ML20072E367

From kanterella
Jump to navigation Jump to search
Unit 1,Refueling 21 ISI Summary Rept
ML20072E367
Person / Time
Site: Point Beach 
Issue date: 08/09/1994
From: Prothero C
WISCONSIN ELECTRIC POWER CO.
To:
Shared Package
ML20072E366 List:
References
NUDOCS 9408220225
Download: ML20072E367 (154)


Text

,

~

Wisconsin Bectric Power Co.

231 West Michigan Avenue Milwaukee,WI 53201 Point Beach Nuclear Nat. Unit 1 HIO Nuclear Rond Two Rivers, WI 54241 Dockst 50-2M commercialService Date 12/21/70 UNIT 1 REFUELING 21 INSERVICE INSPECTION

SUMMARY

REPORT FOR FORM NIS-1 k' Y' N N

Date:

Written by:

M

/"2m :ff [b.Iet_Date:8 '/ '/ V 4G r. PReWERo Reviewed by:

Approved by: b Date:

' 7" f 9400220225 940eo9 DR ADOCK 05000266 PDR

i honsin Electric Power Co.

231 West Michigan Avenue Milwaukee, WI 53201 Point Beach Nuclear Plant, Unit I l

6610 Nuclear Road Two Rivers, WI $4241 j

Docket 50-266 CommercialService Date 12/21n0 Acronvms ASME American Society of Mechanical Engineers l

CCW Component Cooling Water EBASCO EBASCO Services Incorporated IDR Indication Disposition Report i

IN Information Notice i

ISI Inservice Inspection LTP Long Term Plan i

\\

MT Magnetic Particle Examination MWR Maintenance Work Request NDE Nondestructive Examination i

NES Nuclear Engineering Section 4

1 NRC Nuclear Regulatory Commission PBNP Point Beach Nuclear Plant 4

P-G Phillips Getschow PT Dye Penetrant Examination PWA Professional Welding Associates QTS Quality Technical Services RT Radiographic Examination UT Ultrasonic Examination VT Visual Examination WE Wisconsin Electric Power Company

Wisconsin Electric Powcr Co.

231 West Michigan Avenue Milwaukee, WI 53201 Point Beach Nuclear Plant, Unit 1 6610 Nuclear Road Two Rivers, WI $4241 Docket 50-266 Commercial 5ervice Date 12/21/70 Table of Contents

1.0 INTRODUCTION

2.0 ABSTRACT OF EXAMINATIONS 2.1 Code Cases and Interpretations

'2.2 Determination of Scope 2.3 Component / Weld Examinations 2.4 Completed Component / Weld Examinations 2.5 Pressure Tests 2.6 Snubber Surveillance Tests 3.0 ABSTRACT OF CONDITIONS NOTED AND CORRECTIVE MEASURES TAKEN 3.1 Component / Weld 3.2 Pressure Tests 3.3 Snubber Surveillance Tests

i Wisconsin Ettetric Power Co.

231 West Michigan Avenue Milwaukee. WI 53201 Point Beach Nucicar Plant, Unit i 6610 Nuclear Road Two Rivers, \\YI 54241 Docket 50-266 ConunercialService Date 12/2100 2.3 Scone of Comoonent Examinations Items from the following components and system areas were examined with NDE techniques by WE (QTS), EBASCO, Phillips Getschow (P-G) and Professional Welding Associates (PWA) personnel.

1 Reactor Vessel j

l Pressurizer j

A Steam Generator Seal Water Heat Exchanger 1

Residual Heat Removal Heat Exchanger 1

Class 1 Pressure Retaining Valve Bolting Class 1 Piping Welds Class 2 Piping Welds Class 1,2, and 3 Pipe Supports 2.4 Comoleted Comoonent/ Weld Examinations j

2.4.1 Explanation of ISI Database fields / entries used in NIS-1 report.

CODE or LLEADING DESCRIITION EXREQ The field that defines the requirement or reason that an examination was performed.

86 E-03 Examinations performed in accordance with the 1986 Edition, no addenda, of ASME Section XI, for the Third Inspection Interval.

A10-03 Additional examinations required in accordance with IWF-2430, reference IDR 94U1-7P019.

A11-03 Additional examinations required in accordance with IWF-2430, reference IDR 94U1-7P029.

l

honsin Electric Power Co.

231 West Michigan Avenue Milwaukee, WI 53201 Point Beach Nuclear Plant, Unit t 6610 Nuclear Road Two Rivers, WI $4241 i

Docket 50-266 J

CommercialService Date 12/2100 l

i i

1 I

1 l

Section XI Examinations (Pages 1XI - 26XI) i

-l i

honsin Electric Powtr Co.

I 231 West Michig:n Avsnus Milwaukee, WI 53201 Point Beach Nuclear Plant, Unit 1 6610 Nuclear Road Two Rivers, WI 54241 Docket 50-266 CommersialService Date 12/2100 Results Indicates the outcome of a particular exam.

P = Pass F = Fail C = Conditionally Accepted Credit Indicates whether or not ASME Section XI credit (IWX-2410) has been taken for the exam. Augmented or other examinations not performed for an ASME Section XI requirement will be indicated by an N.

Examinations also completed for additional, successive, or preservice examination requirements will also be indicated by an N even though they were performed for an ASME Section XI requirement.

2.4.2 Following are database printouts that summarize the ISI examinations that were performed during the Unit 1 Refueling 21 outage.

Wisconsin E12ctric Pow:r Co.

231 Wes Michigan Avenue Milwaukee.WI 53201 Point Beach Nuclear Plant, Unit i 6610 Nuclear Road Two Rivers. WI 54241 Docket 50-266 CommercialService Date 12/21/70 S05-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR-7-P-004, Outage 02, Interval 03.

S06-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR 7-P-005, Outage 02, Interval 03.

S07-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR 7-P-006, Outage 02, Interval 03.

S08-03 Successive examinations required in accordance with IWF-2420(b),

reference IDRs 7-P-008 and 7-P-029, Outage 02, Interval 03.

SO9-03 Successive examinations required in accordance with IWF-2420(b),

j reference IDR 7-P-009, Outage 02, Interval 03, i

S10-03 Successive examinations required in accordance eh IWF-2420(b),

reference IDR 7-P-010, Outage 02, Interval 0A SI1-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR 7-P-014, Outage 02, Interval 03.

S12-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR 7-P-015, Outage 02, Interval 03.

S13-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR 7-P-018, Outage 02, Interval 03.

S14-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR 7-P-019, Outage 02, Interval 03.

S15-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR 7-P-020, Outage 02, Interval 03.

Outage A description of exam.

"Y" exam completed during the outage, scheduled EACH interval.

"C" exam completed during the outage, scheduled ONCE during plant life.

Indicate A description of indications (i.e., N = no indications, R = recordable indications, I = insignificant or non-relevant indications, G =

geometry).

Wisconsin Electric Pow 1r Co.

231 West Michigan Avenue Milwaukee, W1 33201 Point Beach Nuclear Not. Unit 1 6610 Nuclear Road Two Rivers, WI $4241 Docket 50-266 CommercialService Date 12/21n0 B08-03 Examination of components in accordance with the requirements of IWA-5250.

l D01-03 Visual examination of RV head cladding in response to NRC IN 90-029.

P14-03 Preservice exam for manway bolt No. 7, reference MWR 9401615.

P15-03 Preservice exam for RC-427 bolting, reference MWR 9401366.

P16-03 Preservice exam for HS-12, reference MWR 940509.

P17-03 Preservice exam for R84, reference RRM 94-0016.

P18-03 Preservice exam for SK2, reference RRM 94-0015.

R09-03 Re-examination required in accordance with IWA-4500(a), reference IDR 94U1-7P029.

R10-03 Re-examination required in accordance with IWA-4500(a), reference IDR 94Ul-7P037.

R11-03 Re-examination required in accordance with IWA-4500(a), reference IDR 94U1-7P015.

R12-03 Re-examination required in accordance with IWA-4500(a), reference IDR 94UI-7P028.

R13-03 Re-examination required in accordance with IWA-4500(a), reference IDR 94U1-7P022.

R14-03 Re-examination required in accordance with IWA-4500(a), reference IDR 94U1-7P012.

S01-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR 7-P-009, Outage 01, Interval 03.

S02-03 Successive examinations required in accordance with IWF-2424(b),

reference IDR 7-P-010, Outage 01, Interval 03.

S03-03 Successive examinations required in accordance with IWF-2420(b),

reference IDR 7-P-011, Outage 01, Interval 03.

WISCONSIN ELECTRIC POINT BEACH NUCLEAR PLANT, UNIT 1 Interval 03 Period 02 Outage 01 EXREQ = 86E-03 (Outage Sumnary Report - NIS-1)

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Paga Ko.

1 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Consnercial Se.rvice Date: 12/21/70 COMPCPENT IDENTIFICATION ISI EXAM RELIEF MATL A COMPDIA PROGRM JND COMPONENT DESCRIPTION ISOMETRIC No.

METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT.

REUQS, CREDIT M EXAM NOTES C*tegory B-F Item Ptsber: 85.40 PZR-SURGEN02-SE 14.000 SAFE-END TO N0ZZLE ISI-PRI-1105 RT 1.114 04/06/94 94RT-2-WE-01 P

Y N

RT IN LIEU OF UT DUE TO CONFIGLGATION.

1 l

~. _

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1

[

Pega No.

2 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Consnercial Service Date: 12/21/70 00KfMT IDENTIFICATION ISI QA_M RELIEF MATL A COMP 01A PROGRM IND COMPONENT DESCRIPTION ISOMETRIC No.

METHCD REQUEST MATL 8 NOMTHICK EXAMDATE SumARY SHT.

RESULTS CREDIT M EXAM NOTES i

Category B-G-1 Item nmber: B6.40 RPV-FLIG-17 0.000 l

FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSISLE - ESSENTIALLY 100%

OF VOLUME EXAMINE 0.

RPV-FLIG-18 0.000 FLAXGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" OF FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

RPV-FLIG-19 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94ul-165P001 P

Y N

0.7" OF FLANGE SURFACE NOT ACCESSISLE - ESSENTIALLY 100%

OF VOLUME EXAMINE 0.

RPV-FLIG-20' O.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIELE - ESSENTIALLY 100%

i OF VOLUME EXAMINED.

RPV-FLIG-21 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

+

OF WOLUME EXAMINE 0.

RPV-FLIG 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" OF FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF WOLUME EXAMINED.

t

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Prge o,

3 xi 231 West Michigan Avenue 6610 Nuclear Road J

08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Corynercial Service Date: 12/21/70 COMPCCENT IDENTIFICATION IS1

[X_AM RELIEF MATL A COMPDIA PROGRM ))@

COMPC:*ENT DESCRIPTION ISOMETRIC NO.

PETHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CREDIT M EXAM NOTES RPV-FLIG-23 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

RPV-FL1G-24 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

RPV-FLIG-25 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

RPV-FLIG-26 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

RPV-FLIG-27 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

RPV-FLIG-28 0.000 FLANGE LIGAMENT IS!-PRI-1103 UT 0.000 04/08/94 94U1-165POO1 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

_m..

...m...

. =..

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Pegs to.

4 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Commercial Service Date: 12/21/70 COMPCPENT IDENTIFICATION M

EXAM RELIEF MATL A CONPDIA PROGRM M COMPONENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SNT.

RESULTS CREDIT TYP EXAM NOTES RPV-FLIG-29 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

RPV-FLIG-30 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" Of FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

RPV-FLIG-31 0.000 FLANGE LIGAMENT ISI-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

0F VOLUME EXAMINED.

RPV-FLIG-32 0.000 FLK.NGE LIGAMENT

- ISt-PRI-1103 UT 0.000 04/08/94 94U1-165P001 P

Y N

0.7" 0F FLANGE SURFACE NOT ACCESSIBLE - ESSENTIALLY 100%

OF VOLUME EXAMINED.

j i

j

't t

i 1

1 m

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Pce2 Do.

5 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPONENT IDENTIFICATION JSL EjLA5 REllEF MATL A COMPOIA PROGRM ikD_

CCMPONENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL 8 NOMTHICK EXA> SATE

SUMMARY

SHT.

RESULTS CREDIT

TJ_P, EXAM NOTES P

Category B-J ltem Ntsnber: 89.11 AC-06-SI-1001-09 6.000 PIPE TO ELBOW ISt-PRI-1127 PT 0.562 04/06/94 94U1-451P019 P

Y N

AC-06-SI-1001-09 6.000 PIPE TO ELBOW ISI-PRI-1127 UT 0.562 04/06/94 94U1-161P007 P

Y G

CC-06-St-1001-16 6.000 ELBOW TO PIPE ISt-PRI-1127 PT 0.562 04/06/94 94U1-451P020 P

Y N

OC-06-S1-1001-16 6.000 ELBOW T0 PIPE ISI-PRI-1127 UT 0.562 04/06/94 94U1-161P008 P

Y G

AC-10-AC-1001-16 10.000 PIPE TO ELBOW ISt-PRI-1122 PT 1.000 04/12/94 94U1-451P039 P

Y N

QC-10-AC-1001-16 10.000 P!PE TO ELBOW ISI-PRI-1122 UT 1.000 04/12/94 94U1-161P011 P

Y N

RC-04-PR-1001-09 4.000 i

ELBOW TO FLANGE ISt-PRI-1131 PT 0.438 04/13/94 94U1-451PO41 P

Y R

TWO ROUNDED IN01 CATIONS THAT MEET ASME XI ACCEPTANCE CRITERIA.

l OC-04-PR-1001-09 4.000 ELBOW TO FLANGE ISI-PRI-1131 UT 0.438 04/13/94 94U1-161P014 P

Y N

RC-04-PR-1002-04 4.000 PIPE TO ELBOW ISI-PRI-1131 PT 0.438 04/13/94 94U1-451PO42 P

Y N

l

Wisconsin Electric Power Cocpany Point Beach Nuclear Plant, Unit 1 Page to.

6 XI 231 West Michigan Avenue 6610 Nuclear Road 03/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPONENT IDENTIFICATION ISI M

RELIEF MATL A COMPO!A PROGRM IND COMPONENT DESCRIPil0N ISOMETRIC NO.

METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CREDIT M EXAM WOTES RC-04-PR-1002-04 4.000 PIPE TO ELBOW ISI-PRI-1131 UT 0.438 04/13/94 94U1-161P015 P

Y G

RC-04-PSF-1001-04 4.000 TEE TO REDUCER ISI-PRI-1135 PT 0.438 04/13/94 94U1-451PO40 P

Y R

PT thDICATION MEETS ACCPETANCE CRITERIA.

RC-04-PSF-1001-04 4.000 TEE TO REDUCER ISI-PRI-1135 UT 0.438 04/13/94 94U1-161P013 P

Y G

RC-10-AC-1001-06 10.000 ELBOW TO PIPE ISI-PRI-1122 PT 1.000 04/12/94 94U1-451P038 P

Y P

TWO ROUNDED INDICATIONS THAT MEET ASME XI ACCEPTANCE CRITERIA.

