o], 1, 1671 Worcoseer Road 1
Pub 5c Service of New Hampshire
, [*,
March 31,1983 S BN-497 T.F. Q2.2.2 United States Nuclear Regulatory Commission Region I 631 Park Avenue King of Prussia, PA 19406 Attention:
Mr. Richard W. Starostecki, Directo:-
Division of Project and Resident Programs
References:
(a) Construction Permit CPPR-135 and CPPR-136, Docket Nos. 50-443 and 50-444 (b) Telecon of November 10, 1982, A. L. Legendre (YAEC) to Eugene Kelly (NRC Region I)
(c) PSNH Letter, dated December 14, 1982, " Interim 10CFR50.55(e) Report; Tornado Missile Shields for Fuel Storage Building," J. DeVincentis to R. W. Starostecki
Subject:
Interim 10CFR50.55(e) Report; Tornado Missile Shields for Fuel Storage Building
Dear Sir:
In Reference (c), we filed an interim 10CFR50.55(e) report regarding the adequacy of Tornado Missile Shield protection on the North and West walls of the Fuel Storage Building.
Description of Potential Deficiency Blue Sheet No. 49 was written by the NRC for Tornado Missile Shields which are provided on North and West walls of the Fuel Storage Building above El. 64'-0 where ductwork penetrates walls. Ductwork is not installed and clear line of sight is available through openings. There is a l'-0 thick slab at El. 64'-0.
Analysis of Safety Implications As per Section 3.5.2 of Final Safety Analysis Report, Spent Fuel Pool Cooling / Cleanup System and Storage Pool is to be protected against Tornado Missiles.
With the present configuration, a Tornado Missile could enter the Fuel Storage Building through the West wall opening but could not enter the Fuel Pool area because of possible angle of entry and thus is in no violation of FSAR commitment.
8304110913 830331 gDRADOCK05000 1000ElmSt.,P.O. Box 330. Manchester NH03105 Telephone (603)6694000 TWX7102207595
?
United States Nuclear Regulatory Commission FMrch 31,1983 Attention:
Mr. Richard W. Starostecki page 2 A Tornado Missile could enter the building through the North wall opening and enter the Spent Fuel Pool area through slab opening which is located south of North wall opening. Damage to Spent Fuel could possibly result. This is in violation of FSAR commitment and is a potential significant design deficiency.
Corrective Action Taken A study has been made to determine the most expeditious method of protecting the contents of the Fuel Storage Building in the unlikely event that a tornado driven missile would enter the HVAC duct opening in the North wall. The result of this study is a preliminary design of a reinforced concrete shield to perform this function.
Additionally, a review of all openings in all seismic Category 1 buildings has been made to determine if similar design deficiencies exist elsewhere. The results of that review reveal that all such openings are 100% tornado missile protected except eleven.
All eleven are missile protected to some degree; most of them to a large degree.
Currently, probability analyses are underway to determine if any of the potential missile " windows" can be disregarded on the basis that there is an extremely low probability that a missile could enter and damage a safety-related system or component. These analyses are scheduled to be complete by July 15, 1983 at which time a final report on this subject will be issued.
This letter is being filed pursuant to the interim reporting provision of 10CFR50.55(c)(3).
Very truly yours, YANKEE ATOMIC ELECTRIC COMPANY dJ J. DeVincentis Project Fbnager MH0/fsf cc: Atomic Safety and Licensing Board Service List Director of Inspection and Enforcement U.S. Nuclear Regulatory commission Washington, DC 20555
t i
i ASLB SERVICE LIST Roberta C. Pevear Rep. Beverly Hollingworth Designated Representative of Coastal Chamber of Commerce the Town of Hampton Falls 209 Winnacunnet Road Drinkwater Road Hampton, NH 03842 Hampton Falls. NH 01044 Mrs. Sandra Gavutis William S. Jordan, III, Esquire Designated Representative of Harmon & Weiss the Town of Kensington 1725 I Street, N.W.
RFD 1 Suite 506 East Kingston, NH 03827 Washington, DC 20006 Edward J. ficDermottj Esquire E. Tupper Kinder, Esquire Sanders and McDermott Assistant Attorney General Professional Association Office of the Attorney General 408 Lafayette Road 208 State House Annex Hampton, NH 03842 Concord, NH 03301 Jo Ann Shotwell, Esquire Roy P.
Lessy, Jr., Esquire Assistant Attorney General Of fice of the Executive Legal Director Environmental Protection Bureau U.S. Nuclear Regulatory Commission Department of the Attorney General Washington, DC 20555 One Ashburton Place, 19th Floor Boston, MA 02108 Robert A. Backus, Esquire Ms. Olive L. Tash 116 Lowell Street Designated Reoresentative of P.O. Box 516 the Town of Brentwood Manchester, NH 03105 R.F,D.
1, Dalton Road Brentwood, NH 03833 Philip Ahrens, Esquire Assistant Attorney General Edward F. Meany Department of the Attorney General Designated Representative of Augusta, ME 04333 the Town of Rye 155 Washington Road Rye, NH 03870 David L.
Lewis Atomic Safety and Licensing Calvin A. Canney Board Panel City Manager U.S. N,uclear Regulatory Commission City Hall 126 Daniel Street Rm. Efy-439 Washington, DC 20555 Portsmouth, NH 03801 Mr. John B. Tanzer Designated Representative of the Town of Hampton 5 Morningside Drive Hampton. NH 03842