s VINGINIA ELEcTHIC AND POWER COMI*ANY HIcnwoND,VIHOINIA 23261 W.L. STEWART Vics Puneronwy N :ctuam OPERATIONS August 26,1983 Mr. Harold R. Denton, Director Serial No. 457 Office of Nuclear Reactor Regulation N0/JHL:acm Attn:
Mr. Robert A. Clark, Chief Docket Nos. 50-338 Operating Reactors Branch No. 3 50-339 Division of Licensing License Nos. NPF-4 U. S. Nuclear Regulatory Commission NPF-7 Washington, D. C. 20555 Centlemen:
VIRGINIA ELECTRIC AND POWER COMPANY NORTH ANNA POWER STATION UNIT NOS. 1 AND 2 RESPONSE TO THE REQUEST FOR INFORMATION REGARDING MAIN TRANSFORMER FAILURES Per your request for information regarding main transformer failures at North Anna Unit Nos. I and 2, dated July 28, 1983, enclosed is the statistical information which is part of the yearly Doble Engineering Company-client conference minutes on transformer tailures.
Very truly yours, lf 1
-e M L'. Stewart W. L Enclosure cc:
Mr. James P. O'Reilly Regional Administrator Region II Mr. M. B. Shymlock NRC Resident Inspector North Anna Power Station
/se/
8308310239 830826 gDRADOCK 05000338 PDR
,e
--ya gp-,
+
-w-m e-
-r- - -
ae,r
- y-ym--
+-g rww1
^
=
1900 YEARLY TRAtlSFORMER FAILURE SURVEY Tallure kV Rated-BIL
.N o.
H L
T MVA Ase-yrs.
Forus* Phase 3
230 26 s
1 161 750 19-150 3
2 161-750 17.1 150 170 26 s
3 3
161-36 20 10 3
4 140-48-4.8-50 31 s
c -
3 50 11 5
138-550 13.8 110 3
6, 138 550 46-250 30 26 s
3 7
138-12-18 c
3 12 25 8
132 550 13.5-110 c
9 115 550 13.8-110 20 24 c -
3 10 115-350 13.2-110 22.4 14 c -
3 c -
3 11 115 350 13.2 110 22.4 11 12 110-550 13.5-13.3 37 s
- 1 3
13 110-450 13.09-110 12 13 c
12 8
c -
3 14 110-450 13.09 110 3
?
15 110-13.8 25 -
c c -
3 10.5 17 16 69-350 13.8 95 c -
3 17 69-350 4.3-95 3.75 18 c -
3 18 69-350 13-110 2.4-75 10 26 19 69-13 8 2.4-12 20 c -
3 3
20 69-12-6 1 21 67-350 7.2-110 1.67 -
c -
3 3
2 66 34.5 136-45 29 3
23 63-350 12.47-110 7.5 22 c
3 24 46-72-5 1:
c c -
3 25 34.5 200 12 110 5 12 26 34 4-200 13.09-110 10 25 3
c 2'
34.5-2.4-4.8 1.0 -
c 1 21 34 &
5.04-8.7 0.833 -
c 1 4
29 34-4.
6.25 -
3 30 34-4-
4 687 -
3 31 26 4-4.16-3.75 -
c 1 3:
25-12 20 16 3
132-110 11-45 0.575-625 38 3
c i
34 345-1050 16.2-150 285 8
c -
35 115-550 33-200 7.5 25 c -
3 36 230 900 115 550 13.8-110 150 c -
3 37 66-350 12-110 7.5 12 3
c 32 66-350 8-110 0.25 33 c 1 39 12-2.4-1.5 56 s
40 60-14 4-12 3
s 41 500-1675 161 750 26-200 400 12 c 1 42 161-750 69-350 13.8-110 66 24 c 1 43 161-750 17.1-150 170 22 c -
3 44 230-116-14b 145 1
c -
4!
13b-450 69-350 12-110 15 lb c
3 4
138-144-21 c -
3 47 110-450 13.09-110 12 6
3 c
48 69-12-15 F
3 c
49 46-13.8 5 13 c -
3 50 34-13 6 25 3
51 500-230-392 14 3
c 52 500-138-392 3
3 c
53 345 138 13-234 12 54 345-22.8-700 15 3
55 335-138-13.8-234 1 rr 3
c 56 230-825 24.7-150 800 9
3 c
57 230-650 115-350 37.5-200 168 14 3
c
- s = shell; c - core W89)
.p.
4-db TR81 --
y..
^
~
1980YEARLYiRANSFORMERFAILURESURVEY Fblin kV Rosed.BIL N o.
H L
T MVA A ge-yn.
Fons' Phase 55 154-60-11-60 -
3 Sc 147.3-13.2-15 10 c
3 00 138-69-13.2 20 24 c !
