l ATTACHMENT 2 UMERICK GENERATING STATION 1

1 UNITS 1 AND 2 j

Docket Nos.

50-352 50-353 Ucense Nos. NPF-39 NPF-85 j

TECHNICAL SPECIFICATIONS CHANGE REQUEST j

l No. 94-02-0 1

UST OF AFFECTED PAGES 4

UNIT 1 UNIT 2 3/4 3-87 3/4 3-87 9503090307 950301 PDR ADOCK 05000352 P

PDR

TABLE 4.3.7 5-1 ACCIDENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS y

~

E CHANNEL CHANNEL INSTRUMENT CHECK CALIBRATION n

i 1.

Reactor Vessel Pressure M

R 2.

Reactor Vessel Water Level M

R'

~

3.

Suppression Chamber Water Level M

R' 4.

Suppression Chamber Water Temperature M

R 5.

Suppression Chamber Air Temperature M

R.

I 6.

Primary Containment Pressure M

R 7.

Drywell Air Temperature M

R 8.

Drywell Oxygen Concentration Analyzer

'M Q#

9.

Drywell Hydrogen Concentration Analyzer

.M Qe 10.

Safety / Relief Valve Position Indicators.

M R

11.

Primary Containment Post LOCA Radiation Monitors M

R**

12.

North Stack Wide Range Accident Monitor ***

M RL t

13.

Neutron Flux M

R

  • Using calibration gas containing:

Seven volume percent hydrogen, balance nitrogen.

    • CHANNEL CALIBRATION shall consist of an electronic calibration of the channel, not-including the detector, for range decades above 10 R/h and a one point calibration' check of the detector below 10 R/h with an installed or portable gamma source.
      • High range noble gas monitors j
  1. Using calibration gas containing:

Seven volume per::ent oxygen, balance nitrogen.

l l

i

TABLE 4.3.7.5-1 ACCIDENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS C

E CHANNEL CHANNEL 5

INSTRUMENT

_GHECK CALIBRATION n

1.

Reactor Vessel Pressure M

R i

2.

Reactor Vessel Water Level M

R 3.

Suppression Cnamber Water Level M

R 4.

Suppression Chamber Water Temperature M

R 5.

Suppression Chamber Air Temperature M

R 6.

Primary Containment Pressure M

R 7.

Drywell Air Temperature M

R 8.

Drywell Oxygen Concentration Analyzer M

Qf

?.

Drywell Hydrogen Concentration Analyzer M

Q*

10.

Safety / Relief Valve Position Indicators M

R 11.

Primary Containment Post LOCA Radiation Monitors M

R**

12.

North Stack Wide Range Accident Monitor ***

M R

13.

Neutron Flux M

R II

  • Using calibration gas containing:

Seven volume percent hydrogen, balance nitrogen.

l

    • CHANNEL CALIBRATION shall consist of an electronic calibration of the channel, not including the detector, for range decades above 10 R/h and a one point calibration check of the detector below 10 R/h with an 3

installed or portable gamma source..

      • High range noble gas monitors
  1. Using calibration gas containing:

i Seven volume percent oxygen, balance nitrogen.