B Control Valve F/L-2793 TUN.
7Z 387 T3 IFWC350 Control Valve F/L-2793 TUN 8Z 388 T3 1FWO35D Control Valve F/L-2793 TUN 7Z 377 T3 1PR001A Control Valve F/L-2793 AUX 13X 383 A13C 1PR001B' Control Valve F/L-2793 AUX
,13X 333 A13C 2CS010A Control Valve F/L-2793 AUX 21V 343 A13C 2CS010B Control Valve F/L-2793 AUX 23X 343 A13C 2FWO35A Control Valve F/L-2793 TUN 30S 377 T3 2FWU35B Control Valve F/L-2793 TUN 29Z 377 T3 2FWO35C Control valve F/L-2793 TUN 29Z 377 T3 2FWO35D Control Valve F/L-2793 TUN 290 377 T3 21'R001 A Control Valve F/L-2793 AUX 24X 387 A13C 2PR001D Control Valve F/L-2793 AUX 24X 387 A13C
LYRON/BRAIDWOOD MECHANICAL ~ EQUIPMENT OUALIFICATION LIST EQUIPMENT NUMBER EQUIPMENT NAME SPEC.
BLDG.
COL. - ROW EL.
1FP010 GLOBE ISO VALVE F/L-2793 AUX 12V 391 A13c 1FP0ll GLOBE ISO VALVE F/L-2793 CNT 13v 391 C6 1SA032 GLOBE ISO VALVE F/L-2793 AUX 12U 383 A14c 1SA033 GLOBE ISO VALVE F/L-2793 CNT 12U 383 C6 ISD002A GLOBE ISO VALVE F/L-2793 TUN 6S 377 T3 ISD002B GLOBE ISO VALVE F/L-2793 TUN 6S 377 T3 ISD002C GLOBE ISO VALVE F/L-2793 TUN 6S 377 T3 ISD002D GLGBE ISO VALVE F/L-2793 TUN 6S 377 T3 ISD002E GLOBE ISO VALVE F/L-2793 TUN 6Z 380 T3 1SD002F GLOBE ISO VALVE F/L-2793 TUN 6Z 380 T3 ISD002G GLOBE ISO VALVE F/L-2793 TUN 6Z 380 T3 ISD002H -
GLOBE ISO VALVE F/L-2793 TUN 6Z 380 T3 ISD005A GLOBE ISO VALVE F/L-2793 TUN 6S 377 T3 ISD005B GLOBE ISO VALVE F/L-2793 TUN CS 377 T3 ISD005C GLOBE ISO VALVE F/L-2793 TUN 6Z 383 T3 1SD005D GLOBE ISO VALVE F/L-2793 TUN 63 383 T3 2rP010 GLOBE ISO VALVE F/L-2793 AUX 24V 391 A13c 2Fi>0ll GLOBE ISO VALVE F/L-2793 CNT 23V 391 C6 2GA032 GLOBE ISO VALVE F/L-2793 AUX 24U 383 A13c 2SA033 GLOBE ISO VALVE F/L-2793 CNT 24U 383 C6 2SD002A GLOBE ISO VALVE F/L-2793 TUN 30S 377 T3 2SD002B GLOBE ISO VALVE F/L-2793 TUN 30S 377 T3 2SD002C GLOBE ISO VALVE F/L-2793 TUN 29S 377 T3 2SD002D GLOBE ISO VALVE F/L-2793 TUN 29S 377 T3 2SD002E GLOBE ISO VALVE F/L-2793 TUN 29Z 377 T3 2SD002F GLOBE ISO VALVE F/L-2793 TUN 29Z 377 T3 2SD002G GLOBE ISO VALVE F/L-2793 TUN 29 377 T3 2SD002H GLOBE ISO VALVE F/L-2793 TUN 29Z 377 T3 2SD005A GLOBE ISO VALVE F/L-2793 TUN 30S 377 T3 2SD005B GLOBE ISO VALVE F/L-2793 TUN 29S 377 T3 2SD005C GLOBE ISO VALVE F/L-2793 TUN 29Z 377 T3 2SD005D GLOBE ISO VALVE F/L-2793 TUN 29Z 377 T3 IIA 091 CIIECK ISO VALVE F/L-2794-1 CNT 12X 391 C6 2IA091 CIIECK ISO VALVE F/L-27^1-1 CNT 24X 391 C6
BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST e
~
EQUIP"ENT U~
_ NUMBER EQUIPMENT NAME SPEC.