61 138-450 25 200 7.5 13 c 1 62 118-14.4-0.70 -
3 c
63 132-550 13.8 110 12 24 c -
3 64 115-450 44 250 2.4 110 3.3 34 c -
3 65 115-33-20 -
c 3
e6 115-350 13.09 110 24 3
c -
3 67 115-350 13.09-110 24 3
c 3
68 110-14 4-62.5 -
c -
3
-69 110-450 13.8-110 30 21 c -
3 70 110-450 13.09-110 20 1
3 c
71 110-450 13.8-110 20 10 c -
3 m
72 110-13 8-46-c -
3 3
69-350 13.8-95 10.5 16 c -
3 74 69 13.8-7.5 c -
3 j
75 69-13.00-7.5 17 c -
3
[
76 60-12.47-75 11 c
3 7*
69-350 12-110 7.5 12 c -
3 78 69-12-15 6
c -
3 To 67-2*-
33.3 c 1 80 67-13.09-
- 17 c -
81 67-350 13.09-110 5.0 17 c -
3 82 67-350 13.09-110 12 8
c -
3 E?67-350 13.04 110 7.5 c -
3 64 67-350 7.56-110 3.33 25 c 1 85 67-350 7.56-110 3.3 c -
3 h6 66-12-4-
20 -
- 1 E-66-12-4-
20 --
85 44-250 13.09-110 7.5 20 c -
3 89 44-13.09 110 75 16 c -
3 90 43.5-12.47-5 -
c -
3 91 34.5-200 12 110 25 I
c -
3 92 32.5-4 36 625 25 c -
3 93 34.5-7.56-3 333 -
c -
3 i
04 34 4 13.09 5.25 19 c
3 9.:
34 4-13.08-12.5 16 c -
3 9e 34-4-
6.25 -
3 9-13.8-2.4.
2.5 c -
3 9E 4.16 0 45 1.5 P
c -
3 9c 500 345-34.5 408 1
s
- 1 100 345 230-13.5-400 4m s
3 f
101 345 141 13.8 300 e
s 3
102 345-900 138-450 12 110 400 s
3 102 230-650 116-350 13.2 110 224 7
c -
3 104 230-650 116 350 132-74.9 12 c 1
{
105 230-650 115 350 13.2-110 224 1m 3
c 106 230-650 36.5-200 112 11 c
3 107 230-650 16.5 200 84 7
3 c
108 230-650 36.5-200 84 6
3 c
.109 161-69-13.2-30 10 c
3 110 138-450 69-350 34.5-200
!!5 3
c -
3 111^
138-450 69-350 12-110 36 2
c 3
112 s 138 450 69-350 12-110 30 15 3
c 113 138-450 69-350 12-110 92 12 c
3 114 138-450 34.5 200 25 9
3 c
115 138 26.4 84 7
c 3
116
\\
138-26.4 25 10 c
3
\\
l
- s = shell. c = core FR81 34
1980 YEAR,LY TRANSFORMER SURVEY
~
Failure kV Rated.BIL No.
H L
T MVA Ase-yrs.
Form
- Phase 11'69-350 34.5-200 25 8
c -
3 118 69-350 12 110 7.5 12 c -
3 119 26.4-87-14 7
c -
3 120 26.4-4.16-c -
3 2.24 1
121 138-630 34.5-230 160 18 s
3 122 115-69-13.8-12.5 30 c
3 123 ~
115-13.2-140 15 3
c 124 110-450 13.8-110 20 24 c -
3 125 110-450 13.8-110 26 22 c -
3 126 110-13.8-46 -
c -
3 127 69-25-20 9
3 128 69 350 13-110 4-16.8 14 c -
3 129 69-350 13-110 4-16.8 18 c -
3 130 69-12-10 16 c -
3 131 34.5-13.2-14 13 c -
3 132 34 4-13.2 14 2
c -
3 133 230-650 37.5-700 100 13 s
3 134 141.6-550 13.8 110 12 19 c -
3 135 138-450 69-350 12-110 15 18 c -
3 136 34 4-200 13.2 110 14 16 c -
3 137 34 4-13.2-12.5 5w c -
3 138 34-13.2 7.5
~
139 115-550 24-150 30 13 c -
3 140 115 550 12-110 2.3-5 12 c -
3 141 66-350 7.2 110 0.667 13 c 1 142 60-350 4.16-95 7.5 16 c -
3 143 34-13-6.25 3
144 34-13-t,.25 3
145 230-825 34.5 200 160 12 s
3 146 34.5-12 25 16 c -
3 147 24-12.46-2.3-10 38 c -
3 148 34.5-200 12-4.16 5 12 c
3 149 136-69-13.2 30 14 c -
3 150 136-69-132-30 10 c -
3 151 115-450 12 47 110 12 26 c -
3 152 105-450 13.5-12 23 c
2 153 66-350 13-110 63 28 c 1 154 46-13.04-30 10 c -
3 155 46-832-20 15 c -
3 156 46-832-10 19 c -
3 157 500-1300 115-450 224 16 s
3 I5t 500-1300 22-150 369.6 7
s
- 1 159 367 1050 20-150 685 12 s
3 160 352.5-141-500 6
s 3
161 138-450 69-350 34.5-200 7! 14 s
3 162 230-650 115-350 13.3-110 168 3
s 3
163 230-650 115-350 13.2-110 224 1m 3
c 164 230-118-650 11 c -
3 165 1392-34 3-112 3
c 3
166 138 69-135-30 32 s
3 167 138-34.5-12.0-8.33 33 s
- 1 168 138-27-83 31 3
c 169 138-550 13.8 110 22.4 4
3 c
170 138-450 12-110 20 8
3 c
171 138-12-20 11 3
172 115-350 36.5-200 84 13 s
3 4
- s = shell: c = core f.O TR81.
19,30 YEARLY TRAtiSFORMER FAILURE SURVEY,,
Fhil;re kV-Rated-BIL i
i N 3-H L
T MVA Ase-yn.
Form' Phase 44.8 5
c 3
173
!!5 350 36-200 174 115 34.5 40 12 s
3 3
175 115-14 4.