RC-10-AC-1001-06 10.000 ELBOW TO PIPE ISI-PRI-1122 UT 1.000 04/13/94 94U1-161e012 P

Y N

Item Number: B9.21 RC-03-BP-1002-06 3.000 PIPE TO ELBOW ISI-PRI-1137 PT 0.438 04/11/94 94U1-451P027 P

Y N

RC-03-PS-1001-14 3.000 PIPE TO ELBOW ISI-PRI-1133 PT 0.438 04/11/94 94U1-451P036 P

Y N

ARC STRIKE - NO BLEED OUT.

RC-03-PS-1001-15 3.000 ELBOW TO PIPE ISI-PRI-1133 PT 0.438 04/11/94 94U1-451P037 P

Y N

RC-03-PS-1002-17 3.000 PIPE TO ELBOW ISI-PRI-1134 PT 0.438 04/13/94 94U1-451PO43 P

Y N

CORRESPOND WITH TOP OF PRESSURIZER EXAMS.

Wisconsin Electric Power Cocpany Point Beach Nuclear Plant, Unit 1 POge Co.

7 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPC'ENT IDENTIFICATI0ei ISI EXAM RELIEF MATL A COMPDIA PROGRM JNO COMPONENT DESCR!PTION ISOMETRIC NO.

METHOD REQUEST MATL 8 NOMTHICK [XAMDATE

SUMMARY

SNT.

RESULTS CREDIT TyP EXAM NOTES RC-03-PS-1002-18 3.000 ELBOW TO PIPE ISI-PRI-1134 PT 0.438 04/13/94 94U1-451PO44 P

Y N

Item Ntster: 89.40 CtfC ACH-1001 -15 2.000 PIPE TO ELBOW ISI-PRI-1151 PT 0.344 04/11/94 94U1-451P030 P

Y N

CVC-02-ACH-1001-16 2.000 ELBOW TO P!PE ISI-PRI-1151 PT 0.344 04/11/94 94U1-451P029 P

Y N

CtfC-02-PSI -1001-31 2.000 PIPE TO ELBOW ISI-PRI-1143 PT 0.344 04/06/94 94U1-451P018 P

Y N

CtfC-02-P SI-1001 -35 2.000 PIPE TO ELBOW ISI-PRt-1142 PT 0.344 04/06/94 94U1-451P017 P

Y N

CtfC-02-PSI-1001-49 2.000 PIPE TO ELBOW IS!-PRI-1142 PT 0.344 04/07/94 94U1-451P023 P

Y N

CVC-02-PSt-1001-50 2.000 ELBOW 10 PlPE ISt-PRI-1142 PT 0.344 04/07/94 94U1-451P024 P

Y N

i l

CtfC-02-PSt-1002-14 2.000 2LBOW TO PIPE ISI-PRI-1144 PT 0.344 04/11/94 94U1-451P032 P

Y N

ADDED TO DATABASE 03/10/89 l

l CtfC-02-PSI-1002-16 2.000 ELBOW TO PIPE ISI-PRI-1144 PT 0.344 04/11/94 94U1-451P031 P

Y N

l l

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Pagi Ko.

8 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Corsnercial Service Date: 12/21/70 COMPo*'ENT IDENTIFICATION ISI EXAM RELIEF MATL A COMPDIA PROGRM IND COMPC"ENT DESCRIPfl0N ISOMETRIC WO.

METHOD REQUEST MATL B NOMTHICIC EXAMDATE

SUMMARY

SdT.

REsutTS CREDIT M EXAM NOTES cvC-02-PSI-1002-37 2.000 PIPE TO VALVE CV-3048 ISI-PRI-1145 PT 0.344 04/11/94 94U1-451P028 P

Y N

AC-02-SP-1004-15 2.000 PIPE TO EL80W ISI-PRI-1137 PT 0.344 04/11/94 94U1-451P025 P

Y N

RC-02-LD-1001-07 2.000 TEE TO PIPE ISI-PRI-1146 PT 0.344 04/11/94 94U1-451P026 P

Y N

SIS-02-SI-1001-08A 2.000 PIPE TO COUPLING ISI-PRI-1128 PT 0.344 04/05/94 94U1-451P015 P

Y N

SIS-02-St-1001-088 2.000 CDUPLING TO PIPE ISI-PRI-1128 PT 0.344 04/05/94 94U1-451PG14 P

Y N

SIS-02-St-1003-17 2.000 PIPE TO ELBOW ISI-PRI-1130 PT 0.344 04/05/94 94U1-451P013 P

Y N

Sis-02-SI-1003-22 2.000 ELBOW TO PIPE ISI-PRI-1130 PT 0.344 04/06/94 94U1-451P016 P

Y R

SURFACE IRREGULARITY - EUFFE0 OUT RRM 94-0030.

SI S-02-SI - 1004-07A 2.000 PIPE TO TEE ISI-PRI-1150 PT 0.344 04/05/94 94U1-451P009 P

Y N

SIS-02-St-1004-08A 2.000 TEE TO PIPE ISI-PRI-1150 PT 0.344 04/05/94 94U1-451P008 P

Y N

Sis-02-St-1004-24 2.000 ELBOW TO PIPE ISt-PRI-1150 PT 0.344 04/11/94 94U1-451P033 P

Y N

Wisconsin Electric Power Capany Point Beach Nuclear Ptar:t, Unit 1 Page Co.

9 XI 231 t_est Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Camercial Service Date: 12/21/70 COMPC'ENT IDENTIFICATION j_SJ M

RELIEF MATL A COMPOIA PRCCRM M S

C@PCDENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL B NOMTHICK EXAMDATE StMMARY SL RESULTS CREDIT

TIP, EXAM NOTES SIS-02-SI-1004-25 2.000 PIPE TO ELBOW ISI-PRI-1150 PT 0.344 04/11/94 94U1-451P034 P

Y N

Sis-02-SI-1004-28 2.000 ELBOW 10 PIPE ISI-PRI-1150 PT 0.344 04/11/94 94ul-451P035 P

Y N

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page to.

10 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 CNPONENT IDENTIFICATION ISI GAM RELIEF MATL A COMPOIA PROGRM M COMPCEENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL B NOMTHICK EXAMDATE StMMARY SHT.

RESULTS CREDIT TJ,P, EXAM NOTES P

Category C-C ltem Nteber: C3.20 M-19-IWA 30.000 IXTEGRALLY WELDED ATTACHMENT ISI-PRI-1242 MT 0.000 04/15/94 94U1-350P001 P

Y R

UNDERCUT DETERMINED TO BE ACCEPTABLE.

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page No.

11 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Oocket No. 50-266 Commercial Service Date: 12/21/70 COMPONENT IDENTIFICATION 151

[XA$

RELIEF MATL A COMPDIA PROGRM INQ COMPONENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CEEDIT

[YP EXAM NOTES Category C-F-1 Item Ftsrber: C5.118 AC-08-RHR-1004-07 8.000 ELBOW TO PIPE ISI-PRI-1228 PT 0.322 03/10/94 94U1-451P006 P

Y N

AC-08-RNR-1004-07 8.000 ELBOW TO PIPE ISI-PRI-1228 UT 0.322 03/15/94 94U1-161P006 P

Y N

AC-10-RHR-1001-08 10.000 ELBOW TO PIPE ISI-PRI-1220 PT 0.365 03/11/94 94U1-451P005 P

Y R

AC-10-RNR-1001-08 10.000 ELBOW TO PIPE ISt-PRI-1220 UT 0.365 03/10/94 94U1-161P005 P

Y N

AC-10-RHR-1001-34 10.000 ELBOW TO P!PE ISI-PRI-1221 PT 0.365 04/07/94 94U1-451P021 P

T N

ARC STRIKES IN VICINITY -

ACCEPTABLE AC-10-RHR-1001-34 10.000 ELBOW TO PIPE ISI-PRI-1221 UT 0.365 04/07/94 94U1-161P009 P

Y N

AC-10-RNR-1004-05 10.000 PIPE TO ELBOW IS!-PRI-1223 PT 0.365 03/14/94 94U1-451P004 P

Y N

AC-10-RHR-1004-05 10.000 PIPE TO ELBOW ISI-PRI-1223 UT 0.365 03/14/94 94U1-161P004 P

Y N

AC-10-RHR-1006-05 10.000 P!PE TO ELBOW ISI-PRI-1224 PT 0.365 04/07/94 94U1-451P022 P

Y N

Wisconsin Electric Power Coppany Point Beach Nuclear Plant, Unit 1 Paga No.

12 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Cocimercial Service Date: 12/21/70 COMPC"ENT IDENTIFICATION J SJ, E]M RELIEF MATL A COMPDIA PROGRM JND COMPONENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL B NOMTHICK QAMDATE

SUMMARY

SHT.

RESULTS CREDIT M EXAM NOTES AC-10-RNR-1006-05 10.000 PIPE TO ELBOW ISI-PRI-1224 UT 0.365 04/07/94 94U1-161P010 P

Y N

Item Ntsnber: C5.21 SIS-04-SI-1002-09 4.000 PIPE TO ELBOW ISI-PRI-1236 PT 0.337 03/08/94 94U1-451P001 P

Y I

9/32" NICK IN WELD N.A.Z. NOT INSERVICE RELATED SIS-04-SI-1002-09 4.000 PIPE TO ELBOW ISt-PRI-1236 UT 0.337 03/08/94 94U1-161P001 P

Y N

SIS-04-St-1005-04 4.000 PIPE TO ELBOW ISI-PRI-1255 PT 0.337 03/08/94 94U1-451P002 P

Y R

CRATER CRACK THAT NEETS ASME XI ACCEPTANCE CRITERIA.

SIS-04-SI-1005-04 4.000 PIPE TG ELBOW ISI-PRI-1255 UT 0.337 03/08/94 94U1-161P002 P

Y N

SIS-04-St-1006-23 4.00')

ELBOW TO PIPE ISt-PRI-1253 PT 0.337 03/08/94 94ut-451P003 P

Y N

SIS-04-SI-1006-23 4.000 EL60W TO PIPE ISt-PRI-1253 UT 0.337 03/08/94 94U1-161P003 P

Y N

Item Ntaber: C5.30

$1S-02-SI-1005-08 2.000 PIPE TO TEE ISI-PRI-1249 PT 0.344 04/05/94 94U1-451P012 P

Y N

Wisconsin Electric Power Cospany Point Beach Nuclear Plant, Unit 1 Page Co.

13 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Connercial Service Date: 12/21/70 CCMPCENT IDENTIFICATION JSI EXAM REllEF MATL A COMPDIA PROGRM IND COMPONENT DESCRIPTION ISOMETRIC WO.

METHOD REQUEST MATL 8 NOMTHICK

[XAMDATE

SUMMARY

SHT.

RESULTS CREDIT M EXAM h0TES SIS-02 SI-1008-07 2.000 ELS0W TO PIPE ISI-PRI-1251 PT 0.344 04/05/94 94U1-451P011 P

Y N

SIS-02-SI-1009-03 2.000 ELBOW TO PIPE ISI-PRI-1251 PT 0.344 04/05/94 94U1-451P010 P

Y N

SIS-02-St-1010-12 2.000 PIPE TO VALVE St-876A ISt-PRI-1256 PT 0.344 03/22/94 94U1-451P007 P

Y N

SIS-02-SI-1010-31 2.000 ELBOW TO PIPE ISI-PRI-1258 PT 0.344 04/18/94 94U1-451PO45 P

Y N

SIS-02-St-1011-07 2.000 ELBOW TO PIPE ISI-PRt-1257 PT 0.344 04/18/94 9401-451PO46 P

Y N

Wisconsin Electric Power Company Point Beach Nuclear Plant, tJnit 1 Paga Ko.

14 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Coninercial Service cate: 12/21/70 COMPCf'ENT IDENTIFICATION ISI EXAM RELIEF MATL A COMPDIA PROGRH JND COMPONENT DESCRIPTION ISOMETRIC No.

METHOD REGUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CREDIT M EXAM NOTES Category F-A Item Ntster: N/A A-03 8.000 ANCHC2 ISI-PRI-1331 VT-3 0.000 04/11/94 94U1-750P116 P

Y N

A-04A 8.000 ANCHOR ISI-PRI-1329 VT-3 0.000 04/05/94 94U1-750P075 P

Y N

A-15 10.000 ANCHOR ISI-PRI-1224 VT-3 0.000 04/06/94 94U1-750P100 P

Y N

Wisconsin Electric Peteer Carparty Point Beach Nuclear Plant, Unit 1 Ptge No.

15 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers. Wisconsin 54241 Docket No. 50-266 Commercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M

M REllEF MATL A COMPDIA PROGRM M COM M ENT DESCRIPfl0N ISOMETRIC NO.

METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CRE0li

TYP, EXAM NOTES Crtecory F-B Item Wunber: N/A 24-12-PRB 2.000 RIG!D SUPPORT ISI-PRI-1150 VT-3 0.000 04/05/94 94U1-750P073 P

Y N

24-12-PRC 2.000 RIGID SUPPORT ISI-PRI-1150 VT-3 0.000 04/05/94 94U1-750P079 P

Y N

26-07-PR 2.000 RIGID SUPPORT ISI-PRI-1128 VT-3 0.000 04/05/94 94U1-750P077 P

Y N

2v-16-PSS 2.000 RIGID SUPPORT ISt-PRI-1130 VT-3 0.000 04/05/94 94U1-750POSO P

Y N

t 41-01-PRC 2.000 RIGID SUPPORT ISt-PRI-1141 VT-3 0.344 04/08/94 94U1-750P110 P

Y N

41-07-PRB 2.000 RIGID SUPPORT ISI-PRI-1141 VT-3 0.000 04/08/94 94U1-750P108 P

Y N

41-14-PR 2.000 RIGID SUPPORT ISI-PRI-1141 VT-3 0.000 04/08/94 94U1-750P109 P

Y N

6H 02 8.000 RIGID SUPPORT ISI-PRI-1226 VT-3 0.000 03/10/94 94U1-750P032 P

Y I

SLIDE PLATE 2" OFF CENTER A-02 10.000 ANCHC2 ISI-PRI-1124 VT-3 0.000 04/05/94 94U1-750P071 P

Y N

Wisconsin Electric Power Company Point beach Nuclear Plant, Unit 1 Page Co.

16 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M

M REllEF MATL A COMPDIA PROGRM

]N_00 COMPONENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CREDIT EP, EXAM NOTES A-04 3.000 ANCHOR ISI-PRI-1134 VT-3 0.000 04/13/94 94U1-750P127 P

Y N

A-05 10.000 ANCHO ISI-PRI-1122 VT-3 0.000 04/08/94 94U1-750P103 P

Y N

A-112 14.000 ANCHO ISI-PRI-1326 VT-3 0.000 04/04/94 94U1-750P066 P

Y N

H-060 24.000 RIGID SUPPORT ISI-PRI-1323 VT-3 0.000 03/07/94 94U1-750P004 P

Y N

H-203 10.000 RIGID SUPPORT ISI-PRI-1222 VT-3 0.000 04/05/94 94U1-750P068 P

Y I

GENERAL CORROSION ON BASE PLATE H-205 10.000

  • 1GID SUPPORT ISI-PRI-1223 VT-3 0.000 04/05/94 94U1-750P069 P

Y N

CORROSION ON BASE PLATE H-31 6.000 ANCHOR ISI-PRI-1333 VT-3 0.000 03/07/94 94U1-750P003 P

Y N

H-35 4.000 ANCHOR ISI-PRt-1335 VT-3 0.000 0?/05/94 94U1-750P082 P

Y N

H-73 14.000 RIGID SUPPORT ISI-PRI-1328 VT-3 0.000 03/16/94 94U1-750PO49 P

Y N

HBB 8.000 RIGID SUPPORT ISt-PRI-1331 VT-3 0.000 04/11/94 94U1-750P115 P

Y N

Wisconsin Electric Pcuer Conpany Point Beach Nuclear Plant, Unit 1 Ptge No.

