| Issue date: | 12/14/1994 |
| From: | Stolz J Office of Nuclear Reactor Regulation |
| To: | Public Service Electric & Gas Co, Philadelphia Electric Co, Delmarva Power & Light Co, Atlantic City Electric Co |
| Shared Package | |
| ML20079B281 | List: |
| References | |
| DPR-70-A-162, DPR-75-A-143 NUDOCS 9501050383 | |
| Download: ML20079B278 (8) | |
Text
.
g@ hG f
2 S
UNITED STATES 5
NUCLEAR REGULATORY COMMISSION k....,/
WASWNGTON, D.C. 20555-0001 PUBLIC SERVICE ELECTRIC & GAS COMPANY i
PHILADELPHIA ELECTRIC COMPANY DELMARVA POWER AND LIGHT COMPANY ATLANTIC CITY ELECTRIC COMPANY DOCKET NO. 50-272 SALEM NUCLEAR GENERATING STATION. UNIT NO. 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 162 License No. DPR-70 1.
The Nuclear Regulatory Commission (the Commission or the NRC) has found that:
A.
The application for amendment filed by the Public Service Electric &
Gas Company, Philadelphia Electric Company, Delmarva Power and Light Company and Atlantic City Electric Company (the licensees) dated i
March 28, 1994, as supplemented June 1, 1994, and August 24, 1994, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and i
regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance: (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this amendment v111 not be inimical to the common defense and security or to the malth and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifica-tions as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-70 is hereby amended to read as follows:
1050383 941214 p
ADOCK 05000272 PDR
~,.
, (2) Igchnical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 162, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendnent is effective as of its.date of issuance, to be implemented within 60 days.
FOR T UCLEAR REGULATORY COMMISSION I
pd.
S
+o(
John F. Stolz, Director Project Directorate I-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation j
i
Attachment:
i I
Changes to the Technical Specir', cations i
Date of Issuance: December 14, 1994 I
i r
I b
{
...., -.-~.
i ATTACHMENT TO LICENSE AMENDMENT NO.162 FACILITY OPERATING LICENSE NO. DPR-70 i
DOCKET NO. 50-272 Revise Appendix A as follows:
l Remove Paaes Insert Paaes 3/4 3-26 3/4 3-26 I
i 1
l
6 TABLE 3.3-4 (continued)
ENGINEERED SAFETY FEATURE ACTUATION SYSTEM INSTRUMENTATION TRIP SETPOINTS FUNCTIONAL UNIT TRIP SETPOINT ALLOWABLE VALUES 5.
TURBINE TRIP AND FEEDWATER ISOLATION A.
Steam Generator Water Level --
s 67% of narrow range s 68% of narrow range High-High instrument span each instrument span each steam generator steam generator I
6.
SAFEGUARDS EQUIPMENT CONTROL Not Applicable Not Applicable SYSTEM (SEC) 7.
UNDERVOLTAGE, VITAL BUS a.
Loss of Voltage 2 70% of bue voltage 2 65% of bus voltage b.
Sustained Degraded Voltage 2 94.6% of bus voltage for 2 94% of bus voltage for l
s 13 seconds s 15 seconds 8.
Automatic Actuation Logic Not Applicable Not Applicable b.
Manual Initiation Not Applicable Not Applicable c.
Steam Generator Water Level--
2 9.0% of narrow range 2 8.0% of narrow r r.ge q
Low-Low instrument span each instrument span each steam generator steam generator d.
Undervoltage - RCP 2 70% RCP bus voltage 2 65% RCP bus voltage e.
S.I.
See 1 above (All S.I. setpoints) f.
Trip of Main Feedwater Pumps Not Applicable Not Applicable q.
Station Blackout See 6 and 7 above (SEC and Undervoltage, Vital Bus)
SALEM - UNIT 1 3/4 3-26 Amendment No.162
s 3 8'ou a
~
UNITED STATES 5
ti NUCLEAR REGULATORY COMMISSION
%,.. o,c#
WASHINGTON, D.C. 20555-0001 PUBLIC SERVICE ELECTRIC & GAS COMPANY PHILADELPHIA ELECTRIC COMPANY DELMARVA POWER AND LIGHT COMPANY ATLANTIC CITY ELECTRIC COMPANY DOCKET NO. 50-311 SALEM NUCLEAR GENERATING STATION. UNIT NO. 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 143 License No. DPR-75 1.
The Nuclear Regulatory Commission (the Commission or the NRC) has found that:
A.
The application for amendment filed by the Public Service Electric &
Gas Company, Philadelphia Electric Company, Delmarva Power and Light Company and Atlantic City Electric Company (the licensees) dated March 28, 1994, as supplemented June 1, 1994, and August 24, 1994, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance: (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR Chapter I; D. -The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifica-tions as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. DPR-75 is hereby amended to read as follows:
(2) Technical Soecifications and Environmental Protection Plan i
The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 143, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of its date of issuance, to be implemented within 60 days.
FOR NUCLEAR REGULATORY COMMISSION
((.
L fof' John F. Stolz, Director Project Directorate I-2 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications Date of Issuance: December 14, 1994 J
l
)
enn
ATTACHMENT TO LICENSE AMENDMENT NO.143 FACILITY OPERATING LICENSE NO. DPR '75 DOCKET NO. 50-311 i
Revise Appendix A as follows:
Remove Paaes Insert Paaes 3/4 3-27 3/4 3-27 l
i 1
1 I
l i
TABLE 3.3-4 ENGINEERED SAFETY FEATURE ACTUATION SYSTEM INSTRUMENTATION j
TRIP SETPOINTS FUNCTIONAL UNIT TRIP SETPOINT ALLOWABLE VALUES 7.
UNDERVOLTAGE, VITAL BUS a.
Loss of Voltage 2 70% of bus voltage 2 65% of bus voltage b.
Sustained Degraded Voltage 2 94.6% of bus voltage for.
2 94% of bus voltage for l
s 13 seconds s 15 seconds B.
Automatic Actuation Logic Not Applicable Not Applicable b.
Manual Initiation Not Applicable Not Applicable c.
Steam Generator Water Level--
2 9.0% of narrow range 2 8.0% of narrow range Low-Low instrument span each instrument span each steam generator steam generator d.
Undervoltage - RCP 2 70% RCP bus voltage 2 65% RCP bus voltage e.
S.I.
See 1 above (all S.I. setpoints) f.
Trip of Main Feedwater Pump Not Applicable Not Applicable g.
Station Blackout See 6 and 7 above (SEC and Undervoltage, Vital Bus)
=
9.
SEMIAUTOMATIC TRANSFER TO RECIRCULATION a.
RWST Low Level 15.25 ft. above 15.25 + 1 ft. above Instrument taps instrument taps b.
Automatic Actuation Logic Not Applicable Not Applicable SALEM - UNIT 2 3/4 3-27 Amendment No. 143
--