ML20072H053

From kanterella
Jump to navigation Jump to search
Forwards Response to IE Bulletin 83-03, Check Valve Failures in Raw Water Cooling Sys of Diesel Generators. No Check Valves Installed in Cooling Water Sys at Facilities
ML20072H053
Person / Time
Site: McGuire, Mcguire  
Issue date: 06/07/1983
From: Tucker H
DUKE POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
REF-SSINS-6820, REF-SSINS-SSINS-6 IEB-83-03, IEB-83-3, NUDOCS 8306290282
Download: ML20072H053 (2)


Text

-

I DUKE POWER GOMPANY l'.O. HOX 33180 CIIAHLOTTE, N.C. 28242 IIAL IL TUCKER TELEPHONE vna emeetnews (704) 373-4531 June 7, 1983 mm. c.-om,.

Mr. James P. O'Reilly, Regional Administrator U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303 Re: RII:RLD

$c McGuire Nuclear Station g

Docket Nos. 50-369 and 50-370 c-M_,.

>g IE Bulletin 83-03 c=

Mc

~

Dear Mr. O'Reilly:

--a

?u

.m Please find attached Duke Power Company's response to IE Bulletin 83-03. '

idil Thisbulletinconcernscheckvalvefailuresinrawwatercoolingsystems$

Ch of diesel generators.

p g.;

o I declare under penalty of perjury that the statements set forth herein are true and correct to the best of my knowledge.

Very truly yours,

' seg b x n Hal B. Tucker WHM/php Attachment (1) cc: Director Office of Inspection and Enforcement U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Mr. W. T. Orders NRC Senior Resident Inspector McGuire Nuclear Station G306290282 830607 I

PDR ADDCK 05000369

} y\\\\

O PDR

JP0/WHM June 7, 1983 Duke Power Company McGuire Nuclear Station Response to IE Bulletin 83-03 1.

A review by Duke Power has shown that there are no check valves in the system that supplies raw cooling water to the diesel generators at McGuire Nuclear Station.

It has therefore been determined that IE Bulletin 83-03 does not apply to McGuire.

McGuire does have a separate system which cools the diesel generators.

This is the Diesel Generator Cooling Water System which is a chemically balanced, closed loop system. There is one Walworth check valve per diesel generator in this system.

At McGuire there is a full load, twenty-four hour test performed on the diesel generators and associated equipment every eighteen months.

There is also a surveillance test which is performed every thirty-one days for one hour.

The full load test has been performed twice on Unit 1 and once on Unit 2 with no cooling problems attributable to check valve failures. These tests ensure an adequate cooling water supply to the diesel generators.

If any system degradation occurs, such as valve failure, it would be detected during testing.

2.

This is not applicable to McGuire Nuclear Station.

3.

This is not applicable to McGuire Nuclear Station.

4.

This is not applicable to McGuire Nuclear Station.

5.

This is not applicable to McGuire Nuclear Station.