17 x!

231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPC~ENT !DENTIFICATION ISI EXAM RELIEF MATL A COMPDIA PROGRM IND COMPOrENT DESCt!PilON ISOMETRIC NO.

MET HCD REOUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CREDIT T V.P, EXAM NOTES P

PSA-001-3 10.000 ANCHClt IS!-PRI-1337 VT-3 0.000 04/04/94 94U1-750P067 P

Y N

R-149 10.000 RIGID SUPPORT ISI-PRI-1224 VT-3 0.000 04/08/94 94ut-750P111 P

Y W

R-198 6.000 RIGID SUPPORT ISt-PRI-1239 VT-3 0.000 04/06/94 94U1-750P098 P

Y N

R-208 8.000 RIGID SUPPORT ISI-PRI-1330 VT-3 0.000 04/05/94 94U1-750P074 P

Y N

R-303 6.000 RIGID SUPPORT ISI-PRI-1247 VT-3 0.000 03/09/94 94U1-750P009 P

Y N

R-35 3.000 RIGID SUPPORT IS!-PRl-1134 VT-3 0.000 G4/11/94 94U1-750P118 P

Y N

R-47 10.000 RIGID SUPPORT ISI-PRI-1122 VT-3 0.000 04/08/94 94U1-750P101 P

Y N

R-68 3.000 RIGID SUPPORT ist-PRI-1133 VT-3 0.000 04/06/94 94U1-750P095 P

Y N

R-70A 3.000 RIGID SUPPORT ISt-PRI-1138 VT-3 0.000 04/06/94 94U1-750P093 P

Y N

R-78 3.000 RIGID SUPPORT IS!-PRI-1133 VT-3 0.000 04/06/94 94U1-750P094 P

Y N

RC-07 3.000 CONSit.NT SUPPORT ISI-PRI-1134 VT-3 0.000 04/13/94 94U1-750P128 P

Y N

Wisconsin Electric Power Capany Point Beach Nuclear Plant, Unit 1 Pcee Co.

18 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers Wisconsin 54241 Docket No. 50-266 cmunercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M

JM RELIEF MATL A COMPDIA PROGRM J N,D,D (OMPOWENT DESCRIPTION ISOMETRIC NO.

MET Hm REOUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CREDIT M EXAM NOTES DCP-A-LEG-2 0.000 COMPONENT SUPPORT ISi-PRI-1108 VT-3 0.000 04/08/94 94U1-750P106 P

Y N

RHR-A-LEG-2 0.000 COMPONENT SUPPORT ISI-PRI-1204 VT-3 0.000 03/10/94 94u1-750P031 P

Y N

S-524 24.000 RIGID SUPPORT ISI-PRI-1324 VT-3 0.000 04/05/94 94U1-750P081 P

Y I

GENERAL CORROSION ON BOTTOM PIPE SADDLE.

S-735 6.000 RIGID SUPPORT ISI-PRI-1235 VT-3 0.000 03/11/94 94U1-750PO41 P

Y N

SG-A-MAIN SUPPORT-1 0.000 COMPCSENT SUPPORT ISt-PRI-1202 VT-3 0.000 04/08/94 94U1-750P105 P

Y N

SI-03 6.000 RIGID SUPPORT ISI-PRI-1129 VT-3 0.000 04/05/94 94U1-750P070 P

Y N

SLWHX-LEG-3 0.000 COMPONENT SUPPORT ISI-PRI-1205 VT-3 0.000 03/10/94 T401-750P023 P

Y N

l i

l l

Wisconsin Electric Power Ccepany Point Beach Nuclear Plant, Unit 1 Page Mo.

19 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 i

l Docket No. 50-266 l

Conmercial Service Date: 12/21/70 I

l COMPCf'ENT IDENTIFICATION M

M RELIEF MATL A COMPOIA PROGRM J ND,D COMPC"ENT DESCRIPTION ISOMETRIC No, METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SMT.

RESULTS CREDIT g EXAM NOTES I

Category F-C ltem haber: N/A 1H-01A 6.000 SPRING HANGER ISI-PRI-1236 VT-3 0.000 03/09/94 94U1-750P014 P

Y I

PIPE 3" 0FF CENTER - toad HIGHER THAN COLD REQUIRED RANGE.

1H-03 10.000 SPRIEG HAEGER ISI-PRI-1223 vi-3 0.000 03/17/94 94U1-750P056 P

Y R

ACTUAL LOAD IS HIGHER THAN REQUIRED SETTING 1H-03A 6.000 SPRING HANGER ISI-PRI-1236 VT-3 0.000 03/09/94 94ut-750P015 P

Y N

2H-02 8.000 SPRING HANGER ISI-PRI-1222 VT-3 0.000 04/22/94 94U1-750P033 P

Y R

SPRikG CAN LOAD SETTING LOWERED THAN REQUIRED RANGE.

2H-02A 6.000 SPRING HANGER ISI-PRI-1238 VT-3 0.000 03/10/94 94U1-750P0i7 P

Y N

2H-07 6.000 RIGlD SUPPORT ISI-PRI-1238 VT-3 0.000 04/28/94 94U1-7",0P038 P

Y R

FILLET WELDS UNDERS12CD EVALUATED TO BE AC2*IABLE.

36-22-PSSA 2.000 RIGID SUPPORT ISI-PRt-1136 VT-3 0.000 04/08/94 94U1-750P102 P

Y N

39-16-PSSA 2.000 i

RIGID SUPPORT ISt-PRI-1151 VT-3 0.000 04/11/94 94U1-750P117 P

Y N

UNDER GRATING.

I

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page leo. 20 MI 231 West Michigan Averm 6610 Nuclear Road 0410/94 Milwaukee, Wisconsisi 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Commercial Service Date: 12/21/70 COMPONENT IDENTIFICATION.

In M

RELIEF MATL A COMPO!A PROGRM M COMPCPENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL 8 NOMTHICK EXA80 ATE

SUMMARY

SMT.

RESULTS CREDIT ITP EKAM NOTES 3H-01 10.000 RIGID SUPPORT ISI-PRI-1223 VT-3 0.000 03/17/94 94U1-750P054 P

Y R

GROUT PAD CRACKED AND DIS!NTEGRATING UNDER PLATE 3H-01A 6.000 SPRIXG HANGER ISI-PRI-1248 VT-3 0.000 03/09/94 9401-750P010 P

Y N

3H-02 10.000 SPRING HANGER ISI-PRI-1222 VT-3 0.000

.03/17/94 94U1-750P055 P

Y R

ACTUAL LOAD IS NIGNER THAN REQUIRED COLD SETTING.

40-16-PR 2.000

' RIGID SUPPORT ISI-PRt-1140 VT-3 0.000 04/11/94 9401-750P124 P

Y N

42-10-PSSA 2.000 RIGID SUPPORT ISI-PRI-1143 VT-3 0.000 04/07/94 94U1-750P084 P

V N

42-20-PSSA 2.000 ElGIO SUPPORT ISI-PRI-1143 VT-3 0.000 04/08/94 94U1-750P104 P

Y N

43-12-PH 2.000 RIGID SUFPORT ISt PRI-1144 VT-3 0.000 04/11/94 94U1-750P122 P

Y N

44-07-PRB 2.000 RIGID SUPPORT ISt-PRI-1146 VT 3 0.000 04/11/94 94U1-750P120 P

Y N

44-09-PRA 2.000 RIGID SUPPORT ISt-PRI 1146 VT 0.000 04/11/94 94U1-750P119 P

Y N

44-23-PSSA 2.000 R1(33 SUPPORT ISI-PRt-1147 VT-3 0.000 04/11/94 94U1-750P121 P

Y N

m Wisconsin Electric Power Compary Point Beach Nuclear Plant, Unit 1 4

Ptge 20. '21 XI 231 West Michigan Avenue 6610 Nuclear Road CS/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comunercial Service Date: 12/21/70 COMPONENT IDENTIFICATION j_SJ

f_XAM, RELIEF MATL A COMPOIA PROGRM JND S

f COMPONENT DESCRIPTION ISOMETRIC ho.

METHOD REQUEST MAYL 8 NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CREDIT g EXAM NOTES 4H-02 8.000 SPRikG HANGER ISI-PRI-1227 VT-3 0.000 03/30/94 94U1-750P058 P

Y N

4H-04 8.000 SPRING HANGER ISI-PRI-1228 VT-3 0.000 03/10/94 94U1-750P029 P

Y I

SUPPORT 2" OFFCENTER OF THE LOAD FLANGE.

6H-07 8.000 SPRING HANGER ISI-PRI-1229 VT-3 0.000 03/10/94 94U1-750P024 P

Y N

[

4 6H-10 10.000 SPRING HANGER ISI-PRI-1220 VT-3 0.000 03/10/94 94U1-750P039 P

Y N

6H-13 8.000 SPRING HANGER ISI-PRI-1229 VT-3 0.000 04/22/94 94U1-750P025 P

Y R

LOAD HIGHER THAN REQUIRED SETT!kG 6H-16 6.000 RIGID SUPPORT ISI-PRI-1232 VT-3 0.000 03/10/94 94U1-750P022 P

Y N

6E-20 6.000 SPRING HANGER ISI-PRI-1248 VT-3 0.000 03/09/94 94U1-750P011 P

Y N

6H-25 6.000 SPRIEG HANGER ISI-PRI-1231 VT-3 0.000 03/10/94 94U1-750P028 P

Y R

ACTUAL LOAD IS LOWER THAN REQUIRED SETTING.

6H-27 6.000 i

SPRING HANGER ISI-PRI-1231 VT-3 0.000 03/10/94 94ul-750P02T P

Y N

6H-33 10.000 SPRING HANGER ISI-PRI-1220 VT-3 0.000 04/27/94 9401-750PO40 P

Y R

ACTUAL LOAD (1320) LOWER THAN REQUIRED SETTING.

I

.m

-- - s.

d---

'r Y %

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 P ge No.

22 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Connercial Service Date: 12/21/70 COMPONENT lDENTIFICATION JSI

MAM, REllEF MATL A COMPD!A PROGRM JNQ COMPC**ENT DESCRIPTION ISOMETRIC NO.

METHOD REOUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CRfDji M EXAM NOTES R

A-16 10.000 ANCHC2 ISI PRI-1123 VT-3 0.000 04/11/94 94U1-750P123 P

Y W

CS-02 6.000 SPRING HANGER ISt-PRI-1260 VT-3 0.000 03/09/94 94U1-750P016 P

Y N

NAME PLATE DAMAGED - EVALUATED ACCEPTABLE H-10A 6.000 RIGID SUPPORT ISI-PRI-1322 VT-3 0.000 03/07/94 94U1-750P002 P

Y N

H-110 6.000 RIGID SUPPORT ISI-PRI-1348 VT-3 0.000 03/16/94 94U1-750P053 P

Y N

H-19 30.000 SPRIRG HANGER ISt-PRI-1242 VT-3 0.000 03/22/94 94U1-750P060 P

Y I

SCALE PLATE MISSING - LOADS EVALUATED TO BE ACCEPTABLE.

H-19A 6.000 RIGID SUPPORT IS!-PRt-1323 VT-3 0.000 03/09/94 94U1-750P017 P

Y N

H-26 3.000 RIGID SUPPORT ISI-PRI-1322 vi-3 0.000 03/07/94 94U1-750P001 P

Y N

H-53 6.000 RIGID SUPPORT ISI-PRI-1325 VT-3 0.000 03/07/94 94U1-750P005 P

Y N

H-60 24.000 RIGID SUPPORT ISI-PRI-1327 VT-3 0.000 04/05/94 94U1-750P091 P

Y N

H-84 14.000 RIGID SUPPORT IS!-PRI-1326 VT-3 0.000 03/16/94 94U1-750PO42 P

Y N

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page Co.

23 xt 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Commercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M

M RELIEF MATL A COMPO!A PROGRM M COMPONENT DESCRIPTION ISOMETRIC NO.

METH00 REQUEST MATL B NOMTHICK ExAMDATE

SUMMARY

SHT.

RESULTS CREDIT M EXAM NOTES H-91 10.000 RIGID SUPPORT ISI-PRI-1326 VT-3 0.000 03/16/94 94U1-750PO43 P

Y N

H-95 20.000 RIGID SUPPORT ISI-PRI-1328 VT-3 0.000 C3f16/94 94t ' - 750P050 P

Y I

GENERAL CORROSION ON SUPPORT.

MS-05 0.000 SNUBBER IS!-PRI-1201 VT-3 0.000 04/14/94 94ut-750P134 P

Y N

HS-07 0.000 SNU8CER ISI-PRI-1201 VT-3 0.000 04/14/94 94U1-750P136 P

Y N

HS-09 0.000 SNUESER ISI-PRI-1201 VT-3 0.000 04/14/94 94U1-750P135 P

Y N

HS-13 6.000 SCUSSER ISI-PRI-1129 VT-3 0.000 04/09/94 94U1-750P114 P

Y I

INCOMPLETE THREAD ENGAGEMENT 04 STRUCTURE BOLTS.

HS-14 3.000 SNUBBER ISI-PRI-1135 VT-3 0.000 04/13/94 94U1-750P129 P

Y N

HS-22A 3.000 SNUSBER ISI-PRI-1135 VT-3 0.000 04/13/94 94U1-750P131 P

Y N

HS-51 3.000 SNUBBER ISI-PRI-1135 VT-3 0.000 04/13/94 94U1-750P130 P

Y N

MSH-02 30.000 SPRING HANGER ISt-PRI-1262 VT-3 0.000 04/05/94 94U1-750P088 P

Y N

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Page Co.

24 XI 231 West Michigan Avenue 6610 Nuclear Road 08/90/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPCT NT IDENTIFICATION ISI M

RELIEF MATL A COMPDIA PROGRM ikD COMPONENT DESCRIPTION ISOMETRIC No.

METHOD REQUEST MATL B NOMTHICC EXAMDATE

SUMMARY

SMT.

RESULTS CREDIT lY_P EXAM NOTES MSH-04 30.000 SPRING HANGER ISI-PRI-1261 VT-3 0.000 04/05/94 94U1-750P089 P

Y N

R-350 8.000 SNUSCER ISI-PRI-1222 VT-3 0.000 03/10/94 94U1-750P035 P

Y R

NUT LOOSE ON PISTON END U1R21 R-356 8.000 SNUBBER ISI-PRI-1223 VT-3 0.000 03/10/94 94U1-750P036 P

Y N

DC-03 10.000 UARIABLE SPRING ISI-PRI-1126 VT-3 0.000 04/11/94 94U1-750P125 P

Y N

RC-04 6.000 VARIASLE SPRING ISI-PRI-1129 VT-3 0.000 04/09/94 94U1-750P113 P

Y I

CRACK IN ADJACENT 8UILDING STRUCTURE kOTED.

