P ATTACHMENT 3 Unit 1 Revision Page 3/4 3-30 Replace l

l

)

t 91052200B7 910517 PDR ADOCK 05000348 PDR p

TABLE 3.3-5 (Continued)

ENGINEERED SAFETY FEATURES RESPONSE TIMES INITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS 3.

Pressurizer Pressure-Lov a.

Safety Injection (FCCS) f 27.0'*'/12.0

b.

Reactor Trip (from SI) 3 2.0 c.

Feedvater Isolation 3 32.0

d.

Containment Isolation-Phase "A" 3 17.0

e.

Containment Purge Isolation f 5.0 f.

Auxiliary Feedvater Pumps Not Applicable g.

Service Vater System f 77.0/87.0'1' 4.

Differential Pressure Between Steam Lines-liig a.

Safety Injection (ECCb) 3 12.0/22.0

b.

Reactor Trip (from SI) 3 2.0 c.

Feedvater Isolation 3 32.0

d.

Containment Isolation-Phase "A" f 17.0/27.0

e.

Containment Purge Isolation Not Applicable f.

Auxiliary Feedvater Pumps Not Applicable g.

Service Water System 3 77.0/87.0

5.

Steam Flow in Two Steam Lines-fligh coincident with T

--Low-Lov a.

Steam Line Isolation f 11.0 l

P 6.

Steam Line Pressure-Lov a.

Safety Injection (ECCS) 3 12.0(4'/22.0

b.

Reactor Trip (from SI) f 2.0 c.

Feedvater Isolation f 32.0

d.

Containment Isolation-Phase "A" f 17.0/27.0

e.

Containment Purge Isolation Not Applicable f.

Auxiliary Feedvater Pumps Not Applicable g.

Service Water System f 77.0/87.0

Steam Line Isolation 3 7.0 i

FARLEY - UNIT 1 3/4 3-30 AMENDMENT NO.

l

.