Amend 106 to License NPF-49,relaxing Setpoint Tolerance for Pressurizer Safety Valves & Main Steam Safety Valves from +1% to +3%
ML20081H045
Person / Time
Site: Millstone Dominion icon.png
Issue date: 03/17/1995
From: Mckee P
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20081H049 List:
References
NUDOCS 9503240076
Download: ML20081H045 (6)


Text

.

g,gmaug pe 4

UNITED STATES s-

{

NUCLEAR REGULATORY COMMISSION M

2 WASHINGTON, D.C. 20565 4001 4

9.....,o NORTHEAST NUCLEAR ENERGY COMPANY. ET AL.

QOCKET NO. 50-423

,ilU. STONE NUCLEAR POWER STATION. UNIT NO. 3

]

AMENDMENT TO FACILITY OPERATING LICENSE

+

Amendment No.

106 License No. NPF-49 3

1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Northeast Nuclear Energy Company, et al. (the licensee), dated August 4,1994 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will te conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable l

requirements have been satisfied.

i 9503240076 950317 PDR ADOCK 05000423 P

PDR,

, l 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated _in.the attachment to this license amendment, and paragraph 2.C.(2)lof Facility Operating License No. NPF-49 is hereby 1

amended to read as follows:

(2)

Technical Specifications The Technical Specifications contained in Appendix A, as revised i

through Amendment No. 106, and the Environmental Protection Plan contained in Appendix B, both of which are attached hereto are hereby incorporated in the license. The licensee shall l

operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of the date of its issuance, to be implemented within 30 days of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION L

y/

JF' Phillip F.'McKee, Director Project Directorate I-4 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical l

Specifications j

Date of Issuance: flarch 17, 1995 i

t e

l r

ATTACHMENT TO LICENSE AMENDMENT NO.106 FACILITY OPERATING LICENSE NO. NPF-49 DOCKET NO. 50-423 Replace the following pages of the Appendix A Technical Specifications with the enclosed pages. The revised pages are identified by amendment number and contain vertical lines indicating the areas of change.

Remove Insert L

3/4 4-9 3/4 4-9 3/4 4-10 3/4 4-10 3/4 7-3 3/4 7-3

o REACTOR COOLANT SYSTEN 3/4.4.2 SAFETY VALVES SHUTDOWN LIMITING COMITION FOR OPERATION 3.4.2.I A minimum of one pressurizer Code safety valve shall be OPERABLE with a lift setting

  • of 2500 psia i 3%.**

l i

APPLICABILITY: NODE 4.

ACTION:

With no pressu.-izer Code safety valve OPERABLE, immediately suspend all operations involving positive reactivity changes and place an OPERABLE RHR loop into operation in the shutdown cooling mode.

i I

SURVEILLANCE REQUIRENENTS 4.4.2.I No additional Surveillance Requirements other than those required by Specification 4.0.5.

I i

l

  • The lift setting pressure shall correspond to ambient conditions of the valve at nominal operating temperature and pressure.

i

    • The lift setting shall be within i I% following pressurizer Code safety valve testing.

NILLSTONE - UNIT 3 3/4 4 9 Amendment No.106 aan

f REACTOR COOLANT SYSTEN l

OPERATING LIMITING C0WITION FOR OPERATION 3.4.2.2 All pressurizer Code safety valves shall be OPERABLE with a lift setting

  • of 2500 psia i 3%.**

APPLICABILITY: MODES 1, 2, and 3.

ACTION:

s With one pressurizer Code safety valve inoperable, either restore the inoperable valve to OPERABLE status within 15 minutes or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in at least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

i f

i t

SURVEILLANCE REQUIREMENTS 4.4.2.2 No additional Surveillance Requirements other than those required by i

Specification 4.0.5.

  • The lift setting pressure shall correspond to ambient conditions of the valve at nominal operating temperature and pressure.
    • The lift setting shall be within i 1% following pressurizer Code safety valve testing.

MILLSTONE - UNIT 3 3/4 4-10 Amendment No.106 0275 r

f

j

.e:

L'E 3

TABLE 3.7-3' f

STEAM LINE SAFETY VALVES PER LOOP VALVE NUMBER LIFT SETTING * (13%)**

ORIFICE SIZE tan u 1

RV22A 1185 psig 16.0 square inches l

RV23A 1195 psig 16.0 square inches.

RV24A 1205 psig 16.0 square inches i

RV25A 1215 psig 16.0 square inches j

-RV26A 1225 psig 16.0 square inches l

LQQP 1 RV228 1185 psig 16.0 square inches RV23B 1195 psig 16.0 square inches i

RV24B 1205 psig 16.0 square inches RV258 1215 psig 16.0 square inches RV268 1225 psig 16.0 square inches

]

LOOP 3 j

i RV22C 1185 psig 16.0 square inches RV23C 1195 psig 16.0 square inches RV24C 1205 psig 16.0 square inches RV25C 1215 psig 16.0 square inches RV26C 1225 psig 16.0 square inches LOOP 4 RV220 1185 psig 16.0 square inches RV23D 1195 psig 16.0 square inches RV24D 1205 psig 16.0 square inches

)

RV25D 1215 psig 16.0 square inches RV26D 1225 psig 16.0 square inches

  • The lift setting pressure shall correspond to ambient conditions of the valve at nominal operating temperature and pressure.
    • The lift setting shall be within i 1% following main steam line Code safety valve testing.

NILLSTONE - LNtIT 3 3/4 7-3 Amendment No. 106 een

-