51-05 6.000 R!GID SUPPORT ISI-PRI-1127 VT-3 0.000 04/06/94 94U1-750P085 P

Y N

SI-078 6.000 RIGID SUPPORT ISI-PRI-1127 VT-3 0.000 04/06/94 94U1-750P099 P

Y N

SI-09 6.000 UARinBLE SPRING IS!-PRI-1127 VT-3 0.000 04/05/94 94U1-750P126 P

Y R

LOOSE NUTS AND OFFSET HANGER.

SI-16 4.000 RIGID SUPPORT ISI-PRI-1255 VT-3 0.000 03/10/94 94U1-750P020 P

Y N

SI-34 4.000 RIG!D SUPPORT ISI-PRI-1253 VT 3 0.000 04/05/94 94U1-750P076 P

Y N

Wisconsin Electric Power C a pany Point Beach Nuclear Plant, Unit 1 Page No.

25 XI 231 West Michigan Avenue 6610 Nuclear Road C2/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMP 0NENT IDENTIFICATION JS1 E

REllEF MATL A COMPDIA PROGRM M

M COMPONENT DESCRIPTION ISOMETRIC NO.

METNOO REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT.

RESULTS CREDIT JJP EXAM kOTES SI-36 4.000 RIGID SUPPORT ISI-PRI-1253 VT-3 0.000 04/08/94 94U1-750P107 P

Y N

St-38 4.000 RIGID SUPPORT ISI-PRI-1255 VT-3 0.000 03/10/94 94U1-750P019 P

Y N

S1-39 4.000 SPRING HANGER ISI-PRI-1255 VI-3 0.000 03/10/94 94U1-750P021 P

Y N

SI-44 4.000 QIGID SUPPORT ISI-PRI-1254 VT-3 0.000 03/09/94 94U1-750?006 P

Y N

SI-45 4.000 RIGID SUPPORT ISI-PRI-1254 VT-3 0.000 03/09/94 94U1-750F007 P

Y N

SI-56 4.000 AOCHC3 ISI-PRI-1252 VT-3 0.000 04/05/95 94U1-750P073 P

Y N

SI-61 4.000 RIGID SUPPORT ISI-PRI-1252 VT-3 0.000 04/05/94 94U1-750P072 P

Y N

SI-68 2.000 RIGID SUPPORT ISI-PRI-1256 vi-3 0.000 03/09/94 94U1-7509013 P

Y E

S1-71 2.000 RIGID SUPPORT ISI-PRI-1256 VT-3 0.000 03/09/94 94ut-750P012 P

Y N

SI-77 2.000 RIGID SUPPORT ISI-PRI-1258 VT-3 0.000 04/05/94 94U1-750P065 P

Y I

OVERSIZE HOLES FOR U-BOLT AND ONE END OF U-BOLT IS BENT.

l l

m

t l

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page No.

26 XI 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wiscoesin 54241 Docket ho. 50-266 Commercial Servire Date: 12/21/70 COMPONENT IDENYIFlCATION 11[

{g!!

(((((f, MATL A COMPOIA PROGRM lj@

COMP 0 KENT DESCRIPil0N ISOMETRIC NO.

METHOD REQUEST MATL B NOM 1 HICK EXAMDATE

SUMMARY

SHT.

RESULTS CREDIT IIP EXAM h0TES SI-G7 2.000 RIGID SUPPORT ISt-PRI-1259 VT-3 0.000 03/10/94 94U1-750PC18 P

Y R

MIDDLE NUT THREE THREADS BELOW FULL ENGAGEMENT.

Wonsin Electric Power Co.

231 West Mkhigan Avenue Milwaukee, WI 53201 Point Beach Nuclear Plant, Unit 1 6610 Nuclear Road Two Rivers, WI 54241 Docket 50-266 j

CommercialService Date 12/21/70 Additional Examinations (Pages 1A e 'd 2A)

WISCONSIN ELECTRIC POINT BEACH NUCLEAR PLANT, UNIT 1 Interval 03 Period 02 Outage 01 Additional Exarninations (Outage Stenary Report - NIS-1)

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Page t:o.

1A 231 West Michigan Avenue 6610 Nuclear Road l 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Connercial Service Date: 12/21/70 COMPC"E::T IDENTIFICATION

J_S_I, M

REL!EF MATL A COMPDIA PROGPM jkD St COMPCEST DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL 8 NOMiHICK EXAMDATE SUMMART SHT.

RESULTS CREDIT M EXAM NOTES EXREQ

A10-03 Cetwory F-B Rem /tsnber: N/A 1H-01 10.000 RIGID SUPPORT ISI-PRI-1223 VT-3 0.000 03/30/94 94U1-750P063 P

N N

6H-03 8.000 RIGID SUPPORT ISI-PRI-1226 VT-3 0.000 03/29/94 94U1-750P062 P

N N

6H-04 8.000 RIGID SUPPORT ISI-PRI-1225 VT-3 0.000 03/29/94 94U1-750P061 P

N N

3H-02A 10.000 SPRING HANGER ISI-PRI-1223 VT-3 0.000 03/30/94 94U1-750P087 P

N N

NO NAMEPLATE-LOAD EVALUATED AS ACCEPTABLE.

3H-05 8.000 RIGID SUPPORT IS!-PRI-1222 VT-3 0.000 04/06/94 94U1-750P096 P

W N

3H-08 8.000 SPRING HANGER ISI-PRt-1223 VT-3 0.000 03/30/94 94U1-750P086 P

N N

Wisconsin Electric Power Company Point Basch Euclear Plant, Lhit 1 E

- Page tio.

2A 231 West Michigan Avenue 6610 Nuclear Road

.C2/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Commercial Service Date: 12/21/70 COMPCrENT IDENTIFICATION M

EXAM M2 MATL A COMPDIA PROGRM M COMPCr'ENT DESCRIPTION ISOMETRIC No.

MEimi, Ry JEST MATL B NOMTHICK EXAMDATE SupetARY SHT.

RESULTS CREDIT M EXAM NOTES EXTEQ

A11-03 Categorv F-C Item Ntsber: N/A SI-64 2.000 RIGID SUPPORT ISI-PRI-1256 - VT-3 0.000 04/20/94 94U1-750P140 P

N N

SI-65 2.000 RIGID SUPPORT ISI-PRI-1256 VT-3 0.000 04/20/94 9401-750P139 P

W N

r SI-66 2.000 RIGID SUPPORT ISI-PRI-1256 VT-3 0.000 04/20/94 94ul-750P138 P

N N

i i

SI-72 2.000 RIGID SUPPORT ISI-PRI-1256 VT-3 0.000 04/20/94 94u1-750P137 P

W N

SI-74 2.000 RIGID SUPPORT ISI-PRI-1258 VT-3 0.000 04/20/94 94u1-750P141 P

N N

4 SI-75 2.000 RIGID SUPPORT ISI-PRI-1258 VT-3 0.000 04/20/94 94U1-750P142 P

W N

i -

honsin Electric Power Co.

231 West Michigan Avenue Milwaukee,WI $3201 Point Beach Nuclear Plant, Unit i 6610 Nuclear Road Two Rivers, W1 54241 Docket 50-266 ConunercialService Date 12/21/70 Preservice/ Baseline Examinations (Pages IP - 11P)

WISCONSIN ELECTRIC POINT BEACH N'JCLEAR PLANT, UNIT 1 Interval 03 Period 02 Outage 01 Preservice/ Baseline Exarninations (Outage Stanary Report - WIS-1)

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Psgt No.

1P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPC*ENT IDENTIFICATM,1 M RELIEF MATL A COMPDIA PROGRM M COMPONENT DESCRIPT!ON ISOMETRIC No. METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXREQ . P14-03 Category B-G-2 Item Nunber 87.20 P2R MWAY-BLT-01 THRu 16 0.000 MANWAY BOLTING ISt-PRI-1104 VT-1 0.000 04/16/94 94U1-750P152 P N N

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Page c:o. 2P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPONENT IDENTIFICATION in M REtIEF MATL A COMPDIA PROGRM M COMPONENT DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATL 8 WOMTHICK EXANDAE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXREQ

P15-03 Cetraory B-G-2 Item Pwber: 87.70 RC-427-BLT 0.000 VALVE BOLTING 2-IN GATE ISI-PRI-1146 VT-1 0.000 04/16/94 94U1-750P153 P

h N

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page to. 3P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Consnercial Service Date: 12/21/70 COMPONENT IDENTIFICATION Q [xAM ret.lEF MATL A COMPDIA PROGRM IND COMPC~ENT DESCRIPTION. ISOMETRIC NO. METHOD REQUEST MATL 8 NOMTHICK EMAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXPE9

P16-03 C*t'sory F-C ltem Number: N/A HS-12 6.000 SL*UBBER ISI-PRI-1127 vi-3 0.000 04/22/94 94UI-750P148 P

N N

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page to. 4P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Commercial Service Date: 12/21/70 COMPONENT IDENTIFICATION ISI EXA4 RELIEF MATL A COMPOIA PROGRM IND,O COMPONE*iT DESCRIPTION ISOMETRIC No. METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT. RESUtTS CREDIT M EXAM NOTES EXREQ - P17-63 Cstegory F-8 Itera Mtsaber: N/A R84 3.000 RIGID SUPPORT ISI-PRI-1138 VT"3 0.000 04/24/94 94U1-750P150 P Y N

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 PLge co. 5P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Cocket No. 50-266 Cormnercial Service Date: 12/21/70 COMPOhENT IDENTIFICATION

ISJ, M

RELIEF MATL A COMPO!A PROGRM 18Q COMPONENT DESCRIPTION ISOMETRIC No. METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXREQ

P18-03 Category F-C ltem Ntaber: N/A SK2 2.000 RIGID SUPPORT ISI-PRI-1140 VT-3 0.000 G4/15/94 94U1-750P151 P

Y N l ( l l I

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page to. 6P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Consnercial Service Date: 12/21/70 l COMPONENT IDENT!FICATION M M REL!EF M COMPDIA PROGRM IND JM COMPONENT DESCRIPil0N ISOMETRIC NO. METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SHT, RESULTS CREDIT M EXAM NOTES EXREC

R09-03 Ceregory F-C Item Nunter: N/A SI-80 2.000 RIGID SUPPORT ISI-PRI-1257 VT-3 0.000 05/09/94 94U1-750P146 P

N N

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page Co. ?P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. $0-266 Conmercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M M REttEF MATL A COMPDIA PROGRM M COMPONENT DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATL B MOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM kOTES ExREQ . R10-03 Citecory F-C Item runber: N/A SI-09 6.000 VARIABLE SPRING ISI-PRI-1127 VT-3 0.000 04/25/94 94U1-750P143 P N N HANGER IS OFFSET. MEETS DESIGN REQUIREMENTS.

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page Eo. 8P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Connercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M M RELIEF MATL A COMPDIA PROGRM M COMPC".ENT DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATL 8 NOtTHICK EXAMDATE SUMMART SHT. RE STATS CRE0li M EXAM WOTES ExREQ . R11-03 CYtegory F-C ltern Number: N/A H-313 10.000 RIGID SUPPORT ISI-PRI-1345 VT-3 0.000 04/25/94 94U1-750P144 P W N

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Prge Co. 9P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Commercial service Date: 12/21/70 COMPC'_'EMT IDENTIFICATION M M RELIEF MATL A COMP ED PROGRM

IND, COMPC"E?T DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SMT. RESULTS CREDIT TyP EXAM NOTES ExREQ - R12-03 C*tegory B-J ltem Ptsber: 89.40 SIS-02-s!-1003-22 5 2.000 ELBOW TO PIPE ISI-PRI-1130 PT S 0.344 04/25/94 94U1-451PO48 P N N

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Prge to. 10 P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Commercial Service Date: 12/21/70 COMPONENT IDENTIFICATION LSl M RELIEF MATL A COMPOIA PROGRM M COMPONENT DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATL B NO1 THICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXREo

R13-03 C*tegory F-C ltem haber: N/A 6H-25 6.000 SPRIEG HANGER ISI-PRI-1231 vi-3 0.000 05/11/94 94U1-750P147 P

N N

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page M. 11 P 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Consnercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M M RELIEF MATL A COMPDIA PROGRM M COMPONENT DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATT B NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXREQ R14-03 Cat wory F-C Item Punber: N/A R-350 8.000 SNUBBER ISI-PRI-1222 VT-3 0.000 04/27/94 94U1-750P145 P N I NO BREATHER CAP ON RESERV0lR. i l l i I

Wisconsin Electric Power Co. 231 Wes Michigan Avenue Milwaukee,WI 53201 Point Beach Nuclear Plant, Unit 1 6610 Nuclear Road Two Rivers, WI 54241 Docket 50 266 CommercialService Date 12/2100 ) Augmented / Successive Examinations (Pages IS - 16S) f i

~. ~.-. .~ c 1 ? f WISCONSIN ELECTRIC POINT BEACH NUCLEAR PLANT, UNIT 1 Interval 03 Period 02 Outage 01 Augmented / Successive Examinations (Outage Sunnary Report - NIS-1) Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Pega Ko. 1S 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Connercial Service Date: 12/21/70 a COMPC'ENT IDENTIFICATION ISI

EXAM, RELIEF MATL A COMPDIA PROGRM M COMPOVENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL 8 NOMTHICK EXA80 ATE

SUMMARY

SMT. RESULTS CREDIT lyP EXAM NOTES EXREQ

B08-03 Category B-G-2 Item Ptsaber: B7.30 SG-A-MWAY-INLET-BLT-01 THRU 16 0.000 MANWAY BOLTING ISI-PRI-1202 VT-1 0.000 04/12/94 94U1-750P133 P

W N - 1 SG-A-MWAY-OUTLET-8LT-01 THRU 16 0.000 MANWAY BOLTING R$1-PRI-1202 VT-1 0.000 04/12/94 94U1-750P132 P N N 1 c.

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Page to. 2S 231 West Michigan Averme 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPC"ENT IDENTIFICATION ISI [XAM ret!EF MATL A COMPDIA PROGRM M COMPONENT DESCRIPTION ISOMETRIC NO. METHOD RF00EST MATL B NOMTHICK EXAMDATE StMMARY SHT. RESULTS CREDIT E EXAM NOTES EXREQ 001-03 C*tegory

IN90-29 Item Ntznber: RPVMEAD RPV-HD-CLAD 0.000 RPV HEAD INTERIOR CLADDlNG I51-PRI-1102 VT-3 0.000 04/15/94 94U1-755P001 P

N N PERFORMED USING WESTINGHOUSE CAMERA. I I i l l l l [ I

Wisconstr Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Page Eo. 3$ 231 West Michigan Avenue 6610 Nuclear Road C3/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Connercial Service Date: 12/21/70 COMPC"ENT IDENTIFICATION ISI EXAM RELIEF MATL A COMPDIA PROGRM JNDD COMPC"ENT DESCRIPTION ISOMETRIC No. METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES ExREO

S01-03 C*tegorY F-C ltem Ntaber: N/A SI-50 4.000 RIGID SUPPORT ISI-PRI-1252 vi-3 0.000 03/09/94 94U1-750P008 P

N N

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Pagi to. 4S 231 West Michigan Avenue 6610 Nuctear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPONENT IDENTIFICATION J_S_[ M RELIEF MATL A COMPO!A PROG 9M JWQ COMPONENT DESCRIPTION ISOMETRIC NO, METHOD REQUEST MATL 8 NONTHlCK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT TYP EXAM NOTES EXREo

$02-03 C*tegory f-C Item NLeberg N/A SI-73 2.000 RIGID SUPPORT ISI-PRI-1258 VT-3 0.000 04/04/94 94U1-750P092 P

N N

Wisconsin Electric Power Company Point Beach kuclear Plant, Unit 1 Page Eo. 5s 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Commercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M EXAM RELIEF MATL A COMPDIA PROGRM IND COMPONENT DESCRIPTION ISOMETAIC NO. METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT T_YP EXAM NOTES EXREQ

$03-03 Crtegory F-C ltem P*urther: N/A SI-80 2.000 RIGID SUPPORT ISI-PRI-1257 VT-3 0.000 04/05/94 94ul-750P090 P

N R LOOSE NUT CN 0-BOLT.

