s State of New Jersey i

I Department of Environmental Protection Robert C. Shinn, Jr.

Division of Environmental Safety, Health, Commissioner and Analytical Programs Radiation Protection Programs Bureau of Nuclear Engineering CN 415 Trenton, New Jersey 08625-0415 Tel (609) 987-2032 Fax (609) 987-6354 l

September 5, 1994 I

l U.S.

Nuclear Regulatory Commission l

Attention: Document Control Desk l

Washington, DC 20555 Gentlemen:

Subject:

Oyster Creek Nuclear Generating Station Docket No. 50-219 Amendment to Facility Operating License Technical Specification Change Request No. 219 The subject request was submitted to the NRC by GPU Nuclear i

letter dated JULY 8,

1994.

The request proposes to modify page i

2.3-3 of the Oyster Creek Nuclear Generating Station (OCNGS)

Technical Specifications to allow the degraded voltage setpoint to be raised from 3671 volts to 3840 volts.

The setpoint tolerance range will be decreased from the old range of +/- 1.0% to a new range of +0.5%,

-1.0%.

This engineering review has found that the proposed specifications are more restrictive than the current requirements.

This submittal does not change the current degraded voltage time delay setting.

The New Jersey Department of Environmental Protection's Bureau of Nuclear Engineering (BNE) has reviewed the request within the requirements of 10 CFR 50.91(b) and has no comments.

If you have any questions, please contact David Vann at (609) 987-2053 or Rich I

Pinney at (609) 987-2086.

]

Sincerely, f0SV f0

' Kent W.

Tosch, Manager Bureau of Nuclear Engineering

-0 001 New Jersey is an Equal Opportunity Employer 9409150114 940905

^*(Yded Per g

PDR ADOCK 05000219 u

P PDR

)

i l

=

Y j

c:

Distribution Distribution J.

Lipoti i

N.J.

DEP i

D. Zannoni N.J.

DEP D.

Chawaga NRC Region I State Liaison Officer L.

Briggs NRC Sr. Resident Inspector A.

Dromerick NRC Project Manager l

I M.

Laggert GPU Nuclear BNE/NES Staff I

l l

I e

I i