30 9
s 176 115-450 13-!!0 22.4 15 3
c 177 110-450 13.1-110 45 9
3 c
3 178 110-450 13.09-110 12.5 17 c
1 179 69-12.47-10 7'
c 3
69-14.4-7.5 12 c -
3 180 181 69-12 10 8
c 3
182 67-350 13.09-110 18 15 3
c 183 67-12.47-c -
3 10 24 184 66.36-13.04-42 15 c -
185 34.4-200 12.47-110 7.5 8
3
.c 186 33.5-132-6.25 26 c -
3 18" 33-13-123 32 c 1 188 22.9-13.09-2.8 15 c
3 4
189 22-150 6.9-95 c -
3 43 9
i-
'190 132-13.2-3 24 44 c
191 11-110 4.15-75 5 18 s
3 192 500-250 -
193 230-115 -
104 115-1 -
- 3
- Sheli; C = core i
a i
i 1
4 TR81 36 -
. - ~.,
)
r.
1".31 YEARLY TRANSFORtiER FAILURE SURVEY l
4 Failure kV-Roted BIL Coil No.
H 1-T MVA Age-yrs-Form
- Phase Design" 1
220-825 69 13S-200 6
s 3 e 2
138-650 13.8 50 17 3
3 138-7.56-
$16.25 26 c 1 c-4 134-550 13.8-15 -
c 3 c
_5 132-34 65-138-150 17 s
3 c 6
115-450 13.8-110 24 13 c -
3 c.
7 115-450 13.09-110 18 11 c -
3 c 8
69-1147 10 26 c -
3 c 9
69-350 12-110 7.5 13 c -
3 c 10 69 12-7.5 12 c -
3 c 11 69-12-3.75 -
3 e 12 67-14 4-12.5 -
3 -
13 67-12.5-7.5 30 c
3 c 14 67-350 12.4-6.5 12 3 c c
15 66-13.09-7.5 23 3 c c
16 46-7.5-1147 10 16 c -
3 c 17 4-5-8.32 12.5 16 c -
3 c 18 34 4-4.36-7.5 12 c
3 c 19 344-13.5-10 35 c -
3 e 20 34 4-4-
11.2 14 c -
3 c 2:
34 <.-
4-11.2 14 c -
3 c 22 34-13.2-0.5 23 33-200 13.5-15 24 c
3 e 24 13.5-4.16-10 21 c -
3 25 13.2-110 4.36-75 3.125 17 c -
3 c 26 13.2-110 4.16-75 2.0 20 3 c c
27 110-550 40-250 10-125 31.5 6
c 1 c
28 35-36-10 19 c
3 e 29 127-S E-33 21 c 1
- c 30 86-20-20 11 c 1 c
31 88-13.2-7.5 14 c -
3 e 32 13.5-4 6-25 19 3 e c
33 23C-26-125 13 3 e c
34 161-13 3 30 30 c 1 i
c 35 161-136-30 30 c 1 c
36 135-650 69-350 23-110 56 16 3 e c
37
!!5-550 12 110 2.3-5 5
c -
3 c 31 13.5 13.5-30 20 3 c c
3c 345-1050 230-825 13.8-110 235 c
c -
3 e 40 23G.
60-12-75 25 s
3
?
41 230-0.240-0.3 25 c 1 c
42 138-550 69-350 23-150 33.5 14 c -
3 e 43 66-350 8-110 0.25 33 c 1 c
E 43.5 0.48-0.27' 3.33 5
3 -
r c
45 66-13.5-2 16 c
3 c 46 525 1425 241.5-650 34.5-200 336 7
c 1 c
47 230-132.5-60 2
3 e c
45 161 12-7.2-25 11 3 c c
49 132-12-50 50 132-12-50 51 132-12 50 52 110-13.09-20 11 c
3 c
$3 67-350 12.4-12 9
3 c c
54 14.4-0.277-0 480 2.0 2
3 55 138-550 13.8-110 75 9
3 e c
56 66-350 4.16-75 10 9
3 e c
- s - shell: c = core
- c = circular cous: r = rectangular coih n = new; m - months i
l l
TRTQ82 33
,; -3
)
-. - -- u
M ~ -"-
l 1931YEARLYTRANSFORMERFAILURESURVEY Fribure kV-Rated BIL Coll N o.
H L
T MVA Age-yrs.
Form
- Phase Design **
$7 66-350 4.16-75 7.5 10 c -
3 c 58 500-1675 20 7150 400 7
c 1 c
59 38-10-2 20 c
3 e 60 38-10 3 c 1 32 c
61 132-12-50 --
62 115-450 67-250 60 1
c -
3 c 63 34-4.16-0.375 -
64 34-0.480-0.25 -
65 13.2-110 2.5-3.75 -
c 3 e 66 525-1425 241.5-650 300 7
c !