W'e onsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Page Ko. 6S 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Commercist Service Date: 12/21/70 COMPOWENT IDENTIFICATION M M RELIEF MATL A COMPDIA PROCRM M COMPONENT DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT. RESC.TS CREDIT M EXAM NOTES EXREQ

505-03 C7tegory F-C ltern Nmber: N/A H-302 10.000 RIGID SUPPORT ISI-PRt-1344 VT-3 0.000 03/16/94 9401-750PO47 P

N N

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Page to. 75 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 [OMPCCENT IDENTIFICATION ISI EXAM ret!EF MATL A COMPDIA PROGRM M COMPONENT DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATL B NOMTHICK EXAMDATE

SUMMARY

SMT. RESULTS CREDIT T TP, EXAM NOTES EXREQ

S06-03 C+tegory F-C I tem Nt.rnber: N/A H-313 10.000 RIGID SUPPORT ISI-PRI-1345 vi-3 0.000 03/16/94 94U1-750PO45 P

N R UPPER AND LOWER NUT ON SUPPORT ROD IS LOOSE.

Wisconsin Electric Power Company Point Beach Nuclear Plant. Unit 1 Pagi 100. 85 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Conenercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M

EXAM, ret!EF MATL A COMPO!A PROGRM JWQ CLMPONENT DESCRIPTION ISOMETRIC NO.

METHOD REQUEST MATL 8 WOMTHICK EXAMDATE SUMMART SMT. RESULTS CREDIT M EXAM NOTES EXREQ

S07-03 Category F-C Item Nunber: N/A H-314 10.000 RIGID SUPPORT ISI-PRI-1345 VT-3 0.000 03/16/94 94ut-750PO46 P

N N

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Pzge to. 95 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Mitusukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Coninercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M M REllEF MATL A COMPDIA PROGRM M COMPONENT DESCRIPfl0si ISOMETRIC NO. METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXREQ

S08 03 C*tegorY F-C lteen msber: N/A 3H-06 8.000 SP21NG HANGER ISI-PRI-1222 VT-3 0.000 03/30/94 94U1-750P064 P

W R ACTUAL LOAD IS LOWER THAN REQUIRED COLD SETTING.

Wisconsin Electric P wer Cmpany Point Beach Nuclear Plant, Unit 1 Page to. 10 5 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers Wisconsin 54241 Docket No. 50-266 Commercial Service Date: 12/21/70 COMPC~ENT IDENTIFICATION ISI EXAM REllEF MATL A COMPDIA PROGRM jkD COMPCENT DESCRIPTidN ISOMETRIC NO. METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES SO9-03 EXREQ + Catagory F-C Item Nurrber: N/A 5H-01 6.000 SPRING HANGER ISI-PRI-1230 VT-3 0.000 03/10/94 94U1-750P030 P W R NO LOAD FLANGE ON SPRING CAN - PIPE SUPPORT IS 1" 0FF CENTER TO SPRING HANGER.

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Page Iso. 11 S 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Nitwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Cossnercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M E RELIEF MATL A COMPDIA PROGRM M R COMPC"ENT DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATL 8 NOMTHICE EXA2 ATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES E% REQ . 510-03 C*tesory F-C Hem (* uter: N/A 6H-28 6.000 SPRING HANGER ISI-PRI-1231 VT-3 0.000 03/10/94 94u1-750P026 P N N

Wisconsin Electric Power Coppany Point Beach Nuclear Plant, Unit 1 Page No. 12 S 231 West Michigan Avenue 6610 Nuclear Road C8/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Consnercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M E REllEF MATL A COMPDIA PROGRM M R COMPC~ENT DESCRIPTION ISOMETRIC No. METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXREQ

S11-03 C*tegory F-C Item f*tanber: N/A H-37A 10.000 RIGID SUPPORT ISI-PRI-1340 VT-3 0.000 03/16/94 94U1-750P051 P

N I LIGHT CORROSION ON P!PE.

Wisconsin Electric Power Company Point Beach Nuclear Plant, Unit 1 Prge to. 13 S 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Consnercial Service Date: 12/21/70 E RELIEF MATL A COMPDIA PR0r.RM M COMPOWENT IDENTIFICATION M R COMPCENT DESCRIPil0N ISOMETRIC NO. METHOD REQUEST MATL B NOMTHICK EXANATE SUMMART SNT. RESULTS CREDIT M EXAM NOTES EXREO

$12-03 C*tegory F-C ltem tumber: N/A H-38A 14.000 RIGID SUPPORT ISI-PRI-1340 VT-3 0.000 03/22/94 94u1-750P059 P

N N

Wisconsin Electric Power Conpany Point Beach Nuclea: Plant, Unit 1 Prge to. 14 5 231 West Michigan Avenue 6610 Nuclear Road 05/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Connercial Service Date: 12/21/70 CCNPONENT IDENTIFICATION Hj, M RELIEF MATL A COMPDIA PROGRM JNO COMPCTENT DESCRIPTION ISOMETRIC WO. METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXREQ . S13-03 Cetegory F-C hem Nmber: N/A H-48A 10.000 RIGID SUPPORT ISI-PRI-1340 vi-3 0.000 03/16/94 94U1-750P052 P W I GENERAL CORROSION ON PIPE

Wisconsin Electric Power Conpany Point Beach Nuclear Plant, Unit 1 Page Ko. 15 S 231 West Michigan Avenue 6610 Nuclear Road 08/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Comercial Service Date: 12/21/70 COMPONENT IDENTIFICATI0et M OLM RELIEF MATL A COMPDIA PROGRM M COMPOtfENT DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATL 8 NOMTHICK EXAN ATE SUMMART SMT. RESULTS CREDIT M EXAM NOTES EXREQ

514-03 Category f-C ltem ruFber: N/A H-312 10.000 RIGID SUPPORT ISI-PRI-1345 VT-3 0.000 03/16/94 94U1-750PO44 P

N N

Wiscortsin Electric Power Coepany Point Brach ttriecr Plant, R11t 1 Page Co. 16 5 231 West Michigan Avenue 6610 Nuclear Road C'/10/94 Milwaukee, Wisconsin 53201 Two Rivers, Wisconsin 54241 Docket No. 50-266 Cormercial Service Date: 12/21/70 COMPONENT IDENTIFICATION M M RELIEF MATL A COMPDIA PROGRM M COMPrE7T DESCRIPTION ISOMETRIC NO. METHOD REQUEST MATL 8 NOMTHICK EXAMDATE

SUMMARY

SHT. RESULTS CREDIT M EXAM NOTES EXREQ

S15-03 Cwtectory F-C 1 tem O*wber: N/A H-303 10.000 RIGID SUPPORT ISI-PRI-1344 vi-3 0.000 03/16/94 94u1-750PO48 P

N N l I l

Wonsin Bactric Powrt Co. 231 Wed Michigan Annue Milwaukee, WI 53201 Point Beach Nuclear Plant, Unit i 6610 Nuclear Road Two Rivers. WI $4241 Docket 50-266 CommercialService Date 12/2100 2.4 Pressure Tests 2.4.1 ASME Section XI Pressure Tests Following are pressure tests that have been conducted as part of the pressure test program at PBNP since the last refueling outage.

Wisconsin Electric Powcf Co. 231 West Michigan Avenue Milwaukee, WI $3201 Point Beach Nuclear Plant, Unit ! 6610 Nuclear Road Two Rivers, W1 54241 Docket 50-266 Commercial Servies Date 12/2100 Pressure Tests

Wisconsin Eixtric Powir Co. 231 West Michigan Avenue Milwaukee, WI $3201 Point Beach Nuclear Plant, Unit i 6610 Nuclear Road Two Rivers, W1 54241 Docket 50 266 ConunercialService Date 12/21n0 TEST DESCRIFFION: 40 Month Inservice Pressure Test of Refueling Water Storage Tank and Associated Piping (Unit 1). SYSTEM: Safety Injection (Residual Heat Removal) TEST DOCUMENTS: IT-1070 COMPLETION DATE: March 11,1994 TEST DESCRIFFION: 40 Month Inservice Pressure Test of Component Cooling Water Piping and Components Outside Containment (Unit 1). SYSTEM: Component Cooling Water TEST DOCUMENTS: IT-1020, Part 2 COMPLETION DATE: March 8,1994 TEST DESCRIPTION: 40 Month Inservice Pressure Test of the Spray Additive Tank and Associated Piping (Unit 1). SYSTEM: Containment Spray TEST DOCUMENTS: IT-1110, Part 2 COMPLETION DATE: March 9,1994 TEST DESCRIFFION: System Leakage Test of Class 1 Components Following Refueling Outage (Unit 1). SYSTEM: Reactor Coolant TEST DOCUMENTS: IT-230 COMPLETION DATE: April 29,1994 Page 1 of 1

Wisconsin E12ctric Powtr Co. 231 West Michigan Avenue Milwaukee.WI $3201 Point Beach Nuclear Plaat. Unit i 6610 Nuclear Road Two Rivers. WI 54241 Docket 50-266 CommercialService Date 12/2100 2.6 Snubber Surveillance Tests 2.6.1 ASME Section XI Snubber Surveillance Tests Following are snubber inservice tests that have been conducted for snubbers less than 50 kips as part of the snubber surveillance test program at PBNP since the last refueling outage. r i e i I l

Wisconsin Electric Powir Co. 231 West Michigan Avsnue Milwaukee, WI 53201 Point Beach Nuclear Plant, Unit 1 6610 Nuclear Road Two hers, WI $4241 Docket 50-266 CommercialService Date 12/21/70 Snubber Surveillance Tests

l Wisconsin Electric Power Co. ) 231 West Michigan Avenue '1 I Milwaukee,WI 53201 Point Beach Nuclear Plant, Unit 1 6610 Nuclear Road i Two Rivers, WI 54241 Doeket 50-266 j CommercialService Date 12/21n0 TEST DESCRIPTION: Snubber Inservice Test for Snubbers Less than 50 kips (Unit 1) SNUBBER HS-12 TEST DOCUMENTS: MWR 940509 COMPLETION DATE: April 4,1994 SNUBBER HS-601A-80 TEST DOCUMENTS: MWR 940508 COMPLETION DATE: March 31,1994 Page 1 of 1 4 ~ - -

Wisconsin Electric Powar Co. 231 Wet Michig n Avenue Milwaukee, WI 53201 Point Beach Nuclear Plant. Unit ! 6610 Nuclear Road Two Rivers. WI $4241 Docket 50-266 Comrnercial Service Date 12/21n0 3.0 ABSTRACT OF CONDITIONS NOTED AND CORRECTIVE MEASURES TAKEN 3.1 Comoonent/ Weld Nondestructive examinations were performed by QTS, EBASCO, and PWA personnel. The nondestructive examinations utilized VT, PT, MT, RT, and UT techniques. All the examinations were performed in accordance with written procedures that conform to the applicable sections of the ASME Boiler and Pressure Vessel Code. The folicwing is a summary of the recordable indications found during the examinations and evaluated by PBNP personnel. 94Ul-7P001, Class 2 Spring Hanger, lH-01A Datasheet 94U1-750P014 Inspection revealed that the load flange was 3" off center to the base plate and the cold load setting was higher than the required range. The off center load flange meets design requirements. The IEB 79-14 walkdowns have identified this support for removal. The operability of the system is not affected. No corrective actions are required. 94UI-7P002, Number not used. 94Ul-7P003, Number not used. 94UI-7P004, Class 2 piping support, SI-87 Datasheet 94Ul-750P018 Inspection revealed lack of complete thread engagement on a nut that attaches the support beam plate to the wall. The nut is tight and the condition has been prevalent since construction. This condition has been previously analyzed in CR 91-094 and was found to be acceptable. No corrective actions required. 94U1-7P005, Class 2 piping weld, SIS-04-SI-1005-04 Datasheet 94U1-451P002 A 0.062" crater crack indication on weld SIS-04-SI-1005-04 detected by PT. The indication appears to have resulted from the welding process and meets acceptance criteria of IWC-3514 (IWB-3514). No corrective actions required. 94U1-7P006, Number not used. i

Wisconsin Electric Power Co. 231 Wea Michig n Av:oue Milwaukee, WI $3201 Point Beach Nuclear Plant. Unit i 6610 Nuclear Road Two Rivers, WI 54241 Docket 50-266 CommercialService Date 12/2l00 94U1-7P007, Class 2 Spring Hanger, 6H-13 Datasheet 94U1-750P025 Inspection revealed the nut on the bolt being used as a clevis pin was two threads below full engagement. This pin provides support in the shear direction only and design drawings call for a nut / bolt combination or a pin with cotter pins to prevent lateral movement. This condition meets the design requirements and was evaluated as acceptable with no corrective actions required. 94U1-7P008, Class 2 Spring Hanger,3H-02 Datasheet 94U1-750P055 Inspection revealed that the required cold load setting could not be obtained with the installed spring can range and the cold load setting was higher than the required range. It was found that a size 7 spring can was installed whereas the design drawings called for a size 5. A Condition Report (CR 94-167) was initiated to resolve the conflict. CR 94-167 determined that the operability of the spring hanger and the system was not affected. The drawings will be revised to reflect the "as built" condition. 94Ul-7P009, Class 2 Spring Hanger,4H-04 Datasheet 94U1-750P029 Inspection revealed the load flange was 2" off-center from the support plate. This meets the design requirements of the spring hanger and no actions are required. 94U1-7P010, Class 2 Spring Hanger,5H-01 Datasheet 94U1-750P030 Inspection revealed the load flange on the spring can was missing and the support was 1" off-center of the base plate. This meets the design requirements of the spring hanger and no actions are required. 94UI-7P0ll, Class 2 Pipe Support,6H-02 Datasheet 94U1-750P032 The slide plate was reported 2" off-center from the floor slide plate. This indication does not violate the acceptance criteria of ASME Section XI, IWF-3410 and was found acceptable during analysis performed during IEB 79-14 walkdowns (Stress Cal. No. PD-GGS-001 Rev. 0). No corrective action required.

