Amends 42 & 33 to Licenses NPF-2 & NPF-8,respectively, Correcting Two Tables Listing Fire Hose Stations & Sprinklers for Unit 2 & Deleting During Shutdown from Surveillance Test for Both Units
ML20080L811
Person / Time
Site: Farley  
Issue date: 02/09/1984
From: Varga S
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20080L814 List:
References
TAC-52181, TAC-52182, NUDOCS 8402170026
Download: ML20080L811 (10)


Text

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _

f* **%i 4

,g UNITED STATES y ) 3 r, g

NUCLEAR REGULATORY CC r.ilSSION J

1 C WASHINGTON, D. C. 20r N.~.~...,/

ALABAMA POWER COMPANY DOCKET N0. 50-348 JOSEPH M. FARLEY NUCLEAR PLANT, UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.42 License No. NPF-2 1.

The Nuclear Regulatory Comission (the Commission) has found that:

A.

The application for amendment by Alabama Power Company (the licensee) dated August 26, 1983, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, as amended, the provisions of the Act, and the regulations of the Commission; C.

There is reasonable assurance: (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specif!:ations as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-2 is hereby amended to read as follows:

8402170026 840209 PDet ADOCK 05000348 P

pm

l

. (2) Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 42, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION e

c

\\b b

b Steven A. Varga, Chief Operating Reactors Bra'

  1. 1 Division of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance: February 9,1984

ATTACHMENT TO LICENSE AMENDMENT NO.

AMENDMENT NO. 42 FACILITY OPERATING LICENSE N0. NPF-2 DOCKET N0. 50-348 Revised Appendix A as follows:

Remove Page Insert Page 3/4 7-84 3/4 7-84

PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) l b.

At least once per 92 days by verifying that a sample of diesel fuel from tha fuel storage tank, obtained in accordance with ASTM-0270-65, is within the acceptable limits specified in Table 1 of ASTM 0975-74 when checked for viscosity, water and sediment.

c.

At least once per 18 months by subjecting the diesel to an inspection j

in accordance with procedures prepared in conjunction with its manufacturer's recommendations for the class of service.

4.7.11.1.3 The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:

a.

At least once per 7 days by verifying that:

1.

The electrolyte level of each battery is above the plates, and 2.

The overall battery voltage is greater than or equal to 24 volts.

b.

At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery.

c.

At least once per 18 months by verifying that:

1.

The batteries, cell plates and battery racks show no visual indication of physical damage or abnormal deterioration, and 2.

The battery-to-battery and terminal connections are clean, tight, free of corrosion a7d coated with anti-corrosion material.

FARLEY-UNIT 1 3/4 7-84 AMENDMENT NO. 42

ps uc 4

70,,

UNITED STATES y $ eq g

NUCLEAR REGULATORY COMMISSION

%,g,

.y WASHINGTON, D. C. 20555 7 -

\\'~1:

/

...+

ALABAMA POWER COMPANY DOCKET N0. 50-364 JOSEPH M. FARLEY NUCLEAR PLANT, UNIT N0. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.33 License No. NPF-8 1.

The Nuclear Regulatory Commission (the Comission) has found that:

A.

The application for amendment by Alabama Power Company (the licensee) dated August 26, 1983, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, as amended, the provisions of the Act, and the regulations of the Commission; C.

There is reasonable assurance: (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the rttachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-2 is hereby amended to read as follows:

. (2)

Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.33, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION wus pteven A. Varga, Chi f Operating Reactors Branch #1 Division of Licensing

Attachment:

Changes to the Technical i

Specifications Date of Issuance: February 9, 1984

(

I l

l

ATTACHMENT TO LICENSE AMENDMENT NO.

AMENDMENT N0.33 FACILITY OPERATING LICENSE NO. NPF-8 l

DOCKET N0. 50-364 Revised Appendix ~A as follows:

Remove Pages Insert Pages 3/4 7-54 3/A 7-54 3/4 7-57 3/4 7-57 3/4 7-61 S/4 7-61

PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) b.

At least once per 92 days by verifying that a sample of diesel fuel from the fuel storage tank, obtained in accordance with ASTM-D270-65, is within the acceptable limits specified in Table 1 of ASTM D975-74 when checked for viscosity, water and sediment.

c.