- BLDG.
COL. - ROW EL.
{~
JS019A GATE ISO VALVU F/L-2794-1 AUX 13W 346 AL 1CS019B GATE ISO VALVE F/L-2794-1 AUX 15X 346 A13c 1SI8811A GATE ISO VALVE F/L-2794-1 AUX 13U 364 A13c 1SI8811B GATE ISO VALVE F/L-2794-1 AUX 13Y 364 A13c 2CS019A GATE ISO VALVE F/L-2794-1 AUX 21V 343 A13c 2CS019B GATE ISO VALVE F/L-2794-1 AUX 41X 343 A13c 2SI8811A GATE ISO VALVE F/L-2794-1 AUX 23U 364 A13c-2SI8811B GATE ISO VALVE F/L-2794-1 AUX 23Y 364 A13c IIA 065 GLOBE ISO VALVE F/L-2794-1 AUX 13X 391 A13c lIR066 GLOBE ISO VALVE F/L-2794-1 CNT 12X 391 C6 1CS008A CilECK ISO VALVE
~F/L-2794-2 CNT 12W 410 C6 1CS0088 CIIECK ISO VALVE F/L-2794-2 CNT 12X 402 C6
{
2CS008A CIIECK ISO VALVE F/L-2794-2 CNT 24W 410 C6 2CS008B
- CIIECK ISO VALVE F/L-2794-2 CNT 24X 402 C6 1CSollA CIIECK VALVE F/L-2794-2 AUX 15V 343 A13c ICSullB CIIECK VALVE F/L-2794-2 AUX 15X 343 A13c 2CS011A CIIECK VALVE F/L-2794-2 AUX 21V 343 A13c 2CSOllB CIIECK VALVE F/L-2794-2 AUX 21X 343 A13c 1CS020A CIIECK VALVE F/L-2794-2 AUX 15U 343 A13c 1CS020B CIIECK VALVE F/L-2794-2 AUX 15X 343 A13c 2CS020A CHECK VALVE F/L-2794-2 AUX 21U 343 A13c 2CS020B CIIECK VALVE F/L-2794,-2 AUX 21X 343 A13c 1CS003A NOSL. CIIECK VALVE - 3 0" F/L-2794-2 AUX 13V 343 A13c 1CS003B NOSL. CilECK VALVE - 104 F/L-2794-2 AUX 15X 343 A13c 2CS003A NOSL. CIIECK VALVE - 10" F/L-2794-2 AUX 21V 343 A13c 2CS003B NOSL. CllECK VALVE - 10" F/L-2794-2 AUX 21X 343 A13c 1CS001A GATE VALVE F/L-2794-3 AUX 13V 364 A13c ICS001B GATE VALVE F/L-2794-3 AUX 15X 364 A13c "lCS007A GATE VALVE F/L-2794-3 AUX 13W 401 A13c 1CS007B GATE VALVE F/L-2794-3 AUX 13X 383 A13c 1CS009A GATE VALVE F/L-2794-3 AUX 13V 346 A13c 1CS009B GATE VALVE F/L-2794-3 AUX 13X 346 A13c 2CS001A GATE VALVE F/L-2794-3 AUX 22X 364 A13c 2CS001B GATE VALVE F/L-2794-3 AUX 22X 364 A13c 2CS007A GATE VALVE F/L-2794-3 AUX 23W 401 A13c 2CS007B GATE VALVE F/L-2794-3 AUX 23X 383 AJ3c 2CS009A GATE VAINE F/L-2794-3 AUX 23V 343 A13c 2CS009B GATE VAINE F/L-2794-3 AUX 21X 343 A13c 21A065 GLOBE ISO VALVE F/L-2794-1 AUX 23X 391 A13c 21A066 GLOBE ISO VALVE F/L-2794-1 CNT 24X 391 C6 1RF027 PLUG ISO VALVE F/L-2874 AUX 33V 383 A13c
BYRON /BRAIDWOOD MECHANICAL EQUtPMENT OUALIFICATION LIST
.ENV
~ EQUIPMENT NUMBER EQUIPMENT NAME SPEC.
