Amend 13 to License NPF-11,changing Tech Specs to Allow Reduction of Level Requirements for Carbon Dioxide Storage Tanks
ML20072S365
Person / Time
Site: LaSalle 
(NPF-11-A-013, NPF-11-A-13)
Issue date: 04/01/1983
From: Schwencer A
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20072S368 List:
References
NUDOCS 8304070142
Download: ML20072S365 (5)


Text

..

COW.0t!UEALTH EDISON COMPANY DOCKET NO. 50-373 LA SALLE COUNTY STATION, UNIT 1 AMENDPENT TO FACILITY OPERATING LICENSE License No. NPF-11 Amendment No.13 1.

The Huclear Regulatory Comission (the Comission or the HRC) having found that:

A.

The opp 11 cation for anent* pent filed by the Commonwealth Edison Comp 5ny, dated February 24, 1983, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the.

Conmission's regulations set forth in 10 CFR Chapter I; B.

The facility will operate in' conformity with the application, the provisions of the Act, and the regulations of the Comission; C.

There is reasonable assurance:

(1) that _the activities authorized by.

this anendment can be conducted without' endangering the health and -

safety of the public, and (ii) that such activities will be conducted in conpliance with the Comission's regulations; set forth in 10 CFR Chapter I; D.

The issuance of this acendment will not be inimical to the comon defense and security or to the health and safety of the public; and:

E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable reouirements have been satisfied.

.J$

2.

Accordingly, the license is amended by changes to the Technical Specifications

$A as indicated in the_ attachment to this license anandment and paragraph l.oo 2.C.(2) of the Facility Operating License.No. HPF-11 is hereby ameded to (3

read as follot:s:

/es (2) Technica1' Specifications and Environmental Protection Plan-

.c{

The Technical Specifications contained in Appendix-A, as revised-through Amendment No.13, and the Environmental Protection Plan-j,' e contained in Appendix B, are hereby incorporated in the. license.

aL The licensee shall operate the facility in accordance with the L

Technical Specifications and the Environmental Protection Plan. '

y CrFICE)

............u.......

a...a.......una*..

.....*=..n........n SURNAtet)

....u.......

we p l: NRC FORM MS 00f4 NRCM ONO

OFFICIAL RECORD. COPY uso m m - m e.o a

-[.

' +

3.

This license amendment is effective as of the date of issuance.

FOR THE IlVCLEAR REGULATORY COR11SS10ll

.Originalsigned by A. Schwencer, Chief Licensing Branch No. 2 Division of Licensing Date of Issuance:

APR 1 1983

.I i

1 1

  • SEE PREVIOUS CONCURRENCES

. cmce).D..L...:.L..B..#. 2. /..P..M.....

.D.L...:.L..B..#. 2../.L..A......

D..L..

B. C......

.....O..E..L..D...........

. sunnme >.A..B..o..u..r..n..i..a..*..:..k. w.

E.Hy.l t..o..n..*..

. A..S..c..h........ e.r.....

.C..W. 9.o..d..h...q.d.*..._.........

.. 31.281.0.3......... 3/.2.91.8.3........,.,41.)).83...........31.22/.83.......

- om >

wne rORM 318 00-80) NRCM ONO -

OFFICIAL RECORD COPY usae.ms u P

Y I 3.

Within 90 days a er the issuance of this amendment, or s ch la er tin as the Cemnission.a specify, the licensee shall-satisfy pplicable s

recuirement of P. L.

-425 related to pursuing an agreementy th the T /

Secretary of Energy for e disposal of high-level radioac)1ve w A

te v

and spent nuclear fuel.

2 4.

This license amendment is effec ve as of the date of issuance, b) g 9/

R THE NUCLEAR REGULATORY C0fEISS10H Darrell Eisenhut, Director g

Division of licensing g

Office of Hu lear Reactor Regulation Date of Issuance:

\\\\

g-x orneep.0.L;Wf 2 LPM DL:L

,(6,,,,

p(,;(B!,2[B C.,,,,,,. ; A S,,,,,,, DL,;,,,, R,,,,,,,,,,

..ABN..,,,, E!!h(1,.g,,,,,,,,,,

AS,c hy, enc e,r,,,,,,TM,,,

,lg,;,,,,,,,D,[i,E,1 s,,hu,,t,,,

tnf,a,,: hg sua - >

... 34.a.fl8 3.......3

/.8 3,,,,,,,,,ht

.g a,,,,,,,,,,,, t,,,,/,8 3,,,,,,,,,,,, z,,,,,,,,3,,,,,,,,,, y.,,,,,, 3,,,,

. om >

{hRC FORM 318 00-80) NRCM 024o OFFICIAL RECORD COPY

_ usceo:mi-us-eaa

ATTACHMENT TO LICENSE AMENDMENT MO. 13 ri FACILITY OPERATING LICEllSE NO. NPF-11 DOCKET HO. 50-373 Replace the following page of the Appendix "A" Technical Specifications with the enclosed pages. The revised page is identified by araendment number and contains vertical lines indicating the area of. change.

1 REMOVE INSERT 3/4 7-17 3/4 7-17 t

f 1

e

- OFFICE) suRume) oin) s mRc poRM 318 00-80) NRCM Oee.

OFFICIAL RECORD COPY

usam mig

-PLANT SYSTEMS CO, SYSTEMS a.

LIMITING CONDITION'FOR OPERATION r

3.7.5.3 The following low pressure CO2 systems of Unit 1 and Unit 2 shall be OPERABLE.*

a.

Division l'diese1' generator 0 room.

b.

. Division 2 diesel generator-1A room.

c.

Division 3. diesel generator IB room.

.d.

Unit 2 Division 2 diesel generator 2A room.

APPLICABILITY: Whenever equipment protected by the low pressure CO2 systems is required to be OPERABLE.

i ACTION:

a.

With one or more of the above required low pressure CO2 systems.

I inoperable, within one-hour establish a continuous fire watch with -

backup fire suppression equipment for those areas in which redundant systems or components could be damaged; for other areas, establish 4

an hourly fire watch patrol.

Restore the system to OPERABLE status-within 14 days or, in lieu.of any.other report required by.

Specification 6.6.B, prepare and submit'a Special Report to the; Commission pursua'nt to Specification 6.6.C within the next 30: days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE ~ status.

b.

The provisions of Specification-3.0.3 and 3.0.4 are not applicable.

~

SURVEILLANCE REQUIREMENTS 4.7.5.3 Each of the above required low pressure CO2 systems shall be demonstrated OPERABLE:

a.

At least once per 7 days by verifying CO storage tank' level to be.

2 greater than 50%.fu11 and pressure' to be greater' than 290 psig,. Land l

b.

At least once per 31 days by verifying that each valve',-manual, poweri operated, or' automatic, in the' flow path isJin the correct position.

[

c.

At least once per 18 months' byL verifying:

1.

The system valves ~and associated motor ope" rated ventilati6n dampers actuate, manually and automatically, upon receipt of 4

.a simulated. actuation signal,7and 2.

Flow from each nozzle'during a." Puff Test."

"The normal or emergency power. source'may be inoperable in OPERATIONAL 4

CONDITION 4 or 5'or when defueled.

L LA SALLE - UNIT 1l _

3/4.7 Amendment No.313 -

L

?