a
.DESIGl!
J CTITCIFAL Cortifica PT PHIIJLDE2.PHIA EI.ECTRIC CCMPA.
~#
~'
~
'm Peach Botten Atcaic Power Statien g,
R.D. 1, Delta, Pennsylvania 17314 February 15, 19e3 Mr. R. C. Haynes Ad=inistxator U.S. Nuclear Pagulatory Co:mmission Region I 631 Park Avenue King of Prussia, PA 19406 St%7ECT RIPCitTABI2 OCCtmAD42 - PPC!<2T MF; CAT 7Ctri Ccnfir: sing J. r. Mit: nan's conversation with R. Blough, Region I, United Statens Nuclear Fagulatory CtenMasion cu 2/15/83.
Reference s Docket No. 50-278 Peach Botto:s t: nit 3 Technical Specificatica 4.7A.f 10CFR50 Appendix 3 III C3 FAport No. 3-83-C8/IP Occurrence Date:
2/14/83 Identificatien of _ Occurrences Three of eight main steam isolation valves fMSIvs) failed to pass the Technical rpecification limit of 11.5,SCFH.
In addition, containment isolation valve MD 2-74 failed a local leak rate test.
hth failures resulted in the IwW Appendiz J 11mit of 0.6 Ia being exceeded for local leak rate test totals.
Conditions Prior to Occurrence:
Unit 3 shutd.cwn for refueling.
p;perent Cause of Occurrence:
[
Abnoz nal wear of valve internals.
Analysis ef_ Occurrence:
1 Redundant MSIVs were cperable and had acceptsble laak rates.
The valve in line with MO 2-74 has not fet been testad for laak rate, but it is in an oporsb;e corditien.
This redundant valve, MO 2-77, will be testad as socn as possible to date.nine its leak rate.
Because the clant is cold shutdcAm no further is::ediate actica is required per Technical Speificatient-.
8302230202 830215
,=
PDR ADOCK 05000278
%,g g g
PDR l'
bIi Corrective Action:
v P
t' valves will be disassembled for inspecticn. repaired, ara rotestad i
prior to return of Unit 3 to pcmor.
Pravious occurrencu r
2-82-21/3L, 2-80-13/3L, 3-91-21/3L, 3-79-36/3L.
e very truly yours, M. 5. Fleisch: nann Statica Styrintar4 ant i
k i