a.,

Southern California Edison Company 23 PARME R STREET lRvlNE. CALIFORNIA 92718 NICHARD M. ROSE NBLUM TELEPHONE September 16, 1994

,,.........o v.c.....--

U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C.

20555 Gentlemen:

Subject:

Docket Nos. 50-361 and 50-362 Proposed Technical Specification Change NPF-10/15-442 San Onofre Nuclear Generating Station Units 2 and 3

Reference:

December 31, 1992, letter from Harold B. Ray (Southern California Edison (Edison) to USNRC Document Control Desk;

Subject:

Docket Nos. 50-361 and 50-362, Amendment Application Nos. 128 and 112; Changes to Technical Specifications 3.2.1, " LINEAR HEAT RATE," and 3.2.4, "DNBR HARGIN"; San Onofre Nuclear Generating Station Units 2 and 3 Enclosed are Amendment Application Numbers 145 and 129 to Facility Operating Licenses NPF-10 and NPF-15 for San Onofre Nuclear Generating Station Units 2 and 3, respectively.

The Amendment Applications consist of Proposed Technical Specification Change Number NPF-10/15-442 (PCN-442).

PCN-442 is provided as to this letter.

PCN-442 is an amendment request to change the Technical Specification (TS) 3/4.2.1, " Linear Heat Rate," Linear Heat Rate (LHR) limit. TS 3/4.2.1 requires maintaining the linear heat rate at or below 13.9 kilowatts per linear foot (kw/ft) for steady state operation. This amendment request is to revise this value from 13.9 kw/ft to 13.0 kw/ft.

The Bases of TS 3/4.2.1,

" Linear Heat Rate," are also being revised to reflect the new value.

The 13.0 kw/ft value is used in a new large Break Loss of Coolant Accident analysis to provide additional analysis margin.

The Reference (PCN-325) also requested changes to portions of TS 3/4.2.1.

Therefore, the proposed changes from the Reference which affect the same pages as this amendment request (PCN-442) are provided as Enclosure 2.

PCN-299 implements the Technical Specification Improvement Project which incorporates the recommendations of NUREG-1432, " Standard Technical Specifications Combustion Engineering Plants."

PCN-299 was submitted to the NRC for review on December 30, 1993.

This proposed change does not require any changu to PCN-299 because the LHR limit is being transferred to the Core Operating Limit Report.

9409220014 940916 PDR ADOCK 05000361 L

- '\\

8 i

P PDR J

i g

Document Control Desk Your approval of this amendment application is requested prior to Mode 3 entry during startup from the Unit 2 Cycle 8 Refueling Outage. Mode 3 entry is expected on approximately March 26, 1995.

If you have any questions regarding this amendment application, please contact me.

Sincerely, 7

f

/k /W /b) N

'C Enclosures cc:

L. J. Callan, Regional Administrator, NRC Region IV A. B. Beach, Director, Division of Reactor Projects, NRC Region IV K. E. Perkins, Jr., Director, Walnut Creek Field Office, NRC Region IV J. A. Sloan, NRC Senior Resident Inspector, San Onofre Units 2 & 3 H. B. Fields, NRC Project Manager, San Onofre Units 2 and 3 H. Kocol, California Department of Health Services

,-