- BLDG.
COL. - ROW EL.
' 2O':Il 2RF027 PLUG ISO VALVE F/L-2874 AUX 23V 383-A13c 1
1RF026 PLUG VALVE - 2" F/L-2795 CNT 12V 390 C6 2RF026 PLUG VALVE - 2" F/L-2795 CNT 26S 390 C6 1FWOO9A GATE ISO VALVE - 16" F/L-2874 TUN 6S 377 T3 IFWOO9B GATE ISO VALVE - 16"
'F/L-2874 TUN 7W 377 T3
{
IFWOO9C GATE ISO VALVE - 16" F/L-2874 TUN 6W 377 T3 1FWOO9D GATE ISO VALVE - 16" F/L-2874 TUN 7S 377 T3 2FW009A GATE ISO VALVE - 16".
F/L-2874 TUN 305 377 T3 2FWOO9B GATE ISO VALVE - 16" F/L-2874 TUN 29Z 377 T3 2FWOO9C GATE ISO VALVE - 16" F/L-2874 TUN 29Z 377 T3 2FWOO9D GATE ISO VALVE - 16" F/L-2874 TUN 29S 377 T3 00G059 BUTTERFLY VALVE - 3" F/L-2884 AUX 15U 401 A8 00G060 BUTTERFLY VALVE - 3" F/L-2884 AUX 15U 401 A8 00G061 BUTTERFLY VALVE - 3" F/L-2884 AUX 15U 401 A8 00G062 BUTTERFLY VALVE - 3" F/L-2884 AUX -
15U 401 A8 00G063 BUTTERFLY VALVE i"3" F/L-2884 AUX 15U 401 A8 00G064 BUTTERFLY VALVE - 3" F/L-2884 AUX 21U 401 A8 LOG 057A BUTTERFLY ISO VALVE F/L-2884 CNT 12V 384 C6 IVQ001A BUTTERFLY ISO VALVE F/L-2884 CNT 120 462 C6 lVQ001B BUTTERFLY ISO VALVE F/L-2884 AUX 12X 451 A13d IVQ002A BUTTERFLY ISO VALVE F/L-2884 CNT 12V 462 C6 IVQ002B BUTTERFLY ISO VALVE F/L-2884 AUX 12S 451 A13d IVQ003 BUTTERFLY ISO VALVE F/L-2884 AUX 13W 475 A13d lVQ004A BUTTERFLY ISO VALVE F/L-2884 CNT 12U 462 C6 4
lVQ004B BUTTERFLY ISO VALVE F/L-2884 AUX 120 451-A13d IVQ005A BUTTERFLY ISO VALVE F/L-2884 CNT 12V 475 C6 l
IVQ005B BUTTERFLY ISO VALVE F/L-2884 AUX 13V 472 A13d
,2OG057A BUTTERFLY ISO VALVE F/L-2884 CNT 24V 384 C6 ISX016A BUTTERFLY ISO VALVE F/L-2884 AUX 13Y 403 A13c 1SX016B BUTTERFLY ISO VALVE F/L-2884 AUX 13V 401 A13c 1SX027A BUTTERFLY ISO VALVE F/L-2884 AUX 13Y 403 A13c 1SX027B BUTTERFLY ISO VALVE F/L-2884 AUX 13V 403 A13c 1
e
BYRON /BRAIDWOOD MECHANICAL' EQUIPMENT QUALIFICATlON LIST i[
.JUIPMENT NUMBER EQUIPMENT NAME
~ SPEC.
BLDG.
COL. - ROW EL.
