ML20080S739

From kanterella
Jump to navigation Jump to search
Provides Followup Response to IE Bulletin 83-03, Check Valve Failures in Raw Water Cooling Sys of Diesel Generators, Item 5.Detailed Insp of Svc Water Check Valve Internals Showed Traces of Rust on Seating Surfaces
ML20080S739
Person / Time
Site: Cooper 
Issue date: 09/30/1983
From: Kuncl L
NEBRASKA PUBLIC POWER DISTRICT
To: Jay Collins
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
REF-SSINS-6820 IEB-83-03, IEB-83-3, LQA8300230, NUDOCS 8310180471
Download: ML20080S739 (2)


Text

-

GENERAL OFFICE S

Nebraska Public Power District

  • "?EeMse"%;Ts*"^eet *** """

LQA8300230 September 30, 1983 Mr. John T.

Collins Regional Administrator U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive Suite 1000 Arlington, Texas 76011

Subject:

Response to IE Bulletin No. 83'-03

" Check Valve Failures in Raw Water Cooling Systems of Diesel Generators"

Dear Mr. Collina:

This report is the follow-up response to item 5 of the subject Bulletin.

The four service water check valves referenced in our June 10, 1983 letter to the Nuclear Regulatory Commission are SW-35CV, 36CV, 37CV and 38CV. The valves were disassembled and inspected and the overall results indicated the valves had negligible wear and were functioning,

properly.

Detailed inspection of thu valve internals showed the seating surfaces and hinge pins had some minor pitting and traces of rust. The discs and hinge pins were dye penetrant tested for defects.

None were found.

The tolerances between the hinge pins and hinges were measured and found.to be normal. The valves were reasscmbled and returned to oper-ation.

As indicated in our initial response letter, all four check valves have been placed on a three year Inservice Test schedule to assure continued valve integrity.

Sincerely, I

L. C. Kt.nc1 Assistant General Man ver-Nuclear JDW:JRF:cmk Original:

Document Control Desk U.S. Nuclear Regulatory Commission Wast.ington, DC 20555 ff u

,I 8310100471 830930 PDR ADOCK 05000298 0

PDR

-o Mr. Jol-t T. Collins September 30, 1983 Page 2 STATE OF NEBRASKA )

) ss PLATTE COUNTY

)

L. G. Kuncl, being first duly sworn, deposes and says that he is an authorized representative of the Nebraska Public Power District, a

public corporation and political subdivision of the State of Nebraska; that he is duly authorized to vubmit this information on behalf of Nebraska Public Power District; and that the statements contained herein are true to the best of his knowledge and belief.

[

~

~

G. Kunc Subscribed in my presence and sworn to before me this sod _ day of September, 1983.

Cc&wo 7D. Mfa NOTARY #UBllIC

} h

,s.

s s

owessa i e

MT i EXP!RES fk 5 4