r:
~ g DUKE POWER GOMPANY P.O. HOx 33180 CHAltLOTTE, N.O. 28242 HAL B. TUCKER '
TELEPHONE VMB PRESWENT (704) 373-4531 February 1, 1984-
==. r-mo-Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Attention:
Ms. E. G. Adensam, Chief Licensing Branch No. 4 Re: Catawba Nuclear Station Docket Nos. 50-413 and 50-414
Dear Mr. Denton:
Section 7.3.2.1 of the Catawba Safety Evaluation Report discusses Confirmatory Issue 25, Steam Generator Level Control and Protection. Duke Power has received and reviewed vendor drawings, purchased equipment, and completed the supporting detailed design and installation for a Steam Generator Overfill Protection System. This system changes the Catawba feedwater isolation initiation logic from a two-out-of-three to a two-out-of-four high-high steam generator level. The hardware was purchased from the same vendor as the original logic system, so that all test and diagnostic functions will be maintained as in the original system.
This modified SG Overfill Protection System eliminates the issue of a single channel failure causing the high-high level trip to be reduced to a two-out-of-two system. The system will now be in total compliance with IEEE 279, Paragraph 4.7, " Control and Protection System Interaction."
Very truly yours, 6
Hal B. Tucker ROS/php cc:
Mr. James P. O'Reilly, Regional Administrator U. S. Nuclear Regulatory Commission Region Il
[
101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303 0
NRC Resident Inspector Catawba Nuclear Station Mr. Robert Guild, Esq.
Attorney-at-Law P. O. Box 12097 Charleston, South Carolina 29412 8402060077 840201 PDR ADOCK 05000413 E
{
j Mr. Harold R. Denton, Director February 1, 1984 Page 2 cc: Palmetto Alliance 2135 Devine Street Columbia, South Carolina 29205 Mr. Jesse L. Riley Carolina Environmental Study Group 854 Henley Place Charlotte, North Carolina 28207
!