Wisconsin Elzctric PowIt Co. 231 West Michigan Avenue Milwaukee, WI 53201 Point Beach Nuclear Plant. Unit I i 6610 Nuclear Road Two Rivers, WI 54241 Docket 50 266 CommercialService Date 12/21no 94Ul-7P012, Class 2 Pipe Support, R-350 Datasheet 94U1-750P035 i Visual inspection revealed that one nut on the piston rod of snubber R-350 was loose. The remaining nuts on the snubber were tight and the operability of the snubber was not compromised. Investigation revealed that the most likely cause of the loose nut was from insufficient tightening during snubber surveillance testing conducted during 1993 (U1R20). MWR 941097 was issued to tighten the nut, j 94Ul-7P013, Class 2 Spring Hanger,6H-33 Datasheet 94U1-750P040 Inspection revealed that the load on the spring can (1300#) was lower than the required cold load setting. The improper load violated the acceptance criteria of IWF-3410 (a) (5) but has existed since construction as evidenced by the previous inspection reports. Since the load is within the operating range of the spring can, the operability of the spring hanger and the pipe system is not affected. The spring can will be readjusted under MWR 9402427. 94U1-7P014, Class 2 Piping Weld, AC-10-RHR-1001-08 Datasheet 94U1-451P005 Linear indication at toe of weld AC-10-RHR-1001-08 detected by PT appears to be a hot crack in the weld area. The indication is 0.12" long and the ASME Section XI acceptance criteria is greater than 0.2". The acceptance criteria has been met, therefore no corrective action required. 94Ul-7P015, Class 3 Pipe Support, H-313 Datasheet 94U1-750P045 Inspection revealed the upper and lower locknuts on the tension bar to be loose. This condition was previously identified and was not repaired. This support is exempt from inspection requirements in the ISI program. RRM 94-0037 was initiated to tighten the locknuts. 94Ul-7P016, Class 3 Pipe Support, H-95 Datasheet 94U1-750P050 Light general corrosion was reported on the riser clamp of the floor support. The i corrosion is a result of humidity and general moisture in the air. The corrosion does not compromise the structural integrity of the support or the pipe and is acceptable. There is no corrosive environment present to cause unusually high corrosion rates. No corrective actions required. i }

Wisconsia Electric Power Co. 231 Wats Michigan Avenue Milwaukee.WI $3201 Point Beach Nuclear Plant. Unit 1 6610 Nuclear Road Two Rivers, WI $4241 Docket 50-266 Comrnercial Service Date 12/21/70 94U1-7P017, Class 2 Pipe Support, H-37A Datasheet 94U1-750P051 Inspection revealed light general corrosion on the pipe near the clevis. The corrosion is a result of humidity and general moisture in the air. The corrosion does not compromise the structural integrity of the support or the pressure retaining function of the pipe and is acceptable. There is no corrosive environment present to cause unusually high corrosion rates. No corrective actions required. 94U1-7P018, Class 3 Pipe Support, H-48A Datasheet 94U1-750P052 Inspection revealed light general corrosion on the pipe near the clevis. The corrosion is a result of humidity and general moisture in the air. The corrosion does not compromise the structural integrity of the support or the pressure retaining function of the pipe and is acceptable. There is no corrosive environment present to cause unusually high corrosion rates. No corrective actions required. 94U1-7P019, Class 2 Pipe Support,3H-01 Datasheet 94U1-750P054 Inspection revealed the grout pad under the base plate to be cracked and disintegrating. Condition Report 94-101 was initiated to investigate the root cause and corrective actions. CR 94-101 determined that the operability of the system is not affected. Additional examinations in accordance with IWF-3410 were performed with no additional discrepancies. This support will be subject to successive examinations. l 94Ul-7P020, Class 2 Pipe Support,3H-03 Datasheet 94U1-750P057 Inspection revealed that the base plate was suspended 3/4" off of the grout pad. This support was previously analyzed by calculation No. 85 of the IEB 79-14 walkdown. The condition identified was acceptable with no actions required. 94U1-7P021, Class 2 Spring Hanger,2H-02 Datasheet 94U1-750P033 Inspection revealed that one of the two spring cans was slightly below the required load range. The improper load range violates the acceptance criteria of IWF-3410 (a) (5) but has existed since construction as evidenced by previous inspection reports. The spring can will be readjusted under an MWR 9402424. The operability of the spring hanger and the system is not affected.

Wisconsin Electric Power Co. 231 West Michigm Avenue Milwaukee,WI 53201 Point Beach Nuclear Plant. Unit I 6610 Nuclear Road i Two Rivers, WI 54241 Docket 50-266 CommercialService Date 12/21n0 94U1-7P022, Class 2 Spring Hanger, 6H-25 Datasheet 94U1-750P028 Inspection revealed that the actualload was lower than the required load range. The improper load range violates the acceptance criteria of IWF-3410 (a) (5) but has existed since construction as evidenced by previous inspection reports. The spring can will be readjusted under an MWR 9402426. The operability of the spring can and the system is not affected. 94Ul-7P023, Class 2 Spring Hanger,1H-03 Datasheet 94U1-750P056 Inspection revealed that the actual load was higher than the required load range. The improper load range violates the acceptance criteria of IWF-3410 (a) (5) but has existed since construction as evidenced by previous inspection reports. The spring can will be readjusted under an MWR 9402425. The operability of the spring can and the system is not affected. 94UI-7P024, Class 2 Spring Hanger,3H-06 Datasheet 94U1-750P064 Inspection revealed that the actual load was lower than the required load range. The improper load range violates the acceptance criteria of IWF-3410 (a) (5) but has existed since construction as evidenced by previous inspection reports. The spring can will be readjusted under an MWR 9412428. The operability of the spring can and the system is not affected. 94U1-7P025, Class 3 Pipe Support, S-524 Datasheet 94U1-750P081 Inspection revealed general corrosion on the pipe support and pipe saddle. The corrosion is a result of humidity and general moisture in the air. The corrosion does not compromise the structural integrity of the support or the pipe and is acceptable. There is no corrosive environment present to cause unusually high corrosion rates. No corrective actions required. 94Ul-7P026, Class 2 Pipe Support, H-203 Datasheet 94U1-750P068 General corrosion was reported on the support with a higher amount on the base plate. The corrosion is a result of humidity and general moisture in the air. The corrosion does not compromise the structural integrity of the support or the pipe and is acceptable. There is no corrosive environment present to cause unusually high corrosion rates. No corrective actions required.

Wisconsin Electric Power Co. 231 Wat Michigan Annue Milwaukee,WI 53201 Point Beach Nuclear Plant, Unit i 6610 Nuclear Road Twc Rivers. WI 54241 Docket 50-266 CommercialService Date 12/21n0 94Ul-7P027, Class 2 Pipe Support, H-205 Datasheet 94U1-750P069 General corrosion was reported on the support with a higher amount on the base plate. The corrosion is a result of humidity and general moisture in the air. The corrosion does not compromise the structural integrity of the support or the pipe and is acceptable. There is no corrosive environment to cause unusually high corrosion rates. No corrective actions required. 94Ul-7P028, Class 1 Piping Weld, SIS-02-SI-1003-22 Datasheet 94U1-451P016 Dye penetrant inspection revealed an indication that when sized exceeded the ASME Section XI acceptance criteria of IWB-3514-2. The indication was as a result of a surface irregularity in the welded area and was not a flaw like indication. The surface irregularity was mechanically removed (RRM 94-0030). 94Ul-7P029, Class 2 Pipe Support, SI-80 Datasheet 94U1-750P090 Inspection revealed a loose nut on the U-bolt support. The nut was tightened and the support reinspected. An additional examination, in accordance with IWF-2430, was performed. This support will be subject to successive examination in accordance with IWF-2420. 94Ul-7P030 - Number not used. 94Ul-7P031 - Number not used. 94Ul-7P032, Class 1 Pipe Support,42-20-PSSA Datasheet 94Ul-750P112 Inspection revealed that the pipe support was not attached to the building structure in any manner. Further investigation revealed that the support is actually a guide / restraint and does not support any load. This item will be removed from the ISI database. 94U1-7P033 - Number not used. l

Wisconsin Electric Powir Co. 231 Wc 1 Michigan Avsnue Milwaukee.WI 53201 Point Beach Nuclear Plant. Unit i 6610 Nuclear Road Two Rivers. WI 54241 Docket 50 266 CommercialService Date 12/21/70 94U1-7P034, Class 1 Spring Hanger, RC-04 Datasheet 94U1-750P113 Inspection revealed a crack in the concrete building structure by the support. Further evaluation revealed that the concrete was not part of the support. The support meets the acceptance criteria of IWF-3410. The cracked concrete has been previously evaluated by WE civil / structural engineering to not have any operability concerns or affect on the loading of RC-04. No corrective actions required. 94Ul-7P035, Class 1 Hydraulic Snubber, HS-13 Datasheet 94U1-750P114 Inspection revealed three nuts on the support plate did not have complete thread engagement. The nuts did not show any evidence of loosening and remain tight. Evaluation of this condition indicates that there is adequate thread engagement to provide the appropriate support. No corrective actions are required. 94Ul-7P036, Class 1 Piping Weld, RC-10-AC-1001-06 Datasheet 94U1-451P038 Dye penetrant inspection revealed two rounded indications that appear to be porosity in the welded area. These indications meet the ASME Section XI acceptance criteria. No corrective actions required. 94Ul-7P037, Class 1 Spring Hanger, SI-09 Datasheet 94U1-750P126 Inspection revealed that the support was offset and that two non-load bearing nuts were loose. The offset support is a condition that existed since construction. The nuts were loose to accommodate the offset. MWR 9401939 was initiated to correct this condition. The operability of the support and the system is not affected. 94U1-7P038, Class 1 Piping Weld, RC-04-PSF-1001-04 Datasheet 94U1-451P040 Dye penetrant inspection revealed two indications in the welded area that were a result of the welding process. The indications meet the ASME Section XI acceptance i criteria. No corrective actions required.

Wisconsin Electric Powcr Co. 231 Woo Michigan AUCnue Milwaukee, WI $3201 Point Beach Nuclear Plant. Unit ! 6610 Nuclear Road Two Rivers. WI 54241 Docket 50-266 ComrnercialService Date 12/21n0 94Ul-7P039, Class 1 Piping Weld, RC-04-PR-1001-09 Datasheet 94U1-451PO41 j Dye penetrant inspection revealed two indications that were a result of the welding process. The indications meet the ASME Section XI acceptance criteria. No corrective actions required. j 94Ul-7P040 - Number not used. 94Ul-7PO41, Class 2 Integral Welded Attachment, H-19-IWA Datasheet 94U1-350P001 Magnetic particle examination revealed a 3/4" indication caused by entrapment of the magnetic particles in the toe of the weld. Supplemental inspection by dye penetrant and visual weld examination determined the welded attachment to be acceptable. No corrective actions required. 94Ul-7P042, Class 2 Spring Hanger, CS-02 Datasheet 94U1-750P016 Inspection revealed a missing nameplate. Subsequent evaluation determined that the load on the spring was to be in the required range. No corrective actions required. 94Ul-7PO43, Class 2 Spring Hanger, H-19 Datasheet 94UI-750P060 Inspection revealed a missing nameplate. Subsequent evaluation determined that the load on the spring was to be in the required range. No corrective actions required. 94U1-7P044, Class 2 Spring Hanger,3H-02A Datasheet 94U1-750P087 Inspection revealed a missing nameplate. Subsequent evaluation revealed that the i wrong size spring can was installed as compared to construction drawings. Condition Report 94-167 was initiated to evaluate this discrepancy. The CR determined that operability of the system was not affected. The construction drawings will be revised to reflect the "as built" condition. 94U1-7PO45, Class 2 Hydraulic Snubber, R-350 Datasheet 94U1-750P145 Inspection revealed a missing " breather cap" on the reservoir. This condition is not inservice related and does not affect the operability of the snubber or system. No corrective actions required.

l l Wisconsin E11ctric Powir Co. 'l 231 Wssa Michigin Avenue 1 Milwaukee,WI 53201 Point Beach Nuclear Plant, Unit i 6610 Nuclear Rood l Two Rivers, WI 54241 Docket 50-266 i CommercialService Date 12/2100 94U1-7P046 - Number not used. 94U1-7PO47, Class 2 Spring Hanger,2H-02A Datasheet 94U1-750P037 Inspection revealed a bent rod on the spring' hanger. This condition existed since construction and was identified and evaluated druing previous inspections.as being acceptable. No corrective actions required. 94Ul-7P048, Class 2 Pipe Support,2H-07 Datasheet 94U1-750P038 Inspection revealed that the fillet welds attaching the support to the building structure 4 were undersized. The drawing called for 1/4" welds where as the welds found were 3/16" and 1/8". This condition was identified during the NRC IEB 79-14 walkdowns and was evaluated as acceptable per Bechtel Calculation PD-GH-P104-042. No corrective actions required. 3.2 Ptessure Tests No reportable indications were observed. 3.3 Snubber Surveillance Tests i Tests were acceptable, no corrective actions required. l

l FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the AS5C Code Rules a

1. Owner Wisconsin Electric Power comoany. 231 W. Michigan Ave.. Milwaukee WI 53201 (Name and Addresa of Owner)
2. Plant Point Beach Nuclear Plant. 6610 Nuclear Road. Two Rivers. WI 54241 i

(Name and Address of Plant)

3. Plant Unit 1
4. Owner Certificate of Authorization (if required) Docket 50-266
5. Commercial Service Date 12/21/70
6. National Board Number for Unit N/A
7. Components Inspected Component or Manufacturer or Manufacturer State or National Appurtenance Installer or Installer Province No.

Board No. Serial No. Reactor Pressure Vessel Babcock & Wilcox R-1 UO10615 NB 0138 Pressurizer Westinghouse 16A6256-1 UO10618 NB 0685 A Steam Generator Westinghouse 16A-6339-1 U010616 16A-60791 Seal Water HX Atlas 699 NB 0563 i Class 1 Piping System Westinghouse Class 2 Piping System Bechtel s Class 2 BOP Piping System Westinghouse i 2 ) ? I i I i i NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 % in. x l 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. 1 i I (12/86) This form (E00029) may be obtained from the Order Dept.. ASME. 22 Law Drive, Box 2300. Fairfield. NJ 07007-2300. 1 ( l i i

Sheet _2_, of1 FORM NIS-1 CONTINUED 8. Examination Dates 4/1/94 to 4/29/94

9. Inspection Interval from 5/6/93 to 5/12/94
10. Applicable Editions of Section XI 1986 Addenda None
11. Abstract of Examinations. Include a list of examinations and a statement concerning status of work required for current interval.

Refer to attached Inservice Inspection Final Report, Section 2.0.

12. Abstract of Conditions Noted.

Refer to attached Inservice Inspection Final Report, Section 3.0.

