NEDO-32205-A EQUIVALENT MARGIN ANALYSIS PLANT APPLICABILITY VERIFICATION FORM FOR Qmd Cities 9ation Thit 2 BWR/2-6 WELD Surveillance Weld USE:

%Cu =

0.26 S4W Capsule Fluence =

f.0 E 18 Measured % Decrease =

45 % (Charpy Curves)

R.G.1.99 Predicted % Decrease =

39%

(R.G.1.99, Figure 2)

I imitino Beltline Weld USE:

% Cu =

0.30 32 EFPY Fluence =

3.4 E 17 R.G.1.99 Predicted % Decrease =

21 %

(R.G.1.99, Figure 2)

Adjusted % Decrease =

22% (R.G.1.99, Position 2.2) 2Z%.s. 34%, so vessel welds are bounded by equivalent margin analysis.

9501310464 950125 PDR ADOCK 05000254 P

PDR

l NEDO-32205-A EQUlVALENT MARGIN ANALYSIS PLANT APPLICABILITY VERIFICATION FOIO1 YOR Qwd Cities 9ation Urat 2 BWR/2-6 WELI)

Surveillance Weld USfa

%Cu =

0.26 S4W Capsule Fluence =

2.43 E 19 Measured % Decrease =

53 % (Charpy Curves)

R.G.1.99 Predicted % Decrease =

49%

(R.G.1.99, Figure 2)

Limitino Beltline Weld USE:

%Cu =

0.30 32 EFPY Fluence =

3.4 E 17 R.G.1.99 Predicted % Decrease =

212fi (R.G.1.99, Figure 2)

Adjusted % Decrease =

225 (R.G.1.99, Position 2.2) i 23.134%, so vessel welds are bounded by equivalent margin analysis.