ML20082U811
| ML20082U811 | |
| Person / Time | |
|---|---|
| Site: | Marble Hill |
| Issue date: | 12/09/1983 |
| From: | Shields S PSI ENERGY, INC. A/K/A PUBLIC SERVICE CO. OF INDIANA |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| References | |
| 10CFR-050.55E, 10CFR-50.55E, S83-39, SVP-0163-83, SVP-163-83, NUDOCS 8312190182 | |
| Download: ML20082U811 (2) | |
Text
_
~
DA B PUBLIC SERVICE December 9, 1983 S83-39 INDIANA SVP-0163-83 S. W. Shields Senior Vice President -
Nuclear Divisior' Mr. James G. Keppler, Docket Nos.:
STN 50-546 Regional Administrator STN 50-547 U. S. Nuclear Regulatory Commission Construction Permit Nos.:
Region III CPPR - 170 799 Roosevelt Road CPPR - 171 Glen Ellyn, Illinois 60137 Marble Hill Nuclear Generating Station - Units 1 and 2
Dear Mr. Keppler:
On August 9,1983, Mr. S. J. Brewer of Public Service Company of Indiana, Inc. (PSI) notified your office of a potentially reportable item as required by 10 CFR 50.55(e). This item concerns inadequate penetration (effective throat) of flare bevel welds.
This condition may affect numerous cable tray supports constructed to date.
If the tube steel to support welds of these cable tray supports have inadequate penetration, the welds may not be able to withstand their design basis loading.
PSI is currently working to revise necessary drawings and contractor procedures to prevent recurrence of the subject problem.
PSI is also preparing a program to address the quality of past flare bevel welding.
The program results will be reviewed and corrective actions taken, if necessary.
This letter is intended to fulfill the requirements of an interim report under the provisions of 10 CFR 50.55(e). A further report will be filed on or before May 11, 1984.
If you have any questions regarding this matter, please contact me at your convenience.
Sincerely
,/
8312190182 831209
^/-
DR ADOCK 05000
, S. W. Shields g
SWS/LGY/bak 1h t c P. O. Box 190, New Washington, Indiana 47162 812. 289.3000
senvice wouWA l
Letter:
-J. G. Keppler December 9, 1983 S83-39 SVP-0163-83 cc: Director of Inspection and Enforcement U.- S. Nuclear Regulatory Comission Washington, D. C.
20555 J. E. Konklin J. F. Schapker i
f l
1