13. Abstract of Corrective Measures Recommended and Taken.

Refer to attached Inservice Inspection Final Report, Section 3.0. We certify that the statements made in this report are correct and the examina: ions and corrective measures taken conform to the rules of the ASME Code, Section XI. Certificate of Authorization No. (if applicable) NRC Docket 50-266 Expiration Date N/A W -,f /o.rA' Date 19 Signed Mc. Electric Power Co. By A44 m, CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBil. Co. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI, By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions l$ 73/ r W/ ~7 E' s

    • #4 A

~ [ laspector'[ Signature ' National Board, State, Province, and Endorsements dyasb M 19 M Date

Wisconsii Electric Powir Co. 231 West Michigan Avenue Milwaukee, WI 53201 Point Beach Nuclear Plant, Unit i 6610 Nuclear Road Two Rivers, WI 54241 Docket 50-266 CommercialService Date 12/2100 UNIT 1 REFUELING 21 REPAIR /kEPLACEMENT

SUMMARY

REPORT FOR FORM NIS-2 bf[ oate: f-y 94 written by: c/4tG PROTttFR6 Reviewed by: b ff M Q ate: P '/ - 9'/ Approved by: N 779 Date: [ [ W

Wiscomin Electric Power Co. 231 West Michigan Avenue Milwaukee, WI 53201 ) Point Beach Nuclear Nnt, Unit 1 6610 Nuclear Road Two Rivers, WI 54241 Doctot 50-266 CommercialService Date 12/2100 Table of Contents

1.0 INTRODUCTION

2.0 ABSTRACT OF REP' AIR / REPLACEMENT 1 l

Wisconsin Electric Powir Co. 231 West Michigan Avenue Milwaukee,WI 53201 Point Beach Nuclear Plant, Unit ! 6610 Nuclear Road Two Rivers, WI 54241 Docket 50-266 CornmercialService Date 12/2100 Acronvms j i ASME American Society of Mechanical Engineers CR Condition Report MR Modification Request MWR Maintenance Work Request PBNP Point Beach Nuclear Plant RRM Repair, Replacement, Modification WE Wisconsin Electric Power Company i

Wisconsin Electric Pow:r Co. 231 West Michigan Avenue Milwaukee,W1 $3201 Point Beach Nuclear Plant. Unit 1 6610 Nuclear Road Two Rivers, WI 54241 Docket 50-266 CommersialSedce Date 12/21770 ) UNIT 1 REFUELING 21 REPAIR / REPLACEMENT

SUMMARY

1.0 INTRODUCTION

From May 6,1993 to May 12,1994 repairs and replacements were performed on item:: at PBNP Unit 1. These repairs and replacements were completed in the first examination outage of the second period of the third 10-year interval at PBNP Unit 1. 2.0 ABSTRACT OF REPAIRS / REPLACEMENTS f 2.1 Repairs / replacements performed on ASME Class 1 and 2 items are documented on the attached NIS-2 forms. Repairs / replacements on ASME Class 3 items are documented on NIS-2 forms and maintained on file at PBNP. They are not included i in this report in accordance with ASME Section XI, IWA-6210(c). 2.2 The following is an abstract of the repairs / replacements performed at PBNP Unit 1 during first examination outage of the second period of the third 10-year interval. l 2.2.1 Atmospheric steam dump valve (MS-02016) had the trim cage lock assembly removed. A small crack was buffed out where the cage lock assembly was welded to the valve body. A new trim assembly was welded back in place. This work is documented in MWRs 932110 and 936512 and RRMs 93-0032 and 93-0086. 2.2.2 The bolting on the flange connection of flow transmitter FIT-930 was replaced because of corrosion from boric acid leaking from the fiange. This replacement is documented in MWR 932936 and RRM 93-0039. 2.2.3 Five Class 2 supports were modified in accordance with the requirements of the NRC IEB 79-14 reconciliation program. The modifications included shiming the lateral clearances to ensure the supports meet their existing design requirements. This work is documented in RRM 93-0075 and MWRs 935382,935383,935385,935389, and 935391. 2.2.4 The disk assemblies in valves SI-854A and SI-854B were replaced as part - of the check valve upgrade per MR 90-260. This work is documented in MWRs 936352 and 936355 and RRM 93-0078. 2.2.5 A linear indication was identified in the SI piping system. The indication was caused by work on an adjacent support. This was buffed out. This work is documented in MWR 936530 and RRM 93-0085.

Wisconsin Electric Power Co. 231 Wes Michigan Avenue Milwaukee, WI 33201 Point Beach Nue: car Plant. Unit i M10 Nuclear Rosd Two Rivers. WI 54241 Docket 50-2M CommercialService Date 12/2100 2.2.6 The air operator on CV-110C was replaced with a manual operator temporarily. The air operator was refurbished and reinstalled. This replacement is documented in MWRs 935950,940285, and 940232 and RRM 94-003. 2.2.7 The supporting steel for a spring support EB-1-MS-H5 on the main steam piping was relocated. This replacement is documented in MWR 940364 and RRM 94-0004. 2.2.8 Pipe support H-10 was modified in accordance with MR 93-047 to upgrade for the NRC IEB 79-14 reconciliation program. This work is documented in MWR 940365 and RRM 94-0005. 2.2.9 The pipe clamp on support SI-04 was replaced with a heavy duty clamp. This replacement is documented in MWR 940369 and RRM 94-0006. 2.2.10 Shims and anchorage were installed on supports SI-10 and R-194 to upgrade the support for the NRC IEB 79-14 reconciliation program. This replacement is documented in MWRs 940371 and 940373 and RRM 94-0007. 2.2.11 Test connections on the main feed system were installed. These test connections facilitated the testing of main feed check valves CS-466AA/BB j and CS-476AA/BB. This replacement is documented in MWRs 940293, 940294,940461, and 940463 and RRM 94-0008. i 2.2.12 The support on valves SI-839A, B, C, and D was reinforced by adding weld and plate material. This work is part of MR 93-047, NRC IEB 79-14 reconciliation program. This work is documented. in MWR 940370 and RRM 94-0010. 4 2.2.13 Shims were added to support R102 as part of the NRC IEB 79-14 reconciliation program. This work is documented in MWR 940372 and RRM 94-0011. 2.2.14 RCP seal water and excess letdown piping supports PS CH 151R-2-H222, PS CH 151R-2-SKA-1 and PS CH 151R-SKA2 were modified in accordance with the requirements of the NRC IEB 79-14 reconciliation program. This work is documented in MWRs 941065,940367, and 940368 and RRM 94-0012. 2.2.15 The U-bolt was removed from piping support SK-2 in accordance with the requirements of the NRC IEB 79-14 reconciliation program. This work is documented in MWR 940801 and RRM 94-0015.

Wisconsin Electric Power Co. 231 West Michigan A.enue Milwaukee, %1 53201 Poird Beach Nuclear riant, Unit 1 6610 Nuclear Road Two Rivers, WI 54241 DocLet 50-266 CominercialService Date 12/21/70 2.2.16 Shims were added to whip restraint R84 to make it a pipe support in accordance with the requirements of the NRC IEB 79-14 reconciliation program. This work is documented in MWR 940536 and RRM 94-0016. 2.2.17 During maintenance of CC-00777B, one body-to-bonnet nut required replacement. This work is documented in MWR 935020 and RRM 94-0019. 2.2.18 The volume control tank relief valve (CV-257) was designed to relieve a water environment. This valve was replaced with a valve designed to relieve an H and N atmosphere. This replacement is documented in 2 2 MWR 915279 and RRM 94-0020. 2.2.19 MS-2006 was sent to the CRANE-ALOYCO facility for repairs as part of the relief valve program. This repair is documented in Purchase Order 247390 and RRM 94-0021. 2.2.20 MS-2008 was sent to the CRANE-ALOYCO facility for repairs as part of the relief valve program. This repair is documented in Purchase Order 247390 and RRM 94-0022. 2.2.21 The bonnet and diaphragm assembly on CV-216 was replaced. This replacement is documented in MWR 913462 and RRM 94-0024. 2.2.22 The bonnet and diaphragm assembly on CV-212 was replaced. This replacement is documented in MWR 913461 and RRM 94-0025. 2.2.23 The base plate was shimmed and the grout pad was repaired on support MSH-01 in accordance with the NRC IEB 79-14 reconciliation program. This replacement is documented in MWR 940363 and RRM 94-0026. 2.2.24 The main feedwater check valves CS-466AA and CS-476AA were replaced because of leak by. This replacement is documented in MWRs 9401539 and 9401540 and in RRM 94-0027. 2.2.25 Analysis of the oil on residual heat removal pump P-010B showed a high heat problem in the bearings. The rotating assembly of the pump was replaced. This work is documented in MWR 9401614 and RRM 94-0029.

Wisconsin Ekstric Power Co. 231 West Michigan Avenue Milwaukee, W1 53201 Point Beach Nuclear Plant, Unit 1 6610 Nuclear Road j Two Rivers, WI $4241 Docket 50 266 CommercialService Date 12/21/70 2.2.26 ISI on weld SIS-02-SI-1003-22 revealed a rounded indication that did not meet the ASME Section XI inservice acceptance criteria. The indication appears as porosity from the welding process. The rounded indication was buffed out and a surface examination was performed revealing no indications. This work is documented in MWR 9401938 and RRM 94-0030. 2.2.27 During gasket replacement on the pressurizer manway, one of the manway bolts became galled (bolt No. 7). This bolt was replaced with one from stock. This replacement is documented in MWR 9401615 and RRM 94-0031. 2.2.28 The supports on valves SI-844A and SI-844B were modified to provide seismic restraint. This replacement is documented in MWRs 9401518 and 9401519 and RRM 94-0032. 2.2.29 Boric acid on the studs of RC-427 was noted during a system walkdown. The stud nuts were removed and replaced because of general corrosion from the boric acid. This replacement is documented in MWR 9401366 and RRM 94-0033. 2.2.30 Boric acid on the studs of the flan;;e connection for FIC-179 was noted during a system walkdown. The stud nuts were removed and replaced because of general corrosion from the boric acid. This replacement is documented in MWR 9401371 and RRM 94-0034. 2.2.31 Two support nuts on the tension bar were found loosened on support H-313. The nuts were tightened. This work is documented in MWR 9401960 and RRM 94-0037. 2.2.32 The tie. rods on snubber HS-12 were replaced. This replacement is documented in MWR 940509 and RRM 94-0038.

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Sation XI

1. Owner Wisconsin Electric Power Comnany Date May 26.1993 Name 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet I

of 2 Addrem

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWRs 932110. 936512 Address Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date _S/A Address

4. Identification of System Main Steam Bechtel Spec 6118-MR-185
5. (a) Applicable Construction Code ANSI B31.11961 Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Starrged Component Manufactunr Serial No.

No. Identification Built Replacement (Yes or No) MS42016 N/A N/A N/A N/A N/A Repaired No l

7. Description of Work Remove crack m bods of valve in cace lock area and install new trim.
8. Tests Conducted: Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure O Other & Pressure osi Test Temp.

'F Preservice test in accordance with IT-90 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. -~ (12/82) 'Ihis Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

i l Sheet 1 of1 Form NIS-2 Continued

9. Remarks RRM 93-0032. RRM 93-0086. CR 94-290 Applicable Manufacturer's D.ta Reports to bc.uached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reoair conforms to the rules of the ASME Code, Section XI.

rep.it oc replacement Type Code Symbol Stamp N/A Certificate of Authorizati n No. Docket 50-266 Expiration Date N/A / g Signed 4 /r Dr l'= nim,n DateOn / h , 19 Owner oc Owner's De.ignee, Tide d CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. Cr have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ~ ' /' 7 / / Commissions l075lr WI7V o [ i.poes sig.ture n.co i so.a. suu, we,.a saor.cou Date 6(4 I 19 f1 ~-,

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI ' 1. Owner Wisconsin Electric Power Comoany Date April 27.1994 Name 231 W. Michiran Ave.. Milwaukee. WI 53201 Sheet 1 of 2 Addam

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 932936 Addasa Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Addreae

4. Identification of System Safety Iniection 2-SI-301N-3
5. (a) Applicable Construction Code ANSI B31.1 1962. Edition. N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda 4
6. Identification of Components Repaired or Replaced and Replacement Components
Repaind, ASME National
Replaced, Code l

Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Replacement (Yes or No) Ftr-930 N/A N/A N/A N/A N/A Replacement No 4

7. Description of Work Replace studs on FIT-930.
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure (ID Other O Pressure osi Test Temp.
  • F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet 1 of1 Form NIS-2 Continued

9. Remarks RRM 93-0039 Applicable Manufacturer's Data Reports to be anached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reolacement conforms to the rules of the ASME Code, Section XI.

repair er replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed /W A8 -T5I G.it,.J.e Date

  • b 1' 19 9F
  1. Owner or Owner's Designee, Title j

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wiwonsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 , and state that to the best of my knowledge and belief, the Owner has performed exammations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection. Commissions /d 7.7 /, M'7f, E < # [ IIupector's Signature National Board, State, Province, and Endorsements Date V N 19 9

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner _ Wisconsin Electric Power Comnany Date January 14. 1994 Nanu 231 W. Michiran Ave.. Milwaukee. WI 53201 Sheet I

of 2 Addren

2. Plant Point Beach Nuclear Plant Unit 1 Nams 6610 Nuclear Road. Two Rivers. WI 54241 MWRs 935382. 935383. 935385.

Addreu 935389.935391 Repair Organization P.O. No., Job No., etc.

3. Work Preformed By Phillins Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A 2860 Glenmore Road. Green bay. WI 54311 Expiration Date N/A Addrea
4. Identification of System Safety InieClion
5. (a) Applicable Construction Code ANSI B31.1 1962 Edition, None Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) SI-150lR-24843 N/A N/A N/A N/A N/A Replacement No SI-150lR-24844 N/A N/A N/A N/A N/A Replacement No SI-150lR-3-3844 N/A N/A N/A N/A N/A Replacement No SI-150lR 34845 N/A N/A N/A N/A N/A Replacement No SI-150lR-34846 N/A N/A N/A N/A N/A Replacenwnt No

7. Description of Work Shim suonorts to unerade to existine design criteria.
8. Tests Conducted: Hydrostatic 0 Pneumatic O Nominal Operating Pressure O Other 3 Pressure osi Test Temp.

'F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet _2 of _2_ Form NIS-2 Continued

9. Remarks RRM 93-0075 Applicable Manufacturer's Data Reports to be attachea CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reolacement conforms to the rules of the ASME Code, Section XI.

repair or rept.coment Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed A4 A8 JJI GeoADiN4reA Date m f- [ , 19 iY bner or Owner's Designee, Titte / 1 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hanford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed exammations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the exammations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his ernployer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ~" Commissions /0 7.T/, W! 7 8', IA/$ ~ / idgecioe. si,miur. s.uomi s ra, sm., eree..na sna einera. Date I+m_ E 19f 9

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comnany Date Aoril 17. 1994 Name 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Address i

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWRs 936352. 936355 Address Repair Orgaization P.O. No., Job No., etc.
3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Naaw Authorizatica No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address

4. Identification of System Safety Iniection Westinghouse Spec. G-676241 Rev.1
5. (a) Applicable Construction Code USAS B16.51963._ Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Ma wracturer Serial No.

