ML20083G725

From kanterella
Jump to navigation Jump to search
Provides Final Response to IE Bulletin 83-06 Re Nonconforming Matls Supplied by Tube-Line Corp,Describing Results of Review of Items Identified in Initial Response Dtd 831118.Elbows Considered Acceptable,As Furnished
ML20083G725
Person / Time
Site: Catawba  
Issue date: 12/30/1983
From: Tucker H
DUKE POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-SSINS-6820 IEB-83-06, IEB-83-6, NUDOCS 8401060401
Download: ML20083G725 (2)


Text

.,

_m g

DUKE F OWER GoM1wxy I.O.HOK 33180 CHAH1,OTTE, N.O. 28242 IIAL H. TIICKl?R TELEPHfmE December 30, 1983 (704) 373-4sai

= = = = =

NE103.EA5 PIMMMUION Mr. James P. O'Reilly, Regional Administrator U. S. Nuclear Regulatory Commission Region Il 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303 Re: Ril:JPO Catawba Nuclear Station Docket Nos. 50-413 and 50-414

Dear Mr. O'Reilly:

Please find attached a final response to IE Bulletin 83-06 describing the results of our review of those Tube-Line Corporation items identified in our initial response of November 18, 1983.

I declare under penalty of perjury that the statements set forth herein are true and correct to the best of my knowledge.

Very truly yours, d

q - __

Hal B. Tucker LTP:dyh Attachment cc: Document Control Desk l

U. S. Nuclear Regulatory Commission Washington, D. C.

20555 NRC Resident inspector Catawba Nuclear Station i

Mr. Robert Guild, Esq.

~

Attorney-at-Law P. O. Box 12097 Charleston, South Carolina 29412 s

Palmetto Alliance l

2135h Devine Street Columbia, South Carolina 29205 8401060401 831230 PDR ADOCK 05000413 G

PDR d

\\

T s

O Final Response to IE Bulletin 83-06 Items Supplied by Tube-Line Corporation to Catawba Nuclear Station Item a.

The four (4) pipe caps in question are used inside the Fuel Oil Day Tank as part of a level indicator. These pipe caps serve no pres-sure-retaining function and therefore do not require replacement.

Item b.

The two (2) elbows in question were furnished with the auxiliary feed-water pump turbine tube oil coolers. Material test reports have been traced to the heat number from the material manufacturer. The chemi-cal and physical analysis conform to the requirements for SA 312TP 304L, which is the material specified by our turbine manufacturer.

Also, the elbows have successfully hydrotested at 660 psig, which far exceeds our hydro-test requirement of 225 psig. Lastly, the material manufacturer has certified that these fittings were heat treated in accordance with ASTM-A312 requirements, so that heat sensitization is not a concern.

For these reasons, the elbows are considered accep-table as furnished and do not require replacement.