Notice of Consideration of Issuance of Amends to Licenses DPR-77 & DPR-79 & Proposed NSHC Determination & Opportunity for Hearing.Amend Would Revise SR for Diesel Generators, Deleting Requirement to Accelerate to at Least 900 Rpm
ML20079A482
Person / Time
Site: Sequoyah  
Issue date: 12/22/1994
From: Williams J
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20079A485 List:
References
NUDOCS 9501030090
Download: ML20079A482 (8)


Text

..

I*

l l.

l UNITED STATES NUCLEAR REGULATORY COMMISSION SE000YAH NUCLEAR PLANT UNITS 1 AND 2 DOCKET NOS 50-327 AND 50-328 NOTICE OF CONSIDERATION OF ISSUANCE OF AMEN 0 MENT TO FACILITY OPERATING LICENSE. PROPOSED NO SIGNIFICANT HAZARDS CONSIDERATION DETERMINATION. AND OPPORTUNITY FOR A HEARING l

The U.S. Nuclear Regulatory Commission (the Commission) is considering issuance of amendments to Facility Operating License Nos. DPR-77 and DPR-79 l

issued to the Tennessee Valley Authority (the licensee) for operation of the Sequoyah Nuclear Plant, Units 1 and 2, located in Soddy Daisy, Tennessee.

The proposed amendments, submitted by the licensee's letter dated December 16, 1994, would revise the surveillance requirements for diesel generators, deleting a requirement to accelerate to at least 900 revolutions i

per minute (rpm), adding wording for voltage and frequency acceptance j

criteria, and deleting a requirement for a 10-year surveillance during i

shutdown.

Before issuance of the proposed license amendment, the Commission will f

i have made findings required by the Atomic Energy Act of 1954, as amended (the i

Act) and the Commission's regulations.

i The Commission has made a proposed determination that the amendment request involves no significant hazards consideration.

Under the Commission's I

regulations in 10 CFR 50.92, this means that operation of the facility in accordance with the proposed amendments would not (1) involve a significant j

l A

ENCLOSURE i

9501030090 941222 PDR ADOCK 05000327 P

PDR l

ji l

s j

2

)

increase in the probability or consequences of an accident previously evaluated; or (2) create the possibility of a new or different kind of l

accident from any accident previously evaluated; or (3) involve a significant reduction in a margin of safety. As required by 10 CFR 50.91(a), the licensee has provided its analysis of the issue of no significant hazards consideration, which is presented below:

(The Tennessee Valley Authority) TVA has evaluated the proposed technical specification (TS) change and has determined that it does not represent a significant hazards consideration based on criteria established in 10 CFR 50.92(c). Operation of Sequoyah Nuclear Plant (SQN) in accordance with the proposed amendment will not:

1.

Involve a significant increase in the probability or consequences of an accident previously evaluated.

i The proposed changes to these surveillances do not alter the intent or methods for verifying diesel generator (D/G) operability. The intent of the 900 revolutions per minute (rpm) l requirement is still maintained by the 60 plus or minus 1.2 hertz (Hz) requirement with acceptable tolerances. The deletion of the requirement to perform interdependence testing during snutdown does not alter the test but does provide reasonable flexibility to perform testing during power operation. By testing this function at power the probability and consequences of an accident are not increased. These surveillances verify operability of the D/Gs and do not impact the availability of D/Gs for accident mitigation.

In addition, these tests, as well as the D/Gs, can not be the source of an accident.

These proposed changes will not increase the probability or consequences of an accident.

2.

Create the possibility of a new or different kind of accident from any previously analyzed.

The D/G and TS testing to verify operability are not postulated to create an accident.

The affected surveillances are not changed in intent and will be performed in the same manner.

Testing D/G starts during power operation is conducted on a weekly basis, therefore, 10-year interdependence testing under_these conditions will not present additional accident generation concerns.

Therefore, the proposed changes will not create a new or different kind of accident.

E s

3 3.

Involve a significant reduction in a margin of safety.

The testing requirements affected by the proposed changes will continue to verify D/G operability within the same or more conservative limits, intent, and testing methods. The changes provide flexibility in verifying D/G speed during ambient starts and relaxed operating conditions for performing interdependence tests. This flexibility does not lessen the operability verification requirements for the D/Gs or the margin of safety provided by the D/Gs. Therefore, the proposed changes do not reduce the margin of safety.

l The NRC staff has revie*ad the licensee's analysis and, based on this review, it appears that the thne standards of 10 CFR 50.92(c) are satisfied.

Therefore, the NRC staff proposes to determine that the amendment request involves no significant hazards consideration.

The Commission is seeking public comments on this proposed l

determination. Any comments received within 30 days after the date of l

publication of this notice will be considered in making any final I

determination.

Normally, the Commission will not issue the amendment until the expiration of the 30-day notice period.

However, should circumstances change during the notice period such that failure to act in a timely way would result, for example,.a derating or shutdown of the facility, the Commission may issue the license amendment before the expiration of the 30-day notice period, provided that its final determination is that the amendment involves no significant hazards consideration. The final determination will consider all public and State comments received.

Should the Commission take this action, it will publish in the FEDERAL REGISTER a notice of issuance and provide for opportunity for a hearing after issuance.

The Commission expects that the need to take this action will occur very infrequently.

l*

i

('

l 4

Written comments may be submitted by mail to the Rules Review and Directives Branch, Division of Freedom of Information and Publications Services, Office of Administration, U.S. Nuclear Regulatory Commission, Washington, DC 20555, and should cite the publication date and page number of this FEDERAL REGISTER notice. Written comments may also be delivered to Room 6D22, Two White Flint North,11545 Rockville Pike, Rockville Maryland, from 7:30 a.m. to 4:15 p.m. Federal workdays. Copies of written comments received may be examined at the NRC Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC.

