Forwards Response to Forwarding IE Bulletin 83-06 Nonconforming Matls Supplied by Tube-Line Corp. Tube-Line Supplied Matl Installed in Unit 3 Auxiliary Feedwater Sys
ML20082K853
Person / Time
Site: Oconee  
Issue date: 11/18/1983
From: Tucker H
DUKE POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-SSINS-6820 IEB-83-06, IEB-83-6, NUDOCS 8312050320
Download: ML20082K853 (3)


Text

S" 9

a

': DUKE POWER GOMPJLNY A'

P.O. BOX 33180 GHAMLOTTE,' NM.'28242 HAL H. TUCKER

retepuoy, 3 3.?.' 28No#6),ergly, 1983 Mr. James P. O'Reilly, Regional Administrator U. S. Nuclear Regulatory Commission Region 11 101 Marietta. Street, NW, Suite 2900 Atlanta, Georgia 30303 Re: Oconee Nuclear Station Docket Nos. 50-269, -270, -287 IE Bulletin 83-06

Dear Sir:

In response to NRC letter dated July 22, 1983 which transmitted IE Bulletin 83-06 concerning non-conforming materials supplied by Tube-Line Corporation, please find attached a response for Oconee Nuclear Station.

I declare under penalty of perjury that the information contained herein is correct to the best of my knowledge as executed on November 18, 1983.

Very truly yours, C

d 4

s Hal B. Tucker RLG/php Attachment cc: Document Control Desk U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Mr. J. C. Bryant NRC Resident Inspector Oconee Nuclear Station Mr. John F. Suermann l-Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555 8312050320 831118 DR ADOCK 05000269 fg{

k PDR ll1

i

')

s-JP0/HBT/RLC November 18, 1983 Duke Power Company Oconee Nuclear Station Response to IE Bulletin 83-06 Duke Power has reviewed the information provided by the Bulletin and has determined that the only Tube-Line material supplied to Oconee is installed in the Unit 3 Auxiliary Feedwater System.

This Bulletin requires the following actions for ASME Code materials furnished by Tube-Line which are installed in safety-related systems in operating plants.

Provide a list of the T-L supplied materials and identify the systems a.

in which the materials are installed.

- 12, three inch raised face, weldneck flanges

- 4, six inch weldend caps

- 2, six inch tees All of these materials are carbon steel and are installed in the Oconee Unit 3 auxiliary feedwater system header which is connected to the steam generators.

b.

Implement a program as discussed in 2b or 2c of the Bulletin.

Duke has completed an analysis that demonstrates the stresses in the auxiliary feedwater system do not exceed the yield strength of the flange material.

Samples from the same heat numbers as those installed at Oconee show that the physical properties of the caps and tees are equal to or better than the ASME code requirements.

The flanges were specified as ASME SA-105.

The requirements for yield strength at ambient temperature is 36 KSI and tensile strength at ambient temperature is 70 KSI. The worst case sample tested by Babcock and Wilcox or Tube-Line exhibited a yield strength of 31.1 KSI and a tensile strength of 59.8 KSI.

The stress analysis of the Auxiliary Feedwater System was based on the Code of Record for Oconee 3, i.e., 1967 USAS B 31.1 Code. There are six three inch WNRF flanges per steam generator. The flanges are located on the risers that lead to the Auxiliary Feedwater Steam Generator Nozzles.

Three methods of analysis were utilized to evaluate the subject flanges.

First, the 1967 Edition of the USAS B 31.1 Code was investigated for flange acceptability requirements.

Second, the 1974 ASME Code Sections III and VIII were utilized to perform an evaluation of the subject flanges.

Third, the 1980 ASME Code Section III was utilized to perform an evalua-tion of the subject flanges.

Based on the results of this analysis, the auxiliary feedwater system is considered to be operable.

i

i 7

JP0/HBT/RLG Wovember 18, 1983 During the spring 1984 Oconee 3 refueling outage, the items of concern will be checked to verify that appropriate material standards are met.

Items which do not meet the specifications will be replaced.