ML20078C064

From kanterella
Jump to navigation Jump to search
Revised Fire Protection Operability Requirements,Including Issue 21 to Depp Table of Contents,Issue 2 to FPOR-22 & Issue 3 to FPOR-23
ML20078C064
Person / Time
Site: Fort Saint Vrain 
Issue date: 10/12/1994
From: Russell D
PUBLIC SERVICE CO. OF COLORADO
To:
References
PROC-941012, NUDOCS 9410280064
Download: ML20078C064 (5)


Text

9 FORT ST. VRAIN NUCLEAR GENERATING STATION Public

) SOfVIC et PUBLIC SERVICE COMPANY OF COLORADO O

oocumeur raamsmiTTa' TO

_Doqument Control Clerk DATE DItob_er 20. 1914__

o FROM,_ Ddble__Ru ne])

.lart_St,_Vrain

_16805_MCR_1

_Platteri))e,_C0__B06El THE FOLLOWING MATERIAL IS TRANSMITTED HEREWITH:

DFPP Index, Issue 21, dated 10-12-94 FPOR 22 Issue 2 FPOR 23 Issue 3 O

l-A,hh O

i PLEASE RETURN YOUR SIGNED ACKNOWLEDGEMENT INDICATING RECEIPT OF THE ABOVE MATERIAL 9410280064 941012 PDR ADOCK 05000267 F,

PDR c...

,ooto F orm (C) 372 22 3'74 INITi ATOR. Forward White Copy to Recips ', Retain Yellow Copy l

RECIPiE NT - Return AcEnowiedged Whrte Copy to initiatot

DFPP 10-12-94 Issue 21 O

SECTION DFP.S.1

+

FIRE PROTECTION OPERABILITY REOUIREMENTS TABLE OF CONTENTS NUMBER TITLE ISSUE EFFECTIVE DATE FPOR-0 Fire Protection Operability 4

12-7-92 FPOR-1 Emergency Diesel Generator Carbon 4

12-7-92 Dioxide System FPOR-2 Carbon Dioxide Hose Reels -

4 12-7-92 DELETED FPOR-3 Halon Systems 5.

12-7-92 FPOR-4 Deluge Spray Systems 3

12-7-92 FPOR-5 Fixed Water Spray Systems 4

12-7-92 FPOR-6 Plant Yard Hydrants 3

12-7-92 FPOR-7 Fire Extinguishers 4

12-7-92 FPOR-8 Breathing Air System - DELETED 3

12-7-92 FPOR-9 Fire Hose Stations 4

12-7-92 FPOR-10 Fire Water Pumps 4

12-7-92 O

FPOR-11 Fire Water Headers and Mains 3

12-7-92 FPOR-12 Fire Detectors 6

12-7-92 FPOR-13 Fire Barriers 7

12-7-92 FPOR-14 Fire Doors 8

12-7-92 FPOR-15 Fire Dampers 5

12-7-92 FPOR-16 Fire Protection Cooldown Trains -

5 12-7-92 DELETED FPOR-17 Alternate Cooling Method (ACM) 5 12-7-92 DELETED FPOR-18 Ladders - DELETED 4

12-7-92 FPOR-19 Cable Wraps - DELETED 3

12-7-92 FPOR-?O Emergency Lighting - DELETED 4

12-7-92 FPOR-21 Site Fire Brigade - DELETED 2

12-7-92 FPOR-22 Storage of Activated Graphite -

2 10-12-94 DELETED FPOR-23 Fire Water Makeup System 3

10-12-94 C:)

uh

.A m a4 4mi n J.

4 u-.a y&

4 4awA A Jr 622+,g

.p-_

-<4 4 __

=

-C 6

_As-.

dian.31_a

.se p_.

4, a A

FPOR-22 Issue 2 Page.1 of 1 E

FIRE PROTECTION OPERABILITY REQUIREMENTS Storage of Activated Graphite i

This requirement has been deleted.

IFPOR-22 I

s O

i i

?

lO i

d

FPoR-23 legus 3 Pags 1 of 2 O

flRE PROTECTION OPERABILITY REQUIREMENTS V

Fire Water Makeup System FPOR-23 The Fire Water Makeup Syster shall be operable with:

a)

A minimum of five (5) million gallons of water in the storage pond (s).

b)

At least two (2) operable circulating water makeup pumps.

c)

An operable flow path capable of taking suction from the storage pond (s) and delivering the water to the fire water pump pits.

APPLICABILITY: At all times ACTIONS:

e..

With less than 5 million gallons of water in the storage pond (s), establish a backup water source of water within 72

hours, b.

With one of the circulating water makeup pumps inoperable, perform an operability check on the remaining pump.

tOs c.

With both the circulating water makeup pumps inoperable, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> return at least one pump to service or establash a source of backup fire suppression.

d.

With no operable flow path available, within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> restore an operable flow path or provide an alternate source of makeup water to the fire water pump pits.

i SURVEILLANCE REOUIREMENTS:

The fire water makeup system shall be demonstrated operable:

l a.

At least once per seven (7) days by verifying the storage pond inventory.

l b.

Deleted l

)

FPOR-23 Iocuo 3 Page 2 of 2 O

J

.c.

At least once per 18 months by:

1)

Cycling each testable valve in the makeup water flow path (s) through at least.one complete cycle of full.

travel.

l 2)

Deleted BASIS FOR FPOR-231 The operability of the Fire Water Makeup System, in conjunction with the fire water pumps (FPOR-10),

ensures adequate fire suppression capability for any postulated fire (except in congested cable areas) involving water used as the primary suppression fluid.

The makeup system and the fire water pumps supply Deluge Systems, Fixed Spray Systems, Fire Hose Stations, and Plant Yard Hydrants.

There is a small possibility that a fire in one of the congested cable areas could disable the Fire Water Makeup System. In this

scenario, the Platteville Volunteer Fire Department would be summoned for assistance in extinguishing the fire using their pumpers.

O.

In-the unlikely event all makeup pumps, storage ponds and flow paths are inoperable simultaneously, off-site fire department response is available for supplemental or backup capability. 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> is sufficient time to return one makeup pump to service or establish a backup fire water source.

As detailed in the DFPP and the DFPP Safety Evaluation, one million gallons of water is adequate for fire suppression purposes. Hence, 5 million gallons of water in the storage pond (s) is very conservative and 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is adequate time to restore the storage

-l pond (s) level in the avant the inventory is less than 5 million gallons of water.

l The Surveillance Requirements and the normally operating status of l the circulating water makeup pump (s) are adequate to ensure a pump will be available in the event of a fire, and an adequate water supply and operable flow path exist, f

O