1SX169A BUTTERFLY VALVE F/L-2884 AUX 8P 401 A0 1SX169B BUTTERFLY VALVE F/L-2884 AUX 6P 401 A6 2SX016A BUTTERFLY ISO VALVE F/L-2884 AUX 23Y 370 A13c 2SX016B BUTTERFLY ISO VALVE F/L-2884 AUX 23Y 403 A13c 2SX027A BUTTERFLY ISO VALVE F/L-2884 AUX 26V 403 A13c 2SX027B BUTTERFLY ISO VALVE F/L-2884 AUX 23X 403 A13c 2SX169A BUTTERFLY VALVE F/L-2884 AUX 26P 401 A6 2SX169B BUTTERFLY VALVE F/L-2884 AUX 29P 401 A6 2VQ001A BUTTERFLY ISO VALVE F/L-2884 CNT 24U 462 C6 2VQ001B BUTTERFLY ISO VALVE F/L-2884 AUX 24S 452 A13d 2VQ002A BUTTERFLY ISO VALVE F/L-2884 CNT 24V 462 C6 2VQ002B BUTTERFLY ISO VALVE F/L-2884 AUX 24U 451 A13d 2VQ003 BUTTERFLY ISO VALVE F/L-2884 AUX 23V 467 A13d 2VQ004A BUTTERFLY ISO VALVE F/L-2884 CNT 24U 462 C6 2VQ004B BUTTERFLY ISO VALVE F/L-2884 AUX 24U 451-A13d 2VQ005A BUTTERFLY ISO VALVE F/L-2884 CNT' 24V 475 C6 2VQ005B BUTTERFLY ISO VALVE F/L-2884 AUX 23V 467 A13d LOG 079 BUTTERFLY VALVE - 3" F/L-2884 CNT 12X 403 C6 LOG 080 BUTTERFLY VALVE - 3" F/L-2884 CNT 12X 403 C6 10G081 BUTTERFLY VALVE - 3" F/L-2884 CNT 12V 395 C6 LOG 082 BUTTERFLY VALVE - 3" F/L-2884 AUX 13X 402 A13c LOG 083 BUTTERFLY VALVE - 3" F/L-2884 AUX 13V 379 A13c LOG 084 BUTTERFLY VALVE - 3" F/L-2884 AUX 13X 402 A13c 2OG079 BUTTERFLY VALVE - 3" F/L-2884 AUX 13U 395 A13c LOG 085 BUTTERFLY VALVE - 3" F/L-2884 CNT 24X 403 C6 2OG080 BUTTERFLY VALVE - 3" F/L-2884 CNT 24X 403 C6 20G082 B'1TTERFLY VALVE - 3" F/L-2884 AUX 24V 395 A13c 2OG081' BUTTERFLY VALVE - 3" F/L-2884 CNT 23X 402 A13c 2OG083 BUTTERFLY VALVE - 3" F/L-2884 AUX 23V 379 A13c 2OG084 BUTTERFLY VALVE - 3" F/L-2884-AUX 23X 402 A13c 2OG085 BUTTERFLY VALVE - 3" F/L-2884 AUX 23U 395 A13c OWOO20A RELIEF VALVE
~ F/L--2 8 8 5 AUX PN 390 A3 OU0028B RELIMP VALVE F/L--2 8 85 AUX ION 390 AC IVA02CA AUX. BLDG. IIVAC PHR PUMP CUB. COOLER FAN F/L-2900 AUX 13U 346 A33c IVA02CB AUX. BLDG. IIVAC RIIR PUMP CUB. COOLER FAN F/L-2900 AUX 13U 346 A13c l
IVA02CC AUX. BLDG. IIVAC RIIR PUMP CUB. COOLER FAN F/L-2900 AUX 13X 346 A13c IVA02CD AUX. BLDG. IIVAC RilR PUMP CUB. COOLER FAN F/L-2900 AUX 13X 346 A13c l
w
LYRON/BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST
~-
IENT
BLDG.
COL. - ROW EL.