At least once per 18 months by subjecting the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for the class of service.

4.7.11.1.3 The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:

a.

At least once per 7 days by verifying that:

1.

The electrolyte level of each battery is aoove the plates, and 2.

The overall battery voltage is greater than or equal to 24 volts.

b.

At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery.

c.

At least once per 18 months by verifying that:

1.

The batteries, cell plates and battery racks show. no visual indication of physical damage or abnormal deterioration, and 2.

The battery-to-battery and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion material.

FARLEY-UNIT 2 3/4 7-54 Amendment tio. 33

e TABLE 3.7-5 LIST OF SPRINKLER SYSTEMS Location Sprinker l

(Room No.)

Description Elevation System i

2160 Hatch Area 100'-0" 2A-25 2161 SGJth Corridor 100'-0" 2A-25 2172 Hallway 100'-0" 2A-101 2175 Ha11way 100'-0" 2A-118 2185 CCW Heat Exchanger and Pump Room 100'-0" 2A-27 2190 MCC Panel Room 100'-0" 2A-62 2209 Hallway 121'-0" 2A-35 2210 South Corridor 121'-0" 2A-36 2223 Mechanical Penetration Room 121'-0" 2A-45 2227 West Cable Chase 128'-0" 2A-23 2244 Mezzanine 131'-0" 2A-36 2245 Mezzanine 131'-0" 2A-36 2300 West Cable Chase 139'-0" 2A-23 2312 Corridor 139'-0" 2A-48 2316 Corridor 139'-0" 2A-48 2318

' Cable Spreading Room 139'-0" 2A-43 2319 West Corridor 139'-0" 2A-59 2452 Clean Storage Area 155'-0" 2A-52 l

2462 Non-Radioactive Vent Equipment Room 155'-0" 2A-51 2466 West Cable Chase 155'-0" 2A-23 2500 West Cable Chase 168'-2" 2A-23 FARLEY-UNIT 2 3/4 7-57 Amendment No. 33

TABLE 3.7-5 LIST OF FIRE HOSE STATIONS AUXILIARY BUILDING l

LOCATION (Room No.)

ELEVATION H0SE CABINET NO.

2103 83'-0" N2V43-D-103 2110 83'-0" N2V43-D-102 2161 100'-0" N2V43-D-110 2163 100'-0" N2V43-D-109 2184 100'-0" N2V43-D-124 2185 100'-0" N2V43-D-108 2186 100'-0" N2V43-D-131 2189 100'-0" N2V43-D-107 2208 121'-0" N2V43-D-128 2209 121'-0" N2V43-D-104 2210 121'-0" N2V43-D-126 2223 121'-0" N2V43-D-127 2234 121'-0" N2V43-D-125 2237 121'-0" N2V43-D-132 2312 139'-0" N2V43-D-114 2316 139'-0" N2V43-D-111 2319 139'-0" N2V43-D-116 2319 139'-0" N2V43-D-119 2332 139'-0" N2V43-D-113 2334 139'-0" N2V43-D-117 2345 139'-0" N2V43-D-112 2404 155'-0" N2V43-D-122 2408 155'-0" N3V43-D-123 2446 155'-0" N2V43-D-105 2452 155'-0" N2V43-D-120 2452 155'-0" N2V43-D-121 2462 155'-0" N2V43-D-106 2502 175'-0" N2V43-D-101 2505 184'-0" N2V43-D-100 2602 139'-0" N2V43-D-118 AUXILIARY BUILDING TO DIESEL GENERATOR BUILDING TUNNELS TRAIN A TUNNEL TRAIN B TUNNEL H0SE CABINET NO.

HOSE CABINET N0.

N2Y430001A N2Y43D001P N2Y430001B N2Y43D001Q l

N2Y430001C N2Y430001R N2Y430001D N2Y430001S N2Y430001E N2Y43D001T N2Y430001F N2Y43D0010 N2Y430001G N2Y43D001V N2Y430001H N2Y430001W N2Y430001J N2Y43D001X N2Y430001K N2Y430001Y N2Y430001L N2Y43D001Z N2Y430001M N2Y430002A N2Y43D001N N2Y430002B FARLEY-UNIT 2 3/4 7-61 Amendment No. 33

-