Final Deficiency Rept Re Colt Industries Thermostatic Valves W/Potential Failure Mode Which Might Cause Overcooling of Emergency Diesel Generators.Caused by Loose Nut.Replacement Parts on Order.Also Reportable by Colt Per Part 21
ML20073M749
Person / Time
Site: Marble Hill
Issue date: 04/14/1983
From: Shields S
PSI ENERGY, INC. A/K/A PUBLIC SERVICE CO. OF INDIANA
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
REF-PT21-83 S82-13, SVP-0021-83, SVP-21-83, NUDOCS 8304220198
Download: ML20073M749 (2)


Text

d

. Ls A

PUBLIC SERVICE INDIANA S. VV. Shields April 14, 1983 Senior Vice President.

S82-13 Nuclear Division SVP-0021-83 Mr. James C. Keppler, Docket Nos.: STN 50-546 Regional Administrator STN 50-547 U. S. Nuclear Regulatory Commission Construction Permit Nos.:

Region III CPPR - 170 799 Roosevelt Road CPPR - 171 Glen Ellyn, Illinois 60137 Marble Hill Nuclear Generating Station - Units 1 and 2

Dear Mr. Keppler:

On June 2,1982, Mr. R. H. Porter of Public Service Company of Indiana, Inc. (PSI) notified your office of a potentially reportable item as required by 10 CFR 50.55(e). Colt Industries issued a report under 10 CFR 21 which identified certain thermostatic valves with a potential failure mode which might cause overcooling of their emergency diesel generators.

The failure mode of the thermostatic valve is a loose nut which allows an extended stroke of the valve. This additional stroke causes the thermal assembly to control at a lower temperature thus overcooling the diesel engine. PSI has received the valve manufacturer's, Robertshaw Controls Company, procedure for modifying the affected valves. PSI is now proceeding to acquire the replacement parts and wi_1 make the necessary modifications prior to installation of the diesel generators.

This letter is intended to fulfill the requirements of a final report as defined in 10 CFR 50.55(e).

If you have any questions regarding this matter, please contact me at your convenience.

Sincerely, n

/

l q

CV l

S. W. Shields

%fj SWS/LGY/bak

)

8304220198 830414 PDR ADDCK 05000546 APR 18 G83 S

PDR P. O. Box 190, New Washington, Indiana 47162 812. 289.3000

s SERVICE -

INDIANA ' Letter:

J. G.'Keppler April 14,-1983 S82-13 i

SVP-0021-83 cc: Director of Inspection & Enforcement U. S. Nuclear Regulatory Commission Washington, D. C.

20555 J. E. Konklin J. F. Schapker i

4 9

4 i.

t

,~

-,c-

-g-

-r

~ -..an.

,.e,.

-