ML20080M718

From kanterella
Jump to navigation Jump to search
Ro:On 820623,during Diesel Fire Pump Weekly Surveillance, Diesel Fire Pump Ob Observed to Have Pegged High Temp Indication.Open Svc Water Tie Valves Maintained Fire Protection Sys.Caused by Failed Solenoid Operated Valve
ML20080M718
Person / Time
Site: LaSalle Constellation icon.png
Issue date: 07/06/1982
From: Holyoak R
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20080M708 List:
References
NUDOCS 8402210259
Download: ML20080M718 (1)


Text

o .

f.;qn.;.

r~ ~ . ;3. gw. ;

gi9. .Q.U., f", --I

  • Commonwealth Edison

' . 7.4r9f1 f .W@.', . LaEa .

.c- Ce.:n:y "i.na" pcutt *1Nu Ecytear22 Steven .

rm . MkiM,1 M 2'. > d7,, f.ta semes, mec:s 615:1 fT~~ ' " . 4;. Te!e:~.cne 815/257 6761 r,

July 6, 1982 Mr. James G. Keppler Regional Administrator Directorate of Regulatory Operations, Region ill U. S. Nuclear Regulatory Com:nission 799 Remsevelt Road Glen Eilyn, Illinois 60137 a

Dear Sir:

This special report is submitted in accordance with LaSalle Unit 1 Operating License NPF-II, Appendix B, Technical Specifications 3.7.5.1 and 6.6.c.

On June 23,1982 et 0200, during a diesel fi re pump weekly survel11ance (LOS-FP-W2), the OB Diesel Fire Pump was observed to have a " pegged high" temcerature indication. As a result, the diesel was shutdown and taken out of service to protect the equipment from further damage.

The OA Diesel Fire Pump was also inoperative and out of service at that time due to fuel oil line repairs.

Both diesels were declared inoperative in accordance with technical specification 3.7 5.1.

While both dieseis were inoperative, backup service water tie valves were verified open, maintaining fire protection at all t i ces .

. The Diesel Fire Pump OB overheated as a result of a failed cooling water solenoid operated valve. Upon investigation, the coil of the solenoid operated valve was found to be burnt. The diesel did not receive sufficient cooling water and consequently overheated Operability was restored to the OA Diesel Fire Pump on June 23, 1982 at 1510. -

The fuel oil leak was repaired by installing a replacenient fuel line. The OB Diesel Fire Pump was returned to operability on June 28, 1982, at 1756 af ter installation of a new coil and a complete diesel inspection. Post

- maintenance revealed no degredation to the diesel. Both Diesel Fi re Pumps

- were test run in accordance with LOS-FP-W2 before operability was declared.

8402210259 840209 ,

i PDR ADOCK 05000373 g PDR /

i: R. H. Ho , ak Station perintendent LaSalle County Station RhH/0W/ gen u

- ~ - - - - - __ ___ ___ .

. fr.

  • Ccmmonwealth I-dC'. '

-s t :: - '..: e . rEdison

.r; :: y .: . E c i ::,-

.-1s g- /

't.

t.':_ : - s et.  : c i :e -

,Q i 4 *}. it.  : ~ s 5 1. M ' 5 ~i Se:terber 7, 1953 James G. Keppler Regionel Administrator '

Region lil U.S. Nuclear Regulatory Conmission 799 Roosevelt Road Glen Ellyn, IL 60137 ,

Dear Sir:

This Special Recort i s submi tted in accordance wi th LaSalle Uni t 1 Coerating License NDF-11, A::pendix A, Technical 50eci fication 3.7.3.1 and 6.6.c.

On Augus: 27, 1953, the OA Diesel Fi re Pur.p was being operated as a pre requisite for the SDR (E-ergency Power Redundancy) test. While running, the coling line

~or the righ; angle drive broke causing the diesel to be shut down and decla red It had inope rab le . The OS Diesel Fire Pump was also inocerable at the tire.

been taken out of service voluntarily for maintenance to make receirs on the re l i e f va l ve .

in accordance with the Action Statement of Techn: cal Speci fi ca tion 3.7.5.1, a

hene ct' #ication was rade wi thin 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of :he event and a teleco::y was sent tc con'irm the conversation.

~ ! so , .shii e toth d iesel s we re inoperative , back uo se rvice wa:e r :le valves

.s e re veri fi ed cpen , maintai ning fi re protection at all times.

erati;ity was restored to one ciesel # ire cum: by 1200 en Augus: 27, 19c3. The

- +

se:cnd c'esei fi re cump was ret.tored by iL30 .cugustFi27, 1933 in accordance wi th re eurp Survei11ance).

the sati s f actory ::e rf ormance of LOS-; P-W' . (Di esel

~

JeL cM%d v

G. J. Diederich

, Superintendent

,' LaSalle County Station GJD/JSK/GVira Enclosure ,

cc: Director of Inscection & Enforcement information & Progra- Control Director of .anage M .ent U.S No.C Dece-e,t Managenen: Sranch IN:C-Feceres Center F i i e c.' O.C