The filing of requests for hearing and petitions for leave to intervene is discussed below.

By January 27, 1995, the licensee may file a request for a hearing with respect to issuance of the amendment to the subject facility operating license and any person whose interest may be affected by this proceeding and who wishes to participate as a party in the proceeding must file a written request l

for a hearing and a petition for leave to intervene.

Requests for a hearing l

and a petition for leave to intervene shall be filed in accordance with the Commission's " Rules of Practice for Domestic Licensing Proceedings" in 10 CFR Part 2.

Interested persons should consult a current copy of 10 CFR 2.714 which is available at the Commission's Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC and at the local public document l

room located at the Chattanooga-Hamilton County Library, 1101 Broad Street, Chattanooga, Tennesee 37402.

If a request for a hearing or petition for leave to intervene is filed by the above date, the Commission or an Atomic Safety and Licensing Board, designated by the Commission or by the Chairman of the

"~

n--

~n--

,>-a

5 l

Atomic Safety and Licensing Board Panel, will rule on the request and/or l

petition; and the Secretary or the designated Atomic Safety and Licensing Board will issue a notice of hearing or an appropriate order.

As required by 10 CFR 2.714, a petitior for leave to intervene shall set forth with particularity the interest of the petitioner in the proceeding, and how that interest may be affected by the rssults of the proceeding. The l

petition should specifically explain the reasons why intervention should be I

permitted with particular reference to the following factors:

(1) the nature of the petitioner's right under the Act to be made party to the proceeding; (2) the nature and extent of the petitioner's property, financial, or other interest in the proceeding; and (3) the possible effect of any order which may l

l be entered in the proceeding on the petitioner's interest.

The petition should also identify the specific aspect (s) of the subject matter of the proceeding as to which petitioner wishes to intervene. Any person who has

)

filed a petition for leave to intervene or who has been admitted as a party l

may amend the petition without requesting leave of the Board up to 15 days prior to the first prehearing conference scheduled in the proceeding, but such an amended petition must satisfy the specificity requirements described above.

1 Not later than 15 days prior to the first prehearing conference scheduled in the proceeding, a petitioner shall file a supplement to the petition to intervene which must include a list of the contentions which are sought to be litigated in the matter.

Each contention must consist of a specific statement of the issue of law or fact to be raised or controverted.

In addition, the petitioner shall provide a brief explanation of the bases of the contention and a concise statement of the alleged facts or expert opinion which support the contention and on which the petitioner intends to rely in i

i a

6 1

i proving the contention at the hearing.

The petitioner must also provide references to those specific sources and documents of which the petitioner is I

aware and on which the petitioner intends to rely to establish those facts or i

expert opinion.

Petitioner must provide sufficient information to show that a genuine dispute exists with the applicant on a material issue of law or fact.

Contentions shall be limited to matters within the scope of the amendment under consideration. The contention must be one which, if proven, would entitle the petitioner to relief. A petitioner who fails to file such a supplement which satisfies these requirements with respect to at least one contention will not be permitted to participate as a party.

3 Those permitted to intervene become parties to the proceeding, subject to any limitations in the order granting leave to intervene, and have the opportunity to participate fully in the conduct of the hearing, including the opportunity to present evidence and cross-examine witnesses.

If a hearing is requested, the Commission will make a final determination on the issue of no significant hazards consideration.

The final i

determination will serve to decide when the hearing is held.

)

If the final determination is that the amendment request involves no significant hazards consideration, the Commission may issue the amendment and i

make it immediately effective, notwithstanding the request for a hearing. Any hearing held would take place after issuance of the amendment.

j If the final determination is that the amendment request involves a i

l significant hazards consideration, any hearing held would take place before the issuance of any amendment.

A request for a hearing or a petition for leave to intervene must be filed with the Secretary of the Commission, U.S. Nuclear Regulatory

]

i l

j

l-L**

7 Comission, Washington, DC 20555, Attention:

Docketing and Services Branch, or may be delivered to the Commission's Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC 20555, by the above date. Where petitions are filed during the last 10 days of the notice period, it is requested that the petitioner promptly so inform the Commission by a toll-free telephone call to Western Union at 1-(800) 248-5100 (in Missouri 1-(800) 342-6700). The Western Union operator should be given Datagram Identification Number N1023 and the following message addressed to Mr. Frederick J. Hebdon: petitioner's name and telephone number, date petition was mailed, plant name, and publication date and page number of this FEDERAL REGISTER notice. A copy of the petition should also be sent to the l

Office of the General Counsel, U.S. Nuclear Regulatory Comission, Washington, DC 20555, and to General Council, Tennessee Valley Authority, ET llH, 400 West Sumit Hill Drive, Knoxville, Tennessee 37902, attorney for the l

l licensee.

Nontimely filings of petitions for leave to intervene, amended petitions, supplemental petitions and/or requests for hearing will not be entertained absent a determination by the Comission, the presiding officer or the presiding Atomic Safety and Licensing Board that the petition and/or j

request should be granted based upon a balancing of the factors specified in l

10 CFR 2.714(a)(1)(i)-(v) and 2.714(d).

For further details with respect to this action, see the application for amendment dated September 8,1994, which is available for public inspection at the Commission's Public Document Room, the Gelman Building, 2120 L Street, NW., Washington, DC 20555 and at the local public document room located at the

!o 8

l Chattanooga-Hamilton County Library, 1101 Broad Street, Chattanooga, Tennesee 37402.

Dated at Rockville, Maryland, this 22nd day of December 1994 FOR THE NUCLEAR REGULATORY COMMISSION

/

Joseph F. Williams, Project Manager e