No. Identification Bu'dt Replacement (Yes or No) $1-854A Crane Aloyco N/A N/A N/A N/A Replacemerd No SI-854B Crane Aloyco N/A N/A N/A N/A Replacement No

7. Description of Work ]1eolace disk assembly on SI-854A and SI-854B.

1

8. Tests Conducted: Ilydrostatic 0 Pneumatic O Nominal Operating Pressure E j

Other E Pressure esi Test Temp. 'F Inservice Test per IT-530 (seat leakage) and IT-03 (full-stroke test) NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. i x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Fonn (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017 l

Sheet _2_ of _2_. Form NIS-2 Continued

9. Remarks RRM 93-0078 Applicable Manufacturer's Dats Reports to be anached

.i l CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reolacement conforms to the rules of the ASME Code, Section XI. repair or replacernent Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A b 0V Signed M X/M Date 6 , 19 'Ownc't or Owner's Deaignes, Title I j CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wiwonsin and employed by HSBil. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to - May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. l070l<WlYV'AW ~" Commissions [ 1rdpector3 Signature National Board, State. Province, and Endorsements Date AI 19 9 [

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date February 2.1994 Name I

231 W. Michigan Ave.. Milwaukee. WI 53201 Sheet 1 of 2 Addreas

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 936530 Address Repair Organization P.O. No.. Job No., etc.
3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address

4. Identification of System Safety Iniection Westinghouse E-Spec 569866
5. (a) Applicable Construction Code USAS B31.119fi Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components

.====

Repaired, ASME National Replaced.

Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Replacement (Yes or No) Piping SI-150lR-02 N/A N/A N/A N/A N/A Repaired No

7. Description of Work Reonir linear indication discovered on SI cioine
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other 50 Pressure esi Test Temp.

'F YT NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) His Form (E00030) may be obtained from the Order Dept., ASME 34$ E. 47th St., New York, N.Y.10017 7 s

  • -r-m

y i Sheet _2,,,, of _2_ Form NIS-2 Continued

9. Remarks _RRM 93-0085 Applicahle Manufacturer's Data Reporu to be susched CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reoair conforms to the rules of the ASME Code, Section XI.

repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed Ah. A0 N SMMO4M Date L 7 ,19 fI bwner or ower's Designee, Title [ / CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Oner's Report during the period May 6.1993 to May 12.1994 , and state that to the best of my knowledge and belief, the Owner has performed exanunations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XL By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. 1 Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property. damage or a loss of any kind arising from or connected with this inspection. hY Commissions l0Y3/ r WIYV L A i / Inspector's Signature National Board, State, Province, and Endorsemenu Date V 8b 19f[

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comnany Date April 27.1994 Name 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Address

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWRs 935950. 940285. 940232 Address Repait Organization P.O. No., Job No., etc.
3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers WI 54241 Expiration Date N/A Address

4. Identification of System Chemical and Volume Control Westinghouse Spec
5. (a) Applicable Construction Code ANSI B31.119,6.L8_ Edition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) CV-00110C N/A N/A N/A N/A N/A Repaired N 'f

7. Description of Work Replace CV-Il0C air onerator with a manual valve operator. refurbish air onerator and reinstall it.
8. Tests Conducted: Hydrostatic 0 Pneumatic O Nominal Operating Pressure O Other Pressure psi Test Temp.

'F test of instrument air line NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 1I in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017 r

Sheet 2 of 2 Fonn NIS-2 Continued

9. Remarks RRM 94-0003 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE

~ We certify that the statements made in the report are correct and this Repair conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A 1 5 I d c a b siO F Date IW Signed 0 , 19 91 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBil. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions /d78/i @7F Nk1 r i / Inkpector/s Signature Nationat Board, State, Province, and Endorsements Date dME 7 19 N \\

l FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comnany Date Acril 22.1994 Name 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addreu

2. Plant Point Beach Nuskar Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 940364 Addresa Repair Organizanon P.O. No., Job No., etc.
3. Work Preformed By Phillies Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Addnu
4. Identification of System Main Steam
5. (a) Applicable Construction Code ANSI B31.1 19E Edition. N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME NaGonal
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufactunt Serial No.

No. Idennficadon Built Replacement (Yes oe No) EB-1 MS-H5 N/A N/A N/A MsH45 N/A Replacement N i

7. Description of Work Modify suonort EB-1-MS-H5 in accordance with MOD 93-047
8. Tests conducted: IIydrostatic 0 Pneumatic 0 Nominal Operating Pressure O Other 50 Pressure esi Test Temp.
  • P l

VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) e eh sheet is numbenxi and the number of sheets is recorded at the top of this form. -~ e 1 (12/82) 1hia Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New Yort. Y.10017

Sheet _2_ of _2_ Form NIS-2 Continued

9. Remarks RRM 94-0004 Applicable Manufacturer's Data Repons to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reolacement conforms to the rules of the ASME Code, Section XI.

repair or replaceawra Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A / $[ RT (w/dAS Date l /( .19 'l Y Signed + ~ Owner or Owner's Designes. Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wiwonsin and employed by HSBII. CO. of Hartford. CT have inspected the con:x>nents described in this Owner's Report during the period May 6.1993 to - Msv 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed exammations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector not his employer makes any nrranty, expressed or implied, concerning the examinations and corrective measures described in this Ower's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ( Commissions /079/, Mi 77, E db A / ~ Inspdctor's Signature National Board, State, Province, and Ohiorsements LV 2I 19 N Date e

i l l FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date Aoril 15.1994 Name 231 W. Michiran Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addnaa

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 940365 Address Repair Organintion P.O. No., Job No., etc.
3. Work Preformed By Phillins Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A 2860 Glenmore Road. Green Bay, WI 54311 Expiration Date N/A Addresa 4 Identification of System Feedwater
5. (a) Applicable Construction Code N/A 19N!/A Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components Repaired.

ASME National

Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacernent (Yes or No) EB-9-FW-H 10 N/A N/A N/A H-10 N/A Replacement N

7. Description of Work Modify succort in accordance with MR 93-047
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other E)

Pressure osi Test Temp.

  • F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) 'This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet 2 of1 Form NIS-2 Continued

9. Remarks RRM 94-0005 Apphcable Manufacturer's Data Reports to be suaehed 1

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Renlacement conforms to the rules of the ASME Code, Section XI. repair or nplacement i Type Code Symbol Stamp N/A i Certificate of Authorization No. Docket 50-266 Expiration Date N/A M // / Signed. S /!'T 1U ('a d dY Date i o [T . 19 D I 6wner or Owner's Dedgnee, Tide [ I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel l Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of liartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss f any ki d arising from or connected with this inspection. //- eA Coassi-am. win. z. o / Inspec6r's signatus Nadonal Board, State. Province, and Endorumess Date l Y / E' 19 9

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date Aoril 23.1994 Nanw 231 W. Michiran Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addreu

2. Plant Point Beach Nuclear Plant Unit i Nanw 6610 Nuclear Road. Two Rivers. WI 54241 MWR 940369 Addreu Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Phillins Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A

.2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Address

4. Identification of System Safety Iniection l
5. (a) Applicable Cons;nr+hn Code ANSI B31.1 19,62, Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1916, no addenda j
6. Identification of Components Repaired or Replaced and Replacement Compouws m-R,fL.i.

Asiw1E National Replaced. Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Replacement (Yes or No) PS SI-250lR.1-SI4 N/A N/A N/A SI44 N/A Replacement N g*

7. Description of Work Replace existine eine clame with heavy duty clamo.
8. Tests Conducted: Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure O Other S Pressure osi Test Temp.

'F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet _2_ of _2_ Form NIS-2 Continued

9. Remarks RRM 94-0006 Applicable Manufacturer's Data Reports to be enached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reolacement conforms to the rules of the ASME Code, Section XI.

repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A [. M G aldt" Date r 15 . 19 bh Signed own'er or Owner's Designee, Title ~ d CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. C'" have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed exanunations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. YD Commissions /0 73 / Wl '75' r IAA i [ Inspector's Signature National Board, State,1%vince, and Endorsernents Date 4 LY' 2/ 19 '7 s

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Company Date April 23.1994 Name 231 W. Michican Ave.. Milwaukee, WI 53201 Sheet 1

of 2 Address

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWRs 940371. 940373 Address Repair Organization P.C. No., Job No., etc.
3. Work Preformed By Ehillins Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A

^ 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Address

4. Identification of System Safety Iniection Westinghouse Spec E-9676262
5. (a) Applicable Construction Code ANSI B31.1 19M. Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Componea Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) SI-250lR 5-S!!0 N/A N/A N/A SI10 N/A Replacement No SI-150lR-5-R194 N/A N/A N/A R-194 N/A Replacement No

7. Description of Work Modify supports for NRC IEB 7914 reconciliation procram
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other E Pressure psi Test Temp.
  • F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the aumber of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet,_2_ of _2_ Form NIS 2 Continued

9. Remarks RRM 944]O7 Apptkable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the staternents made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI.

repeir or replacement Type Code Symbol Stamp N/A Certificate of Authe.rization No. Docket 50-266 Expiration Date N/A K .19 N Signed 4+ 161 6&45-Abr Date (i owner or Owrwr's Designee, Tide l CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the Nationa' Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to MsY 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a 1 of an kind arising from or connected with this inspection. Commissions /07:?/. WE78'. A ZA / Inspe/ tor's SigrIature National Board, State, Provise, and Endorsements Date [- v 20 199Y

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date Anril 29.1994 Name 231 W. Michinan Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Address

2. Plant Point Beach Nuclear Plant Unit 1 Nana 6610 Nuclear Road. Two Rivers. WI 54241 MWRs 940293. 940294. 940461. 940463 Addresa Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Phillios Getschow Type Code Symbol Stamp N/A Nanw Authorization No. N/A 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Address
4. identification of System Main Feed
5. (a) Applicable Construction Code ANSI B31.1 1962 Edition, N/A Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components Repaired.

ASME National

Replaced, Code Nanw of Name of Manufacturer Board Other Year or Stamped i

Component Manufacturer Serial No. No. Identincation Built Replacenwns (Yes ) or No) CSM66AA N/A N/A N/A CS-466AA N/A Replacement No CS-00466BB N/A N/A N/A CS.466BB N/A Replacenwnt No CS-00476AA N/A N/A N/A CS-476AA N/A Replacement No CSM76BB N/A N/A N/A CS-476BB N/A Replacement No i i

7. Description of Work Install test connections on fechater line to enable testine of main feed check valves
8. Tests conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other M Pressure.1400 psi Test Temp. 90 *F Inservice leak test in accordance with Relief Request PTP-3-03 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this fann. (12/82) 1his Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet,_2_ of L Form NIS-2 Continued

9. Remarks RRM 94-0008 Applicable Manufacturer's Data Repona to be anached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI.

repair or replacemers Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date.,NB IST beta >eDate ki,k M 19 9 y Signed A# re v owner or owner' Designee, Title j CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the Natiou Board of Boiler and Pressure Vessel Inspectors and the State or Province c f Wisconsin and employed by HSBil. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinaticas and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinatiom; and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions /878/ r M/ 7I, - /~ Inspedor s signature National Board, State, Province, and Edorsements Date Ly 5 19 W

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date April 24.1994 Name 231 W. Michigan Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Address -2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 940370 Address Repair Organization P.O. No., Job No., etc.

3. Work Preformed By Phillips Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A

_2f 60 Gienmore Road. Green Bay. WI 54311 Expiration Date N/A Address

4. Id wification of System Chemical and Volume Control Svustem
5. (a) Applicable Construction Code ANSI B31.1 19#2. Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) SI-250lR-1-S839 N/A N/A N/A N/A N/A Replacement No 'r 1

7. Description of Work Modify sunoort SI-250lR-1-S839 (support on valves SI-839A. B. C. D) by addine weld and plate material.
8. Tests Conducted: Hydrostatic 0 Pneumatic O Nominal Operating Pressure O Other (3 Pressure nsi Test Temp.
  • F VT-3 NOTE: Supplemental sheets in form oflists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

l Sheet _1 of _2_. Form NIS-2 Continued

9. Remarks RRM 94-0010 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reolacement conforms to the rules of the ASME Code, Section XI.

repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiation Date N/A M T [a 2/.Ab/ Date At ,19 i V Signed 4 - 1 ' owner or ower'. Designee, Tide CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed exammations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a 1 ss of any kind arising from or connected with this inspection. de. f Commissions /073/,ll/75' 5 bY Moctor's Signature Nanonal Board, State, Province, and Endorsements Date a & 25-19 W

l FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date April 23.1994 Name 231 W. Michigan Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addrena l

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 940372 Addreas Repair Organization P.O. No., Job No., etc.

]

3. Work Preformed By Phillips Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date, N/A Addreas
4. Identification of System Safety Iniection t
5. (a) Applicable Construction Code ANSI B31.11962 Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components i
Repaired, ASME National
Replaced, Code i

Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Replacement (Yes or No) SI.2510R-5-R102 N/A N/A N/A R102 N/A Replacement N l

7. Description of Work Add shtms to suonort R102
8. Tests Conducted: Ilydrostatic O Pneumatic 0 Nominal Operating Pressure O Other 50 Pressure osi Test Temp.

'F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) 'nis Form (E00030) may be obtained from ths Order Dept., ASME,345 E. 47th St. New York, N.Y.10017 i

Sheet 1 of 2 Form NIS-2 Continued

9. Remarks RRM 94-0011 Applicable Manufacturer's Data Reports to be ansched CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reolacement conforms to the rules of the ASME Code, Section XI.

repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed [ D M l'"ba Yr Date /7 19 b OIvner or Owner's Designee, Title ~ CERTIFICATE OF INSERVICE INSPECTION 1 I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel l Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.- By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Y Commissions $ I 5'lt YllS'r IYY b ' Inspector's Signature Nanonal Board, State Province, and Endorsernents 4-by 2l 19 VY Date

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI j

1. Owner Wisconsin Electric Power Company Date April 25.1994 Naaw J31 W. Michigan Ave.. Milwaukee, WI 53201 Sheet 1

of 2 Addresa j

2. Plant Point Beach Nuclear Plant Unit 1 Nane 6610 Nuclear Road. Two Rivers. WI 54241 MWRs 941065. 940367. 940368 Addreas Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Phillips Getschow Type Ccde Symbol Stamp N/A Name Authorization No. N/A 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Address
4. Identification of System Chemical and Volume Control Svustem
5. (a) Applicable Construction Code ANSI B31.11957 Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) PS CH 151R-2-H222 N/A N/A N/A H222 N/A Replacement N PS CH 151R-2-SKA2 N/A N/A N/A SKA2 N/A Replacement N PS CH 151R-2-SKAl N/A N/A N/A SKAl N/A Replacement N

7. Description of Work Perform modifications on RCP seal water einine sunoorts
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other E Pressure nsi Test Temp.

'F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

l l 1 Sheet 1 of _jL, j 1 Form NIS-2 Continued )

9. Remarks RRM 94-0012 Applicable Manufacturar's Data Reports to be attached 1

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed dl U Date D . 19 fV / owner or owner's Designee. Title [ ~ CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. Cr have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer trakes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions l0 Ulr NI?Vr SNk /' Inspector's Signature National Board, state, Province, and Endorsements Date 4IY 2/ 19 9

l i l FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date Aoril 15.1994 Narna 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addreu

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 940801 Address Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Phillins Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Address
4. Identification of System Reactor Coolant
5. (a) Applicable Constmetion Code ANSI B31.11962. Edition, N/A Addenda, None

, Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989. no addenda

6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Buih Replacement (Yes or No) PS RC 250!R-R-SK2 N/A N/A N/A SK-2 N/A Replacement N ',f

7. Description of Work Remove U-bolt from ninine suonort
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other E Pressure esi Test Temp.

'F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) nis Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 47th St., New York, N.Y.10017

Sheet 2 of _2_ Form NIS-2 Continued

9. Remarks RRM