Requests Exemption from App R to 10CFR50.48 Requirement for Addl Fixed Fire Suppression Sys in Control Room Area. Best Fixed Fire Suppression Sys for Control Room Area Already Installed
ML20081F536
Person / Time
Site: North Anna  Dominion icon.png
Issue date: 10/31/1983
From: Stewart W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To: Harold Denton, John Miller
Office of Nuclear Reactor Regulation
References
609, NUDOCS 8311030122
Download: ML20081F536 (1)


Text

_ _.

VIRGINIA ELECTRIC AND PowEn CourANy Ricuxoxn,VIROINTA 20261 W.L.Srawrar vaca Passins=,

October 31, 1983 Nucs.aam OPERAT ONs Mr. Harold R. Denton, Director Serial No. 609 Office of Nuclear Reactor Regulation N0/JHL:acm Attn:

Mr. James R. Miller, Chief.

Docket Nos. 50-338 Operating Reactors Branch No. 3 50-339 Division of Licensing License Nos. NPF-4 U. S. Nuclear Regulatory Commission NPF-7 Washington, D. C. 20555 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNIT NOS. 1 AND 2 EXEMPTION REQUEST TO 10CFR50 APPENDIX R The Virginia Electric and Power Company requests an exemption from Appendix R to 10CFR50.48, paragraph III.G.3 from the requirement to add additional fixed fire suppression systems in - the Unit I and Unit 2 control room area at the North Anna Power Station. The installed Halon 1301 System is provided for the underfloor area of the control room. This Halon System is an automatic system ind provides adequate fire protection for control cables and helps maintain safe shutdown capability.

In addition, there is an installed standpipe and hose rack just outside the control room area to provide fire fighting capability. Portable equipment is also available for extinguishing smoldering fires.

In view of the above, and the fact the NRC Staff granted Surry Power Station relief from the requirement to add fixed fire suppression systems in the control room area because Surry has installed hose standpipes and racks outside the control room area, the best fixed fire suppression system for the control room area is already installed at North Anna and additional fixed fire suppression systems would not enhance fire protection safety above that already provided.

I Very truly yours, 8311030122 831031

/

~

DR ADOCK 05000 38 W. L. Stewart cc:

Mr. James P. O'Reilly Regional Administrator Region II k

Mr. M. B. Shymlock p0 NRC Resident Inspector