1 7A03CA AUX. BLDG. HVAC CS PUMP CUB. COOLER TAN F/L-2900 AUX 13W 346 A13C
~
3A03CB
' AUX. BLDG. iNAC CS PUMP - CUB. COOLER FAN F/L-2900 AUX 13W 346 A13C-1 IVA03CC AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 13W 346 A13C I
LVA03CD AUX. BLDG, HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 13W 346 A13C IVA03CE AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 13X 346.A13C l
IVA03CF AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 13X 346 A13C LVA03CG AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 13X-346 A13C j
IVA03CH AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 13X 346-A13C IVA04CA AUX. BLDG. HVAC SI PUMP CUB. COOLER FAN F/L-2900 AUX 170 346 A13C j
IVAG4CB AUX BLDG. HVAC SI PUMP CUB. COOLER FAN F/L-2900 AUX 170 346 A13C IVA04CC AUX. BLDG. HVAC SI PUMP CUB. COOLER FAN F/L-2900 AUX 13Y 346 A13C i
IVA04CD AUX. BLDG. HVAC SI PUMP CUB. COOLER FAN F/L-2900 AUX 13Y 346 A13C lVA06CA AUX, BLDG, HVAC CC PUMP CUB. COOLER FAN F/L-2900 AUX 16U 346 A13G 4
j IVA06CB AUX. BLDG. HVAC CC PUMP CUB. COOLER FAN F/L-2900 AUX 160 346 A13G lVA06CC AUX. BLDG. HVAC CC PUMP CUB. COOLER FAN F/L-2900 AUX -
15Z 346 A13G IVA06CD AUX. BLDG. HVAC CC PUMP CUB. COOLER FAN F/L-2900 AUX 15Z 346 A13G l
IVA07CA AUX. BLDG. HVAC FC PUMP CUB. COOLER FAN F/L-2900 FB 18Z 401 A12 lVAG7CB AUX. BLDG. HVAC FC PUMP CUB. COOLER FAN F/L-2900 FB 183-401 A12 2VA02CA AUX. BLDG. HVAC RH. PUMP CUD. COOLER FAN F/L-2900 AUX 23U 346 A13C 2VA02CB AUX. BLDG. HVAC RH PUMP CUB. COOLER FAN F/L-2900 AUX 23U 346 A13C 2VA02CC AUX. BLDG. HVAC RH PUMP CUB. COOLER FAN F/L-2900 AUX 23Y 346 A13C 2VA02CD AUX. BLDG. HVAC RH PUMP CUB. COOLER FAN F/L-2900-AUX 23Y 346 A13C 2VA03CA AUX. BLDG. HVAC CS PUMP. CUB. COOLER FAN F/L-2900 AUX 23W 346 A13C 2VA03CB AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 23W 346 A13C 2VA03CC AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 23W 346 A13C 2VA03CD AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 23W 346 A13C 2VA03CE AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 23X 346 A13C 2VA03CF AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 23X 346 A13C 2VA03CG AUX. BLDG, HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 23X 346 A13C t
2VA03CH AUX. BLDG. HVAC CS PUMP CUB. COOLER FAN F/L-2900 AUX 23X.
3.46 A13C 2VA04CA AUX. BLDG. HVAC SI PUMP CUB. COOLER FAN F/L-2900 AUX 190 364 A13C 2VA04CB AUX. BLDG. HVAC SI PUMP CUB. COOLER FAN F/L-2900 AUX 19Q 364 A13C 2VA04CC AUX. BLDG. HVAC SI PUMP CUB. COOLER FAN F/L-2900 AUX 23Y 364 A13C
]
2VA04CD AUX. BLDG. HVAC SI PUMP CUB. COOLER FAN F/L-2900 AUX 23Y 364 A13C 2VA06CA AUX. BLDG. HVAC CC PUMP CUB. COOLER FAN F/L-2900 AUX 19V 364 A13G 2VA06CB AUX. BLDG. HVAC CC PUMP CUB. COOLER FAN F/L-2900 AUX 19V 364 A13G l
2VA06CC AUX. BLDG. HVAC CC PUMP CUB, COOLER FAN F/L-2900 AUX 23Y 364 A13G 2VA06CD AUX. BLDG. HVAC CC PUMP CUB. COOLER FAN F/L-2900 AUX 23Y 364 A13G 2VA07CA AUX. BLDG. HVAC FC PUMP CUB. COOLER FAN F/L-2900 AUX 19V 401 A12 2VA07CB AUX. BLDG. HVAC FC PUMP CUB. COOLER FAN F/L-2900 AUX.
19V 401 A13 i
BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST e
EQUIPMENT Eir NUMBER EQUIPMENT NAME SPEC.
BLDG.
COL. - ROW EL.
