ML20080M008

From kanterella
Jump to navigation Jump to search
Annual Rept of Occupational Radiation Exposure,1994
ML20080M008
Person / Time
Site: Monticello 
Issue date: 12/31/1994
From:
NORTHERN STATES POWER CO.
To:
Shared Package
ML20080M002 List:
References
NUDOCS 9503030086
Download: ML20080M008 (4)


Text

,,, _

l ',.s i p_:

i ATTACHMENT-1 R

MONTICELLO NUCLEAR GENERATING PLANT ANNUAL REPORT OF. OCCUPATIONAL RADIATION EXPOSURE E

1994 e.

I I

'i l

c h

3 l

9503030086 950227 PDR ADOCK 05000263 R

PDR

+

I-PMETS-Numb 2r of Porronn31 cnd Man-R m Pcg3 1 02/23/95 by Work cnd Job Functiona (1994) of 2 13:45 Monticello Nuclear Generating Plant Number of Persons >.100 Rem Total Man-Rem W;rk add Job Function Station Utility Contract Station Utility Contract ISI Operators 0

0 0

0.716 0.000 0.000 Maintenance 0

21 28 0.110 7.964 22.023 Supv & Engr 1

1 36 0.498 0.522 26.919 Health Physics 0

0 0

0.240 0.000 0.102 Instr & Control 0

0 0

0.005 0.000 0.000 Securig-0 0

0 0.000 0.000 0.000 Routine Maintenance Operators 4

0 0

1.449 0.000 0.000 Maintenance 27 114 25 24.032 69.856 8.016 Supv & Engr 30 6

10 11.897 3.363 3.826 Health Physics 18 9

13 9.905 2.120 8.857 Instr & Control 9

1 0

6.039 0.106 0.000 Security 0

0 0

0.000 0.000 0.000 Operations Operators 43 0

0 28.059 0.000 0.000 Maintenance 26 37 7

5.461 11.313 2.574 Supv & Engr 34 3

3 13.576 1.534 1.974 Health Physics 30 4

9 9.586 1.084 2.296 Instr & Control 9

1 0

3.298 0.109 0.000 Security 0

0 1

0.000 0.000 0.745 R3 fueling Operators 11 0

0 3.702 0.000 0.000 Maintenance 8

22 0

2.410 5.856 0.033 Supv & Engr 3

2 0

0.777 0.350 0.184 Health Physics 5

0 3

1.060 0.050 0.461 Instr & Control 0

0 0

0.121 0.034 0.000 Security 0

0 0

0.000 0.000 0.000 Special Maintenance Operators 0

0 0

0.474 0.000 0.000 Maintenance 3

115 41 1.369 54.361 17.769 Supv & Engr 2

7 12 0.949 1.452 4.859 Health Physics 0

0 1

0.273 0.034 0.379 Instr & Control 0

0 0

0.075 0.001 0.000 Security 0

0 0

0.000 0.000 0.000

- Special inaint6 nance includes:

1.

Outboard MSIV Replacement 2.

RBCCW Insulation Replacement in the Drywell 3.

Air Supply Upgrade to SRVs and MSIVs 4.

Core Spray Crack Repair Project ER_41 PME 95047T

C, PMETS Number of Porconnel and M:n-R0m

. Pegs 2 02/23/95 by Work and Job Functions (1994).

of 2 13:45 Monticello Nuclear Generating Plant Number of Persons >.100 Rem Total Man-Rem Work adB Job Function Station Utility Contract' Station Utility Contract W2ste Shipping / Handling Operators 0

0 0

0.152 0.000 0.000 Maintenance 5

1 0

1.275 0.544 0.000 Supv & Engr 0

0 0

0.115 0.000 0.000 Health Physics 1

0 0

0.643 0.002 0.031 Instr & Control 0

0 0

0.000 0.000 0.000 Security 0

0 0

0.000 0.000 0.000 i

Unassigned Exposure

-0.282 0.154 0.234 t

Sub Totals Operators 58 0

0 34.552 0.000 0.000 Maintenance 69 310 101 34.657 149.894 50.415 Supv & Engr 70 19 G1 27.812 7.221 37.762 Health Physics 54 13 26 21.707 3.290 12.126 4

Instr & Control 18 2

0 9.538 0.250 0.000 Security 0

0 1

0.000 0.000 0.745 Unassigned

-0.282 0.154 0.234 1

Grand Totals 269 344 189 127.984 160.809 101.282

    • INDIVIDUALS MAY BE LISTED UNDER MORE THAN ONE WORK AND JOB FUNCTION l

J s

i i

ER_41 PME 95047T

fp

~'

~

i..

r I

1 Attachment #2 p

'I p

l(

MONTICELLO NUCLEAR GENERATING PLANT ANNUAL REPORT'OF SAFETY / RELIEF VALVE FAILURES AND CHALLENGES

[

1994 j

h This report is made in accordance with NUREG-0737, Item II.K.3.3 and M:nticello Technical Specification 6.7.A.6 and covers the period from' Jcnuary 1 through December 31, 1994.

Failures 1

09/24/94 The topworks (pilot and second stage assembly) associated with safety / relief valve RV-2-71D failed its as-found setpoint test.

The topworks was lifted three times for the test and setpointr of 1145, 1170, and 1147 PSIG were measured in succession for the three lifts.

The acceptance critieria was 1131 PSIG.

This setpoint. test was performed as required and in accordance with the plant's ASME Boiler and Pressure Vessel Code Section XI IST program.

The setpoints of three other safety / relief valve topworks were also as-found tested during the same test as required by the plant's IST program and'all passed.

Challences None.

%