I GENERAL OFFICE Nebraska Public Power District

" ' " ""sso"~*s#f"^A*e^ """*"

LQA8300027 June 10,1983 Mr. John T. Collins Regional Administrator U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive Suite 1000 Arlington, Texas 76011

Dear Sir:

This report is the initial response to IE Bulletin No. 83-03:

Check Valve Failures In Raw Water Cooling Systems of Diesel Generators.

Cooling water to the diesel generators is supplied by the normally operating service water system. The check valves identified for an initial valve integrity verification and for inclusion in the plant Inservice Test (IST) program are SW-35CV, 36CV, 37CV and 38CV. All four valves will be disassembled and inspected during the present refueling outage.

The valves will also be opened and inspected on a three year IST schedule to assure continued valve integrity.

The service water check valves are 10 inch,150 lb. swing check valves manufactured by Anchor Valve Company.

The valves are installed in vertical piping runs and normally operate with full flow through the valves. There have been no previous failures of these valves.

Sincerely, I

W J. M. Pilant Division Manager of

  • Licensing & Quality Assurance JMP:JRF:rt13/1 l

cc:

U. S. Nuclear Regulatory Commission Attention: Document Control Desk f

l-

'f 8308030290 830610 PDR ADOCK 05000298 P

PDR

Mr. John T. Collins Page 2 June 10, 1983 STATE OF NEBRASKA)

)ss PLATTE COUNTY

)

Jay M.Pilant, being first duly sworn, deposes and says that he is an authorized representative of the Nebraska Public Power District, a public corporation and political subdivision of the State of Nebraska; that he is duly authorized to submit this information on behalf of Nebraska Public Power District; and that the statements contained herein are true to the best of his knowledge and belief.

LML Nay~ M. Pilant Subscribed in my presence and sworn to before me this /()/Q day of fy g

, 1983.

cAo 7n Efa NOTARY PlyBLJC s -n j-i 3

NOTARY k

/j. ! COMMISSION I i'k i LXPHfES lk

.1 s

e h

1

..