ZCU liA05CA Fan F/L-2900 '
AUX 17U 364 A13C IVA05CB Fan F/L-2900 AUX 17U 364 A13C 2VA05CA Fan F/L-2900 '
AUX 19U 364 A13C 2VA05CB Fan
~
F/L-2900 AUX 19U 364 A13C OVA 022YA Damper F/L-2903 AUX 15V 476 A13D OVA 022YB Damper F/L-2903 AUX 15V 476 A13D OVA 023YA Damper F/L-2903 AUX 17V 476 A13D F/L-2903 AUX 17V 476 A13D OVA 023YB Damper OVA 024YA Damper F/L-2903 AUX 17V 476 A13D OVA 024YB Damper F/L-2903 AUX 17V 476 A13D OVA 025YA Damper F/L-2903 AUX 18V 476 A13D OVA 025YB Damper F/L-2903 AUX 18V 476 A13D OVA 053YA Damper
' F/L-2903 AUX 18U 451 A13D OVA 053YB Damper F/L-2903 AUX 18U 451 A13D OVA 053YC Damper F/L-2903 AUX 19U 451 A13D OVA 054YA Damper F/L-2903 AUX 18V 451 A13D OVA 054YB Damper F/L-2903 AUX 19V 451 A13D OVA 057Y Damper F/L-2903 AUX 18V 476 A13D OVA 053YA Damper F/L-2903 AUX 18U 451 A13D OVA 058YB Damper F/L-2903 AUX 190 451 A13D OVA 058YC Damper F/L-2903 AUX 190-451 A13D OVA 059YA Damper F/L-2903
- AUX, 18V 451 A13D OVA 059YB Damper F/L-2903 AUX 19V 451 A13D OVA 062Y Damper F/L-2903 AUX 19V 476 A13D OVA 067YA Damper F/L-2903 AUX 19V 476 A13D OVA 067YB Damper F/L-2903 AUX 19V 476 A13D
~
OVA 072YA Damper F/L-2903 AUX 21V 476 A13D OVA 072YB Damper F/L-2903 AUX 21V 476 A13D i
OVA 079YA Damper F/L-2903 AUX 19U 476 A13D OVA 079YB Damper F/L-2903 AUX 19U 476 A13D 1
OVA 084YA Damper F/L-2903 AUX 15U 451 A13D OVA 084YB Damper p/L_2903 AUX 15U 451 A13D OVA 085YA Damper F/L-2903 AUX.
18U 451 A13D OVA 085YB Damper F/L-2903 AUX 18U 451 A13D OVA 086YA Damper F/L-2903 AUX 21U 451 A13D OVAUFGYB Damper F/L-2903 AUX 21U 451 A13D OVA 037YA Damper F/L-2903 AUX 15S 451 A13D OVA 087YB Damper F/L-2903 AUX 15S 451 A13D
BYRON /BRAIDWOOD MECHANICAL EQUIPMENT QUALIFICATION LIST L
i 11 UMBER EQUIPMENT NAME SPEC.
BLDG.
COL. -- ROW EL.
E I
I' MENT F'/L-2903 AUX 18S 451 A13D F/L-2903 AUX 18S 451 A13D OVA 088YA Damper OVA 089YA Damper.
F/L-2903 AUX 18S 451 A13D OVA 088YB Damper F/L-2903 AUX 18S 451 A13D F/L-2903 AUX 21S 451 A13D OVA 089YB Damper F/L-2903 AUX 21S 476 A13D OVA 099YA Damper F/L-2903 AUX 17Q 476 A13D OVA 099YB Damper OVA 100YB Damper F/L-2903 AUX 17Q 476 A13D OVA 100YA Damper F/L-2903 AUX 15U 476 A13D i
F/L-2903 AUX 17U 476 A13D OVA 424YA Damper F/L-2903 AUX 17U 476 A13D OVA 424YB Damper
.F/L-2903 AUX 18U 476 A13D OVA 425YA Damper F/L-2903 AUX 19U 476 A13D OVA 425YB Damper OVA 427YA Damper F/L-2903 AUX 21U 476 A13D 1RC014A Globe Valve - 1" F/L-2928 CNT 10X 429 C3 OVA 427YB Damper 1RC014B Globe Valve - 1" F/L-2928 CNT 10X 429 C3 1RC014C Globe Valve - 1" F/L-2928 CNT 10X 429 C3 l
1RC014D Globe Valve - 1" F/L-2928 CNT 10X 429 C3 l
2RC014A Globe Valve - 1" F/L-2928 CNT 26W 429 C3 l
2RC014B Globe Valve - 1" F/L-2928 CNT 26W 429 C3 l
2RC014C G]obe Valve - 1" F/L-2928 CNT 26W 429 C3 2RC014D Globe Valve - 1" F/L-2928 CNT.
