ML20080N163

From kanterella
Jump to navigation Jump to search
Interim Deficiency Rept Re Gould-Rundel Type SS-3 Handswitches W/Binding Cams.Initially Reported on 830824.AE Evaluating Concern.Next Rept Will Be Submitted by 840120. Switches Subj of IE Info Notice 83-42
ML20080N163
Person / Time
Site: Wolf Creek 
Issue date: 09/23/1983
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Seidle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, IEIN-83-42, KMLNRC-83-122, NUDOCS 8310040386
Download: ML20080N163 (1)


Text

-

KANSAS GAS AND ELECTRIC COMPANY WE ELECMC CNWl

[

r y

A gtp 2 61983 sta==t norsve-wma apasiot=r. nuctaae i \\ _ --

L_

September 23, 1983 Mr. W.C. Seidle, Chief Reactor Projects Branch 2 U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 KMLNRC 83-122 Re: Docket No. STN 50-482 Subj : Potential 10CFR50.55 (c) Report -

Gould-Rundel Handswitches

Dear Mr. Seidle:

This letter provides an interim report on a potential 10CFR50.55(e) matter concerning Gould-Rundel handswitches. This item was initially reported by Mr. Gene Rathbun of Kansas Gas and Electric Company to Mr. William Johnson of the Nuclear Regulatory Commission, Region IV, on August 24, 1983.

During startup testing of the "D" containment cooling fan, it was discovered that the handswitch used to control the fan motor did not operate properly. The part involved is a Gould-Rundel type SS-3 hand-switch and is mounted at the motor control center for the fan.

Further investigation revealed that the plastic cams inside the switch, which open and close the contact, were binding. The binding was, in part, a result of bending and twisting of a plastic shaft which operates the cams. Therefore, the contacts would not open or close when the switch was manipulated.

The SNUPPS design utilizes four containment cooler fans and all have the same type of control switch. Therefore, the other three switches were checked and they exhibited the same problem as described above.

Through discussions with Gould, it was further determined that these switches are the same as the switches that were the subject of I&E Information Notice 83-42 in which a similar problem was discussed.

Our Architect / Engineer is evaluating the identified concern and the status of this evaluation will be reported to you on or before January 20, 1984.

In the interim, please direct any questions concerning this subject to me or to Mr. Otto Maynard of my staff.

0310040386 830923 Yours very truly,

< f/

j/ /

PDR ADOCK 05000482 S

PDR

//

N GLK:bb gg/

y f cc: RCDeYoung j

WSchum/ASmith 201 N. Market - Wichita, Kansas - Mail Address: RO. Box 208 i Wchita, Kansas 67201 - Telephone: Area Code (316) 261-6451