GPU Nuclear Corporation Nuclear

stteo Midd!etown. Pennsylvania 17057-0191 717 944-7621 TELEX 84 2386 Wnter's Direct Dial Number:

(717) 948 8005 5211-83-371 December 14, 1983 Dr. T. E. Murley, Regional Administrator U. S. Nuclear Regulatory Commission Region I 63't Park Avenue King of Prussia, PA 19406

Dear Sir:

Three Mile Island Nuclear Station, Unit 1 (TMI-1)

Operating License No. DPR-50 Docket No. 50-289 LER 83-046 This letter is to confirm the conversation between Mr. F. Young, URC Inspector and Mr. M. A. Nelson, PRG Chairraan, at 1645 hours0.019 days <br />0.457 hours <br />0.00272 weeks <br />6.259225e-4 months <br /> on December 13, 1983.

Review of cable separation for the Makeup Pump low lube oil pressure trip circuit revealed that the cables for A (Red Channel) and C (Green Channel)

Makeup Pumps are not properly separated. The cables for both pumps are located in the same trays for portions of their routing. The circuits also are not properly classified in that the circuit schedule indicates that the circuits sre non-safeguards classification.

This condition was discovered as a result of an investigation of a green marked cable in a red channel tray and is considered reportable under Technical Specification 6.9.2.A.9.

Further details vill be provided in the 14 day follovup report.

Sincerely, i

'C k

d R.

. TOOLE Operations and Maintenance Director, TMI-l RJT/CEH/dsk cc:

R. Conte, NRC CARIRS 8312300172 831214 PDR ADOCK 05000289 S

pyg j

( (

GPU Nuclear Corporation is a subsidiary of the General Public Utikties Corporation y