- ,o PHILADELPHIA ELECTRIC COMPANY PUBLIC SERVICE ELECTRIC AND GAS COMPANY DELMARVA POWER AND LIGHT COMPANY ATLANTIC CITY ELECTRIC COMPANY DOCKET NO. 50-277 PEACH BOTTOM ATOMIC POWER STATION, UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 91 License No. DPR-44 1.
The Nuclear Regulatory Commission (the Commission) has found that:
I A.
The application for amendment by Philadelphia Electric Company, et al. (the licensee) dated May 26, 1982, complies with the standards and-requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in confermity with the application, i
the provisions of the Act, and the rulas and regulations of the Commission; C.
There is reasonable assurance (f) that the activities authorized
.by this amendment can be conducted without endangering the health and safety of the public, and (11) that such activities will be conducted in compliance with the Commir, ion's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of thid amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Spec-ifications as indicated in the attachment to this license amendment and paragraph 2.C.(2) of Facility Operating License No. DPR-44 is hereby amended to read as follows:
Technical Soecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 91. are hereby incorporated in the license PEC0 shall operatt the facilit accordance with the Technical Specifications. y in 8402170524 840210 PDR ADOCK 05000277
.P PDR
9 3.
This license amendnent is effective as of the date of its issuance.
FOR THE NUCLEAR REGULATORY COMMISSION
/.
.4'ohn F. Stolz, Chie
[0phrating Reactors Branch #4 Givision of Licensing
Attachment:
Chances to the Technical Specifications Date of Issuance: February 10, 1984
?
I l
i l
L l
w
i ATTACHMENT TO LICENSE AMENDMENT NO. 91 FACILITY OPERATING LICENSE NO. DPR-44 DOCKET N0. 50-277 i-l
Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by Amendment number and contain a vertical line indicating the area of change.
Remove.
Insert L
73 73 74a 74a r-,,.i.......
,,i,,,,,..,.
Ueit 2
>j-TABLE 3.2.C 8,
INSTFUMEllTATION TilAT lt41TI ATES CCHTHOL ROD ULOCitS l5 i'*
Hiulmum iso.
Instrument trip Level setting.
t# umber o't Instrument Action of operable Channels Provideel P
ins trusesst by Design Channels rer y
P Trap system M
4 APSH Upscale (Flow
<- (0. 66H e 4 2-0. f.; 6&W) x 6 Inst. Channels (10) niased)
~
EliE__.
~
p HFL?U (2) g 4
APHH Upscale (Startup
$12%
6 Inst. Channels (10)
Hode) 4 APNH townac.sle
%2.5 indicated on 6 Inst. Channels
(.10) y scale y
1 (7) liod 210cic Honitor S (0.66W'41 -0.6 6AW) x 2 Inst. Channels (1)
(Flow Islased)
,_E[LP_,,_
MFLPD (2) m y (7)
Hod BlocP. Monitor 22 5 indicated on 2 Isist. Channels (1) l 3
Downscale scale 6
IHH ccwinacale (3) 22.5 indicated on 8 Inst. Channels (10) scale 6
1pH cetector not in (a) 8 Inst. Channels (10) startup Position 6
IDH Upscale
$108 indicated on 8 InJt. Channels (10) scale 2 (5)
Salt Uetector not in (4) 4 Inst. Channels (1)
Startup Position 2 (5) (6J SkN Upscale
$105 counts /sec.
4 Inst. Channels (1) 1 Scr.am Discharge Volune 1 25 gallons 1 Inst, cliannel (9) liigh Level ____
f FBAPS NOTES FOR TABLE 3.2.C (Cont.)
9 If the number of operable channels is less than recuired by the minimum operable channels per trip function recuirement, place the inoperable channel in the tripped condition within one hour.
This note it applicable in the "Run" mode, "Startup" mode and
" Refuel" mode if more than one control rod is withdrawn.
10.
For the Startup (for IPM rod block) and the Run (for APPM rod block) positions of the Paactor Mode Selector Switch and with the number of ~ OPERABLE channels:
a,_
One less than required by the Minimum OPERABLE Channels per Trip Function requirement, restore the inoperable' channel to OPERABLE status within 7 days or place the inoperable channel in the tripped condition within the neXt hour.
b.
Two or more less than required by the Minimum OPERABLE Channels per Trip Function requirement, place at least one inoperable channel in the tripped condition within one hour.
