..Consumem Power -
w wem Ceapany vi e,,,is.
,,ei,,,
r.,i.,i.,
a.d Co.structio.
-- oeneret offices: 1945 West Pernell Road. Jackson. MI 49201 * (517) 788 0453
'. July 18, 1983 Harold R Denton, Director Office of Nuclear Reactor Regulation Division of Licensing US Nuclear Regulatory Commission Washington, DC 20555 MIDLAND ENERGY-CENTER MIDLAND DOCKET NOS 50-329, 50-330 -
SER OPEN ITEM RELATED TO CRACKING.IN THE REACTOR COOLANT SYSTEM MAKEUP N0ZZLES -
FILE 0505.16, M1.9. SERIAL 23735
~
REFERENCE J W COOK LETTER TO H R DENTON (NRC) SERIAL 22343 DATED APRIL 13, 1983 This letter provides information on the subject of reactor coolant system-makeup (MU) nozzles. The information was requested by the NRC during a telephone conference call on July 13, 1983, and responds to topics related to Open Item Number 8 of the Midland SER.
The referenced letter documents those actions already taken by the Company to
. address the. issue of makeup nozzle cracking.
In order to resolve the SER Open Item, the design specifications for the minimum continuous makeup flow need to be specified. Accordingly, Consumers Power Company commits to maintaining a minimum continuous makeup flow of between 1.5 and 3 gpm. At this flow rate, flow and thermal stratification should not occur in the makeup line, thereby avoiding thermal fatigue of the MU nozzle assembly. The basis for this conclusion is contained in the B&W report to Consumers Power Company which was enclosed with the above referenced letter. That report is titled " Babcock &
Wilcox 177 Fuel Assembly Owner's. Group Safe End Task Force Report on Generic =
. Investigation of HPI/MU Nozzle Component Cracking," B&W Document Number 77-1141514-00.
It is expected that this information should provide the NRC with the information necessary to complete SER Open Item Number 8.
8307260236 830718 PDR ADOCK 05000329 E
PDR JWC/MFC/le' g
oc0783-5055a141
) J L.1
CONSUMERS POWER COMPANY Midland Units 1 and 2 Docket No 50-329, 50-330 Lette'r Serial 23735 Dated July 18, 1983 At the request of the Commission and pursuant to the Atomic Energy Act of-1954, and the Energy Reorganization Act of 1974, as amended and the Commissioa's Rules and Regulations thereunder, Consumers Power Company submits information on continuous makeup flow to reactor coolant system makeup nozzles.
CONSUMERS POWER COMPANY By-J Cook,'Vice President Proj s, Engineering and Construction Sworn and subscribed before me this /9 day of M ////.
0l (k& daw f Notary PgFlic Jackson County, Michigan My Commission Expires _b --%g ///[
t7
(?
l oc0483-0425a100
-. - -