ML20072N192

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Failure of Battery on Backup Diesel Fire Pump.Initially Reported on 830610.Battery Not safety- Related.Item Not Reportable Per 10CFR50.55(e)
ML20072N192
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 07/08/1983
From: Koester G
KANSAS GAS & ELECTRIC CO.
To: Seidle W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, KMLNRC-83-086, KMLNRC-83-86, NUDOCS 8307150241
Download: ML20072N192 (1)


Text

e KANSAS GAS AND ELECTRIC COMPANY THE ELECTAC COMPANY GLENN L MOESTER watt >=EsioEst muctsan July 8, 1983 Mr. W.C. Seidle, Chief Reactor Projects Branch 2 ff

'7 U.S. Nuclear Regulatory Commission i

Region IV I

611 Ryan Plaza Drive, Suite 1000 gl Arlington, Texas 76011 f

I i

L_

KMLNRC 83-086 Re:

Docket No. STN 50-482 Subj: Withdrawal of Potential 10CFR50.55 (e) Report -

Dead Battery on Backup Emergency Diesel Fire Pump

Dear Mr. Seidle:

This letter provides the final report on the potential 10CFR50.55(e) matter concerning failure of the battery on the backup diesel fire pump. This item was initially reported by Mr. Otto Maynard of Kansas Gas and Electric Company (KG&E) to Mr. Dayle Hunnicutt of the Nuclear Regulatory Commission, Region IV, on June 10, 1983.

The Wolf Creek fire protection system utilizes a diesel driven pump as a backup to an electric motor driven pump.

During a recent routine test of the diesel driven fire pump, it was found that the diesel's battery had insufficient charge to start the engine. A test of the battery determined that two cells were dead.

The battery in question has been replaced and a maintenance / surveillance program is now in place to periodically check the condition of the diesel fire pump battery. During plant operations, the maintenance / surveillance program will be required by Technical Specifications and if the battery begins to degrade, this condition will be identified and corrected.

Af ter evaluation of this concern, KG&E has concluded that the battery is not safety-related and that its failure is not reportable pursuant to 10CFR50.55(e). Therefore, KG&E withdraws the potential 10CFR50.55(e) report concerning the battery failure on the diesel fire penp.

If you have any questions concerning this matter, please contact me or Mr. Otto Maynard of my staff.

Yours very truly, GLK:bb cc: RCDeYoung HRoberds/WSchum