Proposed Tech Specs Updating Requirements for Procurement & Testing of Diesel Fuel Oil by Using 1993 Version of Standard ASTM D975
ML20073M713
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 11/07/1994
From:
VERMONT YANKEE NUCLEAR POWER CORP.
To:
Shared Package
ML20073M710 List:
References
NUDOCS 9411140131
Download: ML20073M713 (4)


Text

_,

VYNPS 3.10 LIMITI!1G CONDITIO11S FOR 4.10 SURVEILLANCE REQUIREMENTS OPERATION 4.

480 V Uninterruptible 4.

480 V Uninterruptible Power Systems Power Systems From and after the date When it is determined that one that one Uninterruptible Power Uninterruptible Power System or its System or its associated Motor associated Motor Control Center are made Control Center is or found to be inoperable, the inoperable for any requirements of reason, the Specification 4.5.A.4 requirements of shall be satisfied.

Specification 3.5.A.4 shall be satisfied.

5.

RPS Power Protection From and after the date that one of the two redundant RPS power protection panels on an in-service RPS MG set or alternate power supply is nude or found to be inoperable, the associated RPS MG set or alternate supply will be taken out of service until the panel is restored to operable status.

C.

Diesel Fual C.

Diesel Fuel There shall be a minimum of 1.

The quantity of diesel l

25,000 gallons of diesel generator fuel shall be fuel in the diesel fuel oil logged weekly and after storage tank.

each operation of the unit.

2.

Once a month a sample of diesel fuel sh.all be taken and checked for quality and the results logged. The quality shall be within the applicable limits specified on Table 1 of ASTM D975-93, except cloud point shall be loss than the 10th percentile minimum temperatures for Vermont Yankee as specified in Table 4.10.2.

9411140131 941107 DR ADOCK 05000271 FDR Amendment No. M, 1-14 218 I

1 i

VYMPS TABLE 4.10.1 REACTOR PROTECTION SYSTEM POWER PROTECTION I

Setpoints for Parameter Panels A1, A2, B1, B2, C1, C2 Overvoltage s 125.5 volts overvoltage Time Delay 5 0.35 seconds Undervoltage 2 111 volts Undervoltage Time Delay s 0.35 seconds Underfrequency 2 56.5 Hz Underfrequency Time Delay s 0.35 seconds TABLE 4.10.2 DIESEL CENERATOR CLOUD POINT TEMPERATURES Month 10th Percentile Minimum Temperature - 0F September 39 October 28 November 22 f

December 2

January

-3 February

-1 March 11 1

l i

1 1

Amendment No. -140 219 l

1

VYNPS BASES:

4.10 (Cont'd)

C.

Logging the diesel fuel supply weekly and after each operation assures that the minimum fuel supply requirements will be maintained. During the monthly test for quality of the diesel fuel oil, the tests specified in Table 1 of ASTM D975-93 will be performed. The quality of the diesel fuel oil will be acceptable if the results of the tests are within the limiting requirements for diesel fuel oil shown on Table 1 of ASm D975-93.

Cloud point shall be less than the 10th percentile minimum temperatures for Vermont Yankee which have been determined from over 15 years of site-specific meteorological data using the method specified in Appendix X3 of ASTM D975-93.

l Amendment No.

223

4 VYNPS 3.13 LIMITING CONDITIONS FOR 4.13 SURVEILLANCE REQUIREMENTS OPERATION b.

At least once per quarter by verifying that a sample of diesel fuel from the fuel storage tank is within the acceptable limits j

specified in Table 1 of ASTM D975-93.

Cloud point shall be less than the 10th percentile minimum

)

temperatures for Vermont Yankee as specified in Table 4.10.2.

c.

At least once per 18 months by veri-fying the diesel starts from ambient conditions i

on the auto-start signal and 1

operates for 2;20 minutes while loaded with the fire pump.

3.

The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:

a.

At least once per week by verifying that.

1)

The electrolyte level of each battery is above the plates, and 2)

The overall battery voltage is 2; 24 volts.

b.

At least once per quarter by verifying that the specific gravity c

is appropriate for continued service of the battery.

c.

At least once per 18 months by verifying that:

Amendment No. 6 243 a