- c 67 345-138-13.2-400 10 c -
3 e 68 345 900 138-450 12-110 400 13 s
3 c 69 345-138-33-300 -
70 345-138-234 4
3 -
71 345-138-175 5
3 72 345-69-234 8
3 -
73 345-25-980 -
s 3 c 74 230-900 115-550 90 22 3 e c
75 230-64-10S-28.9 46 c 1 c
76 230-650 36.5 200 13.2-110 100 11 c -
3 e
~~
230-600 7
3 e 78 161-64-13.5-72 -
3 c c
79 161 750 22.5-150 300 29 c -
3 c 80 161 750 12.3-110 27.5 31 c 1 c
Si 142.3-550 13.2 110 7.5 14 c -
3 8:
138-550 69-350 14-110 168 9
c 3 e 83 135 41.6-5 31 c -
3 e 84 135-13.04-20 8
3 c c
85 135-13.5-50 7
3 -
86 134-550 13.5-7.5 c -
3 c 87 120-14-25 52 3
88 115-550 34.5-200 40 25 3 e c
89 115-450 19.9-34.5 7.5 6
90 115 550 13 5-20 17 c -
3 91 115 550 11.5 110 7.5 33 c 1 c
9; 115-550 11.5-110 7.5 33 c 1 c
92 69 350 23-150 2.4-60 20 20 c
3 c 04 60-13.2-7.5 2
3 c
9 64-12-20 -
9e 60-7.5 10 3 c c
9' 67.2 350 12 47 110 7.5 21 c -
3 96 67 350 135-15 -
3 c c
99 67 350 13.6 15 -
c 3 c 1 00-67-13.09-16 6
3 c c
101 67-13.09-7.56 0.833 24 c 1 c
10:
67-250.13.09-110 33 27 c 1 c
10}
67-350 12.4-12 19 3 c c
104 67 350 12.4-12 19 3 c c
105 67-J50 12.4-2.5 28 3 c c
106 67-4.36-8.4 8
3 c c
107 66 350 34-45 31 3 e c
108 46-12.5 10 9
3 c c
109 45 250 13-110 6.67 20 c 1 c
110 43.8-13.09 3.75 17 3 e c
til 34 4-13.4-13.4 2m 3 c c
- = shell; e = core
- c = circular coils; r = rect 4ngular coils n = new; m = months TRTQ82
-. a -
g
.c.
1981 YEARLY TRANSFORMER FAILURE SURVEY Failure kV-Rated BIL Coil N o.
H L
T MVA Age-yrs.
Form
- Phase Desig e **
c -
3 c 112 34 4-13.09-26 113 33-4160-3.75 41 3 c 114 14 4-0.277-0.480 2.0 6
3 -
115 14 4-0.216-0.125 0.75 15 3
116 13.8-4.33-1.5 3 -
!!7 13.8 2.4.
1 8
c 3 c 3.75 33 c -
3 e 118 13.2 110 4.16-75 119 88 13.2 7.5 14 c -
3 c 120 34.5-12.47-5 3
3 -
r 121 525-1425 241.5-650 400 10 c 1
- c li 1
c -
3 c 122 115 13.09-7.2 123 34.5-13.00-7 13 c -
3 c c -
3 e 124
!!5-13.00-12 5
125 34 4-200 13.2 110 5.6 12 c -
3 e l
3 -
r 126 34.4 200 13.2-110 9.375 12 c
3 c 127 13.5-2.4-3.75 -
c 128 345-230-13.8-400 3
s 3 -
129 345-IS-615 4
s 3 -
130 230-60-12.47-150 9
c -
3 c 131 230-650 36.5-200 3 c 45 6m c
132 230-650 36.5-200 c -
3 e 84 6
l 133 230-650 36.5-200 112 11 c -
3 e 134 230-650 36.5-200 13.2-110 165 13 c -
3 c 135 230-650 25-150 515 s
3 c 136 230-24-850 4
c 3 c 137 135-34.
25 -
3 c 131 138-550 14-110 33 2!
c -
3 c 139 135-13.5-35 9
3 140 69 350 12-110 12 12 3 c c
141 344-4.16-3.75 9
3 -
r i
c i
142 34-0.240-0 480 1
7 e.
3 c I
143 20-34.5 4 8-8.32 0.333 -
- 1 144 115-350 13.2-110 12.5 11 c -
3 e l
145 115-450 12.47 110 12 17 c -
3 c l
146 66 350 0.6-45 2.875 18 3 e c
147 46-5-8.32 5 11 c
3 c 141 34.5-200 11.5-110 2.4-10 11 3 c c
14C 34 4-13.5-10 17 c -
3 c 150 34-13.S.
30 li c -
3 e 151 525-1425 241.5-650 300 14 s
- 1
- c 152 142.3-550 13.2-110 25 17 c -
3 -
153 136 6-650 12.47-110 12 25 c -
3 -
154 110 450 69-350 15 31 c -
3 c 155 34.5-200 12-110 5.0 2-3 e c
156 22-150 6.9-95 3.3 33 c 1 c
157
!!$-550 66-350 30 16 3 e c
158-115-550 66-350 30 11 c -
3 e 159 66-350 7.2-110 0.667 13 c 1 r
160 66-350 7.2 110 0.667 13 c 1 r
161 66-350 7.2-110 0.667 13 c 1 r
162 34.5-0.480-1.5 22 c -
3 c 163 13.8-4.16-3500 4
3 c 164 138-13.8-15 3
c 3 e 165 127-88-5 6
c 1
- c
- s = shell; e = core "c = circtuar cons; r = rectangular coils n = new; m = months TRTQ82
- 35 I i_3
l
.1981 YEARLY -TRANSFORMER FAILURE SURVEY Fall.:re kV Rosed BIL Coil H
L T
MVA Age-yrs.