.26W 429 C3 ISX10JT Globe Valve F/L-2928 AUX 18t1 383 All 2SX191A Globe Valve F/L-2928 AUX 18M 384 All O
l 8
J Results of Environmental Qualification Review f or 80P Mechanical Equipment,,
1 A list of 441 pieces of B0P mechanical equipment has been generated for Byron Units 1 and 2.
This equipment is active safety related equipment.
A thorough review of the specification, the environmental conditions, and the equipment design has been made.
I 171.of the 441 components have specification requirements which equal or exceed the applicable environmental conditions in FSAR Table 3.11-2.
Of the remainder, 93 are valves which were specified to.
experience temperatures of 1220F, but are in areas with predicted maximum temperatures of 1300F to 1330F.
48 valves in the steam tunnel have specification requirements of 2800F for the first three hours after an accident.
The peak temperature in the tunnel af ter an accident is calculated to be 3250F. _.However, the calculations also show that the temperature will be reduced to less than 2800F in less than ten minutes and to about 1200F in 30 minutes.
The effect of high temperature on material deterioration is dependent upon both the temperature reached and the time spent at elevated temperature.
Th e stc tunnel temperature profile is calculated using many conservative e-
'ons.
Because of the limitations of heat transfer from steam to a
' ace (especially non-metallic materials), temperature sensitive i
c
(
s will not reach temperatures above 2800F during the p
.ed transient.
As a result, the specification of 2800F for tr.
hours is conservative.
We do not feel these differences are i
significant to the operation of these 141 valves.
72 HVAC f ans have lower radiation levels specified than the current predicted accident radiation environment.
16 of these fans also have a 1040F temperature requirement rather than the predicted 1220F onvironment.
These f ans have been investigated and it has been d?termined that the f ans contain no non-metallic components and are not j
sensitive to the elevated radiation and temperature levels.
The four containment spray pumps were originally specified to experience a post-accident radiation level below the current predicted l
level.
To insure that the pumps will operate reliably under design conditions, a detailed analysis of the design and materials of the pumps was completed.
The conclusion of this analysis was that the pumps are l.
qualified for the design conditions.
53 valves inside containment were specified to withstand 2800F f or three hours af ter the accident.
The current design temperatures are l
3200F for three minutes decreasing to 2700F for 5 to 20 minutes after 7
. the accident.
The specification requirement for radiation was 4 x 10 rads instead of the current 2 x 108 rads.
These valves are being Investigated to determine the effects of the 13 test environmental conditions.
Currently, 45 of the 53 valves have been determined to be acceptable.
The remaining eight are still under investigation.
In summary, the active safety related mechanical equipment has been shown to be adequately designed for the predicted environmental conditions.
All but eight of the 441 components have been f ound acceptable without modification.
These eight valves will be qualified or a justification for interim operation will be prepared prior to fuel load.
r
,I.
?
- /
Environmental Qualification of NSSS Mechanical Equipment A list of 307 pieces of NSSS mechanical equipment has been generated for Byron Units 1 and 2.
All NSSS equipment was procured under specification F/L-2702 (see attachment 1).
This equipment is active safety related inechanical equipment.
The safety related mechanical equipment at Byron /Braidwood has been designed to withstand environmental effects as required by GDC 4 and i
Appendix B of 10CFR50.
The components' system design requirements are contained in design specifications and procurement documents.
Soft parts in these components were selected based upon vendor experience, good engineering practice, and industry data.
The above design practices are supplemented by the Byron /Braidwood pump and valve operability program and the Byron /Braidwood maintenance and surveillance programs.
Westinghouse is in the process of re-verifying the acceptability of the sof t parts used in the NSSS mechanical equipment at Byron /Braidwood.
Based on previous experience, it is anticipated that the results of this review will be acceptable.
It is expected that th e results of this review will be completed by January 31, 1984.