_ _

'p 4

GPU Nuclear Corporation G. 0 duclear

:r388 i

Forked River, New Jersey 08731-0388 609 971-4000 Wnter's Direct Dial Number:

C321-94-2088 June 24,1994 U. S. Nuclear Regulatory Commission Att: Document Control Desk Washington, DC 20555 Gentlemen:

Subject:

Oyster Creek Nuclear Generating Station (OCNGS)

Docket No. 50-219 Facility Operating License No. DPR-16 Containment Vent and Purge Isolation Valves -

Resilient Seals

Reference:

(1) NRC Letter, " Resolution of MPA B-24, Containment Purge and Vent Isolation Valves (TAC No. M81902),"

dated January 12, 1993.

In Reference 1, the NRC identified the need to replace, at least every 5 years, the resilient seals for containment isolation valves V-27-1 through 4, V-23-13 through 16, and V-28-17 and 18.

In lieu of this 5 year seal replacement, GPU Nuclear plans to implement a maintenance / surveillance program of durometer hardness testing and visual inspection for the resilient seals.

This program is in addition to the existing seat leakage testing performed during each refueling outage.

Seal replacement will not be based on calendar age but rather on physical condition as monitored by this maintenance / surveillance program.

Details of the program and supporting technical basis is provided in Attachment I.

It is GPU Nuclear's intention to implement this program during the upcoming 15R Refueling Outage which is scheduled for September 1994.

l' I

I 9407010137 940624 PDR ADOCK OSOOO219 i

P PDR GPU Nuclear Corporation is a subsidiary of General Public Utilities Corporation

i C321-94-2088 i

Page 2 If you have any questions or comments on this submittal, please contact Mr. Michael W. Laggart, Manager, Corporate Nuclear Licensing at (201) 316-7968.

j Very truly yours,

/

J. J. E arton 4 Jesident and Director Vi P

sett Creek Attachment l

/P p cc: Administrator, Region 1 Senior Resident Inspector Oyster Creek NRC Project Manager

-- )