Proposed Tech Spec Changes Re Surveillance Requirements
ML20077D280
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 07/22/1983
From:
SOUTH CAROLINA ELECTRIC & GAS CO.
To:
Shared Package
ML20077D276 List:
References
NUDOCS 8307260463
Download: ML20077D280 (3)


Text

r b.onTAtNmsur <>Y< ITEM

^

M TI e

SvRveu2&w_g egou,qsmsm (wg])

3. g.

At-least once per 18 months during shutdown, by verifying that each 3

automatic valve servicing safety related equipment actuates to its correct position o.T a simulated SI test signal or on an ESFLS, as applicable.

4. g. ~At least once per 18 months, by verifying that each service water system booster pump starts automatically on a safety injection signal.

(o-l & %

SU:"'ER - Uf4IT 1 3/4 8307260463 830722 PDR ADOCK 05000395 PDR p

L.

PLANT SYSTEMS 3/4.7.4 SERVICE WATER SYSTEM-

}

LIMITING CONDITION FOR OPERATION 3.7.4 At least two independent service water loops shall be OPERABLE.

APPLICABILITY:

MODES 1, 2, 3 and 4.

('~

t

.l ACTION:

With only one service water loop OPERABLE, restore at least two loops to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next i.

i 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS 4.7.4 At least two service water loops shall be demonstrated OPERABLE:

At least once per 31 days by verifying that each valve (manual, a.

power operated or automatic) servicing safety related equipment that is not locked, sealed, or otherwise secured in position, is in its r

correct position.

[

[D.

At least once per 18 months dur ing shutdown, by verifying that aar e l

au servicing safet./ related e u'

- tuates to its correct positio_n o ated_

signal or on an ESFLS, as applicable.

At leas per 18 months, by verifying that each service wa emboosterpumpstartsautohaticallyonasafetyiniectionsianal.]

I 4

SUMMER - UNIT 1 3/4 7-12 L.

- - - - - - - - ~ ~ ~ "

r i

ATTACHMENT 2 10CFR50.92 SIGNIFICANT HAZARDS CONSIDERATION 1.

Would the proposed amendment involve a significant j

increase in the probability or consequences of an accident previously evaluted?

Answer: No -

The Technical Specification Surveillance Requirement is not being deleted, but is being transferred to a more applicable section of the Technical Specifications.

The system component surveillance intervals will remain the same.

i 2.

Would the proposed amendment create the possibility of a new kind of accident from any accident previously evaluated?

Answer: No -

The Service Water System is not being modified in any way; therefore, the system's performance will remain the same and will not expose any new unreviewed accident scenarios.

3.

Would the proposed amendment involve a significant reduction in the margin of safety?

Answer: No -

System parameters and component surveillances will remain the same; therefore, there will be no impact on the margin of safety.