Text
.
%5 OPU Nuclest Corporation n_
- Nuclear a n = >"-
f of kod R>v>r. New Jett.ey 08731 0388 009 971 4000 Wnter's Datet D al Number C321-91-2197 July 22,1991 U.S. Nuclest Regulatory Commission Attentions Document Cortrol Desk Vashington DC 20$$$
o Gentlement Subjects Oyster Creek Nuclear Generating Btation Docket No. $?-219 Technical Specification Change Requent No. 198 Pursuant to 10 CPR 50 90 GPU Nuclear Corporation (GPUN)o operator of the oyster Creek Nuclear Generating station (OCN05)o Provisional Operating License No. DPR=16e requeLts a change to Appendix A of that license.
The attached Technical specification change Request proposes to change OCNas Technical specifications with regard to the design pressure for the drywell primary containment vessel.
The current drywell design presouro is 62 psig.
The calculated peak drywell pressure resulting from the design basis loss of coolant accidento as substantiated by recent analysin is 30 psig.
Ve have o
added a 15% allowance to arrive at a new design pressure of 44 psig.
This request is part of CPUN's comprehensive program to address the corrosion of tho Oyster Creek drywell.
Ve therefore, request that a high priority be o
assigned to this request. This change request has been reviewed in accordance with Section 6.5 of the OcNos Technical specifications and using the standards o
in 10 CTR 50.92 we have concluded that these proposed changes do not constitute a significant hasards consideration.
Pursuant to 10 CTR 50.91 (b) (1), a copy of this change request has been sent to the State of New Jersey Department of Environmental Protection.
Very truly yours o h
&O ( f 09
.(v cygn.
Iff J. J. Barton
+ th Vice President and Director VO Oyster creek LW$
JJB/PC/amh Attachment (4
ccs Administrator Region I 00L bc5 o
Q NRC Residant inspector
(\\\\
Nr. Alex Dromericko NRC Project Manager
<o<05u cru nuc,ca, corporai.on is a conseary or conorat runne utmi<es cornarat,on