O TECHNICAL SPECIFICATION UNIVERSITY OF MISSOURI RESEARCH REACTOR FACILITY Number 3.3 Page 2
of 5
Date
SUBJECT:
Reactor Safety System (continued)
Pool Coolant Flow 2
1 0
425(4) gpm (Min) for each 50%
capacity heat exchanger leg or 2
2 0
850(4) gpm (Min) for one 100%
capacity heat exchanger Differential Pressure Across 2.52 psi (Min)
Reucctor 1
0 0
8.00 psi (Max)
Differential Pressure Across 0.63 psi (Min)
Reflector 0
1 0
2.00 psi (Max)
Differential Pressure Across Core 1
0 0
3200(5) gpm (Min)
Differential Pressure Across Core 0
1 1(2) 1600(5) gpm (Min)
Pressurizer Iligh Pressure 1
1 1(2) 95 psia (Max)
Pressurizer Low Level 1
1 1<2) 16 inches below centerline (Min)
Pool Level 0
0 1
23 feet (Min)
Primary Coolant Isolation Valves 507A/B Off Open Either valve Position 1
1 1(2)
Off Open Position Pool Coolant Isolation Valve 509 Off Open Valve 509 Off Open Position 1
1 0
Position Power Level Interlock 1
1 1
Scram as a result ofincorrect selection of operating mode Facility Evacuation 1
1 1
Scram as a result of actuating facility evacuation system Reactor Isolation 1
1 1
Scram as a result of actuating reactor isolation system 94o9130197 940902 PDR ADOCK 05000186 PDR p