Form
- Phase Design" 3 c 16e 35-10 5 12 c
3 -
167 13.8-0 48 0.75 12 3 c 12 17 c
168 69-350 13-110 25 9
c -
3 c 169 67-350 114-170
~
230-25-125 12 c -
3 c 3 c 171 230-22.5-575 o
c 172 230-13.5-33 33 s
3 c c -
3 e 15 33 173 27.6-1 174 500-1425 23.8-150 310 11 s
r 175 500-1300 22 150 330 8
s 1
r 176 500-1300 22 150 330 8
s
- 1 r
3 c 177 345 1050 118-450 13 8-110 300 15 c
178 345-1050 20.3-150 542 10 s
3 c 3 c 179 345-1050 20.3-150 542 10 s
3 180 345-20 325 6
181 230-650 69 350 13.2-110 37.33 2
c 1
- c 3 -
r 5182 230-69-12.47-150 7
s 6
183 230 900 13.6-110 43 30 s
- 1 r
184 220-825 36-26.25-75 22 s
3 c 185 139.2
'4.5 60 19 c
3 c 186 13&-
69-100 11 c -
3 c 18' 136 69-11470 5 -
s 3 e 181 138-69-13.8-8.33 30 s
- 1 189 135-13.0' -
3.75 5
c 3 c 190 135-23 40 10 c -
3 c 191 135-13.5-50 8
3 -
192 138550 13.09 110 10 15 c -
3 c 193 132-12-50 -
19.t 132-12-20 -
195 120-13.2-16.6 e
3 c c
19e 115-69-12.8 67.2 18 m 3 c c
19' 115-450 34.5 200 40 12 c -
3 c 198 115-14 4-5,315 12 22 c -
3 e 19c
!!5-450 13.2-110 22.4 17 c -
3 c 200 110-13.09-20-15 -
c 3 c 201 110-13.09 5 16 c -
3 c
- 202, 60-23.9
'0 II c -
3 c 203 69-12 476 14 3 c s
20;67-250 13.09-110 18 1-c -
3 c 205 66-12.47-7.2 5 10 c -
3 c 206 66-1147 7.2 5 10 c
3 c 207 66-6.9-0.833 54 c I c
205 60-13.5-10 32 c
3 e l
209 46-7.9-13.8 24 15 3 e c
210 46-5-8.32 1.5 -
3 c c
211 34.5-69 11470-50 -
s 3 c 212 34.5-7.2-5 3
c r
213 34.5-7.2 1.5 33 c 1 c
214 34 5-2.4-2.5 27 3 c c
215 34 4-200 22.9 150 14-18.7 24 3 c c
216 34.4-4.36-10 -14 3 c c
217 34-4.36-0.15 218 34-0 480-0.277 5 12 3 e c
's = shell; c = core
- c = circular coils; r = rectangular coils a = new; m = months TRTQ82.
Q.... _.. ---. --.....-- -..
w._-
e s
1981 YEARLY. TRANSFORMER FAILURE SURVEY Failure k% Rated-BIL Coi!
No.
H L
T MVA Age-yrs.
Fonn* Phase Design" 219 33-13.8-7.9 14.0 -
3 220 33-4.3-3.75 28 3 c c
221 23-4 2.5 30 3 c c
222 22.9-150 13.09-110 7 12 c -
3 c 3
't 223 22.5 2.5-3.33 7m c
224 110-69-2.5 25 21 3 c c
225 109-13.7-37.5 26 3 e c
226 69-13.8-5.6 4
c -
3 c 227 69-2.5-1.5 16 c -
3 c 228 66-
- 0. 6-5 7
s 3 c i
l 1
- s = shell; e - core
- c = circular cogs; r = rectangular coils n = new; m = months TRTQ82
- 37
- p. %.. -
w.
_........;--~_,.,,,,
)
1932 YEARLY TRANSFORMER FAILURE SURVEY Ft11xre k V.R ased.BIL Coil Failure N s.
H L
T MVA Ag'e-yrs.
Fore
- Phase Design Mode 1
330-1175 135 550 13.2-110 125 27 s
3 e o
2 230-138-13.8-150 20 s
3 -
3 161-650 69-350 4.16 110 45 12 s
3 e o
4 161-45-12 47-33.3 9
3 e o
c 5
139.2-34.5-15 20 c -
3 c o
6 132-34 65-13.8-150 17 s
3 -
o
?
116-20.8 c -
3 c o
8 115-550 13.8 110 20 25 c -
3 c o
G 115-450 37.5-200 20 20 c -
3 e o
10 115-350 37.5-200 22.4 16 c -
3 c o
Il 115-350 13.2 110 22 4 14 c -
3 c o
12 70 6-13 8 10 70 c -
3 c o
13 69-33-13-45 30 s
3 a
14 69-350 24-150 4.16-7.5 20 c -
3 e o
15 69-350 13.2-9.3 14 c -
3 e o
16 69-13.2-10 10 c
3 e o
17 69 350 12-110 3.75 13 c -
3 c o
18 69-350 12-110 12 17 c -
3 c o
19 69-12-20 22 c -
3 c o
20 6L 135-15 14 c -
3 e o
21 67-12 47-12 13 c -
3 c o
22 67-12.4'.
5 10 c -
3 e o
23 67-12.47-7.5 13 c -
3 e o
24 60-350 13.2-110 16.8 8
c -
3 c e
25 46-13 10 16 c -
3 e o
26 E
10 10 33 c -
3 c e
27 35 10 5 26 c -
3 e 21 3 S-10-5 5
c 3 c c.
29 34 4-200 13.2 110 1.5 35 c -
3 c o
30 34-4-
3.125 31 13 8-416-10 8
c -
3 c o
32 13.2-110 4 33-75 1.5 35 c -
3 e c
33 13-110 24-6 32 c -
3 c o
34 765 345-34 5-500 12 c 1
- c o
35 525-135-135-200 c !
- c o
36 765-500-69-5500 1
c 1 c
37 34.5-13 5 1
c -
3 c e
38 26-4 50 s
- 1
- c o
30 88-15.2-12 e
c 3 -
o 40 85-15.2-10 11 c -
3 o
41 85-15.2-7.5-22 c -
3 -
o 42 23G-135-13.5-165 5
c -
3 c 43 230-60-12-150 2t c --
3 c o
44 138-14 4 75 20 c -
3 e e
45 23.76-13.2-6 55 c -
3 c o
+ -
46 230-
!!5-13-225 17 s
3 -
o 4?
230 115 13 215 25 s
3 o
45 230-60-12-75 26 s
3 -
r o
49 230-44-125 2
c -
3 -
SO 230 13 86 25 s
1 o
51 34.5-4.16-I 9
c -
3 c o
52 762-247-13.8-300 4
c 1
- c a
53 230 115-13-115 27 c
3 -
o 54 161-750 17.1 150 170 26 c -
3 e o
55 161 13.2-20 30
- c 56 115-550 13.8-110 15.5 21 c
3 e o
+ -
- s = shell; c = core
'c = circular coils; r rectariguiar coils
- o = coil failurt; + = core failure; e = other failure (leans. etc.)
TRTQ83
1
~.....
T -
T-.--
'~*
L
~
~
1932 YEARLY TRANSFORMER FAILURE SURVEY Foilure kV-Rated BIL Coil Failure No.
H L
T MVA Age yrs.
Form' Phase Design Mode 5'
161-13 5-18 10 c
3 c o
58 144-25 24-10 1
3 -
59 138 550 13 09-110 12 8
c -
3 c o
60 138-12 50 61 116-12.47-12 11 c -
3 e o
62 110-13.09-20 10 c
3 e 63 69-12.47-12 14 c -
3 c o
64 62.7-350 7.2-110 15 11 c -
3 e o
65 34.5-4.8-20 18 c -
3 c o
66 13.5-1-
3.027 3
c -
3 c o
67 138-550 134-650 14 4-110 56.8 10 c 1
- c 68 115-550 12-110 5 20 c -
3 c o
+ -
69 115-550 12-110 5 19 c -
3 e o
+ -
70 38-10 2 34 c -
3 c 71 38-10-2 32 c -
3 c 72 34.
.48 2
73 33 200 12-110 1.5 16 c -
3 c o
74 12-
.45-2.5 75 500-230-392 16 c -
3 c 76 345-900 138-450 12-110 400 15 s
3 c o
+
345-115 13 5-445 e
c -
3 c 78 289-1300 133-750 13.2 110 217 2
c 1
- c
+
7c 230 230 600 10 c -
3 c 80 230-650 165-200 84 9
c -
3 c o
81 230-650 36.5-200 13.2 110 56 14 c -
3 c o
82 165-130-160 25 c -
3 e o
83 161-69-13 41 c 1
- c 84 161 iS0 14.
40 36 3 -
!5 161-115 13.5-20 21 c -
3 c o
8e 161-115 13.8-34.5 20 20 c -
3 c o
2-161-750 12.3-250 27.5 34 c 1
- c 85 161-750 12.3-250 27.5 34 c 1
- c o
89 135-64-12-50 1
- T -
3 c 90 138-34.5-25 10 c -
3 c o
91 135-13.5-7.5 c -
3 c e
92 132-76.2-34 65-
- 60 8
c -
3 -
o 93 132 550 34.5-200 12.47-110 3C c -
3 c o
94
!!S-34.5 7.5 6
c -
3 c o
75 115-350 24-150 30 12 c -
3 c o
96 115-15 40 8
e -
97 115-550 13.8-110 12.5 32 c -
3 c o
98 115 550 13.8-110 12.5 35 c
3 c o
99 115-13.5-20 2
c 3 e 100 115-13.5-20 21 c -
3 c
=
101 115-13-25 17 c -
3 e 1C2 110-
/ 6-12.47-30 15 c -
3 c o
103 110-550 13.5-110 4 40 c 4
- c 104 110-550 13.8 110 4 40 c i
- c 105 110-550 13.8 110 4 40 c 1
- c 106
!!O-13.2-28 10 c -
3 c o
+
107 69-25-10 2
c -
3 c 108 69-25-7.5 1
c -
3 c 109 69-13.2-10.5 2
c -
3 -
r o
110 69-13.2 10.5 2.5 c -
3 t
o 111 69-350 13.09-110 7.5 25 c
3 e o
- s = shell; c = core
- c = circular coils; r - rectangular coils
- o = coil failure: + = core failure; * = other failure Deads, etc.)
l l
TRTOO E
db
~
.ll w.n -..'
., w..:.-- r.:_..... -
.s.: a t...
~
1982 YEARLY TRANSFORMER FAILURE SURVEY Fdlire kV-Rated BIL Coil Failure N s.
H L
T MVA Age-yrs.
Form
- Phase Design Mode 3 c o
112 69-12 47.
12 15 c
c -
3 c 113 69-12.47 30 26 o
3 c 7 18 c
114 69-12.47 o
3 c 115 69-4.16 5.0 27 o
+
c c -
3 e 116 67-13.8-15 20 o
c 1
- c o
11-67.2-416-0.833 53 3 c o
25 12 c
til 67-350 13.2 110 c I
- c o
119 67-13.09-1.25 27 3 c 120 67-12 47-5 19 o
c 2.5 19 c 1 121 67 4.16-c 122 66-25 10 50 c 1 c
o 7.5 50 c -
3 e 123 63-350 11 110 124 45-13 15 23 c -
3 e o
1.6 46 c 1
- c 125 36-4.16-126 34.5-200 13 09-110 10 2
c -
3 e o
127 34.5-12 7.5 11 c -
3 c 125 34.5-11-7.5 9
c -
- c 12*
26-4 60 s
- 1 o
130 22.9-115 12 47-110 1.5 24 c -
3 c o
3 c 1.5 25 c
131 13 8-110 2.4-75 c -
3 c o
132 13 2-4 36 2.5 26 c -
3 c o
133 416-480-2 3
134 4.1 480-2 8
c o
3 c o
420 10 135 c
3 -
o 136 88-15.2-7.5 14 c
3 -
137 20-3.5-10 39 o
c 13) 46-2 c -
3 e o
c -
3 c
=
139 161-64-10.5-40 140 138-550 36.2-200 15 3
c -
3 sc o
10 5
c -
3 c 141
!!5-350 13.2 110 a
A 142 230-750 34.5-200 30 8
c -
a c c
o 6
143 6o-13.8-4 24 c -
3 e 144 35-10 5 18 c -
3 e c -
3 c o
g a
145 230-650 36.5-200 150 12 g
14e 230-650 36 5-200 150 12 c -
3c o
147 230-650 36.5-200 84 8
c -
3 e o
850 5
s 3 -
r o
14E 230-22.5-c -
3 c e
14u 139.2-34.5-100.8 11 15e 139.2-34 5-67.2 18 c
3 c e
151 138 550 69-350 13.2 110 30 9
c -
3 c
152 136-34.5-83 11 s
3 c o
=
153 13 -
25-11 90 4
5 3 -
r
+ -
154 138-69-34.5-115 10 c -
3 c o
155 135-34.5-50 9
c 3 c o
3 e 156 115-34.5-13.5-26 11 c
157 115-14-50 14 c -
3 c o
155 115-13.8-30 1
c -
3 c e
15c 110-450 69-350 15 32 c -
3 c 33.3 12 c -
3 c o
160 110-13.8-14 10 c -
3 c 161 69-350 12-150 162 69-350 12-150 37.3 8
c -
3 e 3 e 28 4
c 163 43.8-150 43.8-250 p
164 34.4-200 4.16-5.25 10 3 e 5 20 c -
3 c o
165 13-11-
- s = shell; c = core
- c = circular coits; r rectaripular coils
- o = coil failure; r = core failure; * = other failure ticads, etc.)
m.
A
bN,
_. u -
N
_m u
.~.u;
. 2...
1982 YEARLY TRANSFORMER FAILURE' SURVEY'ev Failure kV Rated BIL Coil Failure
~
N o.
H L
T MVA A e yrs.
Form
- Phase Design Mode 16e 144-72-25-15 10 3 -
167 144-25-4.16-10 6
o 168 141.6-550 13.8 110 7.6-42 21 c -
3 c 169 141.6-550 13.8-110 7.6-42 10 c -
3 c 170 138-34.5 13.8 160 21 c -
3 c 171 115-550 25-150 24 27 c -
3 e o
172 115-13 8-24 11 c -
3 c 173 67-350 13.2 110 25 15 c -
3 e o
174 67-13.09-18 15 c -
3 c o
175 67-13.09-1.66 29 c 1
- c o
176 66-350 33-200 3.333 34 c 1 c'
177 66-350 33-200 3.333 34 c 1
- c 178 45-IF 12 17 c -
3 c o
179 43.5-13.09-7.5 14 c -
3 c o
180 36-13.8-30 18 c -
3 -
181 35-13 3 33 c 1
- c o
182 34 4-13.2-13 44 15 c -
3 c o
183 34 4.
13.2-13.44 17 3 c o
164 34 4-4.36-11.2 12 c -
3 c o
185 138 550 69-350 13.09-150 21 18 c -
3 e o
186 110-44.
12.47-33.3 16 s
3 e c
187 110-13.09-7.5 13 c -
3 c o
188 69-350 23-150 7.5 19 c -
3 e o
184 64-13.8-30 c -
3 -
190 69-350 12-110 20 14 c -
3 c o
191 60-350 12.5-110
- 8.. 20 c -
3 e o
192 23C-44-125 10 c -
3 -
193 66-350 23.9-150 6 17 c -
3 e 194 24-150 4.16-75
- 10 22 c -
3 e 195 13.8-50 4.16-25 3
7 c -
3 e o
19c 138-350 34.5-150 18 2
c -
3 e o
197 138-350 34.5-150 18 18 m c -
3 c o
198 67 350 4 16-75 20 1
c -
3 e o
199 23-480-3 13 e.
3.
o 200 46-7.2 -
1 66" 8
3 -
o 201 230-135-250 (1 c -
3 c
- ~-
202 69-1.L 28 16 c -
3 c c
203 34 5-13.5-
.5 e -
3 c 204 34.5-13.0C.
7 12 c -
3 e i o
205 34 4-200 4.3-200 9.375 15 c -
3 e o
20e 120-450 13.2-110 84 9
c -
3 e o
207 13.8-110 4.16-75 3.5 5
c.
3 e 208 4 16-
. 4&-
.5 5
c -
3 c 209 500-1300 230-650 448 4
c I e
210 34.5-13b-5 c -
3 c 211 138 550 69-350 13.2-110 60 8
c -
3-c o
212 138-550 69-350 13.2 110 60 13 c -
3 c o
213 138-550 69-350 13.2 110 60 13 c -
3 e o
214 138-550 69-350 13.2 110 30 14 c
3 e o
215 115-12.47-7.2-25 18 c
3 c o
216 69-12.47-25 12 c -
3 e o
217 69-12.47-25 12 c -
3 e o
218 34.4-4.36-5.6 17 c -
3 c o
+ -
- s = she!!; e = core
- c = circular coils; r - rectanFular coils
- o = coil failure; + = core failure; * = other failure (leads etc.1 TORSioW A
Ab-i.
Oc. - 5
. _. =.
L._
1982 YEARLY TRANSFORMER FAILURE SURVEY Failrre kV-Rated BIL Coll Fallem N 3.
H L
T MVA Ase yrs-Fore
- Phase Desisa Mode c -
3 c 219 344-4.36-11.2 IS '
o
+
3 c 10 20 o
+
220 34 4-13.2-c 7.5 221 34-4-
1 222 765-145-34.5-500 9
s o
223 765-345-34.5-500 9
s
- 1 o
369.6 8
s
- 1 224 500-22-o 369 6 9
s
- 1 225 500-22-r 369.6 9
5
- 1 226 500-22-r 227 345-115-13.8-74 17 s
3 c o
225 345-900 23-150 725 14 s
3 c o
c -
3 -
229 161-115-13.5-187 3
3 c 230 157-69-30 11 c
231 139.2-34.5-5.6 17 c -
3 e 12 16 s
3 c 232 138-550 13.8 110 o
12 14 c -
3 e 233 138-550 13.09-110 o
3 'c 234 120-450 13.2 110 16.8 24 c
c -
3 c 235 120-450 13.2 110 16.8 c -
3 c 23e 120-450 13.2 110 16.8 24 3 e 237 115-450 57-450 12.5-110 33.3 30 s
o 3
238 115-550 37.5 200 13.2 110 50 26 s
r o
3 -
r 239
!!S-34.5-40 25 s
240 115-450 23.5-150
!$ 17 3 e c
o 241 115-22-12 12 3 e c
o 242
!!5-350 13.2 110 56 11 c -
3 e o
243
!!5-350 13.2-110 7 13 c
3 c o
244 115-450 13.2-110 22A 18 c -
3 e c
245 115 4.36 12 15 c -
3 e o
246 113-13.5-12 3 -
247 70.6-13.5-7.5 56 c -
3 c c
243 69-350 24 94-150 7.5 15 c -
3 e o
249 6c-13.8-
.833 53 c !
c o
250 67-350 13.2-110 9.375 c -
3 c o
251 6c-13.0c-5.6 12 c
3 c o
252 6c-12.47-12 19 c -
3 c o
253 67-13
.5 27 c I
- c c
254 66 550 34 5-6 667 s
- 1 c
o 255 66-350 13.09-110
-75 28 12 c -
3 c o
25f do-13.2-20 14 c -
3 c o
25-46-2.4 1
c l
- c o
258 34.5-34.5-120 10 c -
3 c e
259 34.5-13.09-10.5 9
c -
3 c o
260 34.5-12-5 12 c
3 e o
261 34.5-12-5 14 c -
3 c o
262 34.5-12-5 17 c -
3 c o
263 34.5-12-
.833 13 c 1
- c o
264 34 4-4.365-10 33 s
3 -
r c
1 265 34.5-4-
3 75 30 m c
3 r
o 266 34.5-
.480-2.5 6 rr.
3 c c
267 34-34-250 9
s 3 -
268 34-12-6.25 269 34-12 6.25 270 33 S-6.25 28 c -
3 c
+
271 25.2-13.09-7.56 7 13 c
3 r
o 272 25-4-
2.5 23 c -
3 c o
273 25-4-
2.5 23 c -
3 e o
274 25-4-
2.0 25 c -
3 c o
- s = shell; e = core
'c = circular coits; r - rectarigular coils
- o = coil failure; + = core failure; * = other failure (leads, etc.I TRTO83
,_;_-___7__-_-__
==. - -- -~= ::-.:. -. :..'.K = '. :. :. - =.-. c :: ~~~-r.==.
-- -.=---
u - -
- .'2 -?
.-.q...
....4..
..~%-.
1982 YEARLY TRANSFORf1ER FAILURE SURVEY Fall:re kV. Rated-BIL Coil Failure H
L T
MVA Age-yrs.
Form' Phase Design Mode
!?5 25-4-
2.5 25 c -
3 e o
276 23-12.5-5.0 7
c -
3 c o
a 3 e 3.75 20 c
277 23-12.5-o 3
278 22.9-12.47
$ 11 c
r o
3 e 12 10 c
279 16-4.16-280 14 4-
.480-I 1
c -
3 o
.~-
e c -
3 e 5.25 54 281 13.5-4.16-c -
3 c 7.5 25 282 13.2-44-c -
3 c 8 35 283 11-2.3-
- s = shell; c = core
'c = circular coik: r. rectangular coih
'o = coil failure: * = core failure: * = other failure (leads etc )
To35if6Tra A
LN d