Amendment tio. ES,91
- 74a -
jns Nog'o UNITED STATES g
NUCLEAR REGULATORY COMMISSION e.
{g
,E WASHINGTON, D. C. 20:35 5
/
PHILADELPHIA ELECTRIt"'COMDANY PUBLIC SERVICE ELECTRIC AND GAS. COMPANY DELMARVA POWER AND LIGHT COMPANY ATLANTIC CITY ELECTRIC COMPANY DOCKET NO. 50-278 PEACH BOTTOM ATOMIC POWER STATION, UNIT NO. 3 AMENDFENT TO FACILITY OPERATING LICENSE Amendment No. 93 License No. DPR-56 1.
The Nuclear Regulatory Commission (the Comission) has found that:
A.
The application for amendment by Philadelphia Electric Company, et al. (the licensee) dated May 26, 1982, complies with the standards and requirements of the Atomic Energy Act of 1954,
,5 as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in confomity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (11) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the coc=on defense and security or to the health and safety of the public; and I
E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Spec-ifications as indicated in the attachment to this license amendment and paragraph 2.C.(2) of Facility Operating License No. DPR-56 is hereby amended to read as follows:
Techrical Soecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 93, are hereby incorporated in the license. PEC0 shall operate the 'acility in accordance with~ the Technii:al Specifications.
3.
This license amendment is effective as of the date of its issuance.
FOR THE NUCLEAR REGULATORY C0!tilSSION J n F. Stolz Chie perating Recctors Branch #4
~
ivision of Licensing
Attachment:
Changes to the Technical Specifications Date of Issuance: February 10, 1984 e
9
~
' ATTACHMENT 19 I ' CENSE AMENDMENT NO. 93 FACILITY OPERATING LICENSE NO. DPR-56 p0CKETNO.50-278 Replace the.following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by Amendment number and contain a vertical line indicating the arci of change.
Remove.
Insert 73-73 74a 74a
m E
Unit 3
,e it.
TABLE 3,2,C H_
InsTsunstrTATioH Tal4T INITI A1ES CCHTHOL ROD ULOCMS ning pg.
Instrument y
of operatsle trip Level setting uussber of Instrument Action Instrument Channels Provideti u
Channels Per U
by Design Trap Systee m
P 4
APBH Upscale (Flou y
glamed) 4 (0.66W e 4 2-0. 6 MW) x 6 Inst. Channels (10) 7
,,,,[li g__
MFLPD (2) y 4
APHH Upscale (Startup
$ 12 %.
e Mode) 6 Inst. Channels I
(10) 4 APBH Eownscale l
>2.5 indicated on 6 Inst. Channels (10) scale y (7)
Hod 3]ock Monitor 5 (0.66W o 41 -0. 6 6AW) x (Flow Blased) 2 Inst. Channels (1)
Nod Block Honitor 22.5 indicated on Downscale 2 Inst. Channels (1) scale 6
IRH ccwnscale. (3) 22.5 ludicated ou 6 Inst. Channels (10) scale 6
inn cetector not in (a)
Startup Position 8 Inst. Channels (10) 6 1RH Upscale 1108 indicated on B InJt, Channels (10)!
scale 2 (5)
BRl1 Detector not in (II)
Startup Position 34 Inst. Channels (g) 2 (5) (6j SHH Upscale
$10s counts /sec.
4 Inut. Channels (1) 1 Scr.am Discharge Volui.ie 125 gallons 1 Inst. Channel (9) liigh Level PBAPS NOTES FOR TABLE 3.2.C (Cont.)
9.
If the number of operable channels is less than required by the minimum operable channels per trip function requirement, place the inoperable channel in the tripped condition within one hour.
This note is applicable in the "Run" mode, "Startup" mode and
" Refuel" mode if more than one control rod is withdrawn.
10.
For the Startup (for IRM rod block) and the Run (for APRM rod block) positions of the Reactor Mode Selector Switch and with the number of OPERABLE channels:
a.
One less than required by the Minimum OPERABLE Channels per Trip ' unction requirement, restore the lno'perable' F
channel to OPERABLE status within 7 days or place the inoperable channel in the tripped condition within the next hour.
b.
Two or more less than required by the Minimum OPERABLE Channels per Trip Function requirement, place at least one inoperable channel in the tripped condition within one hour.
Amendment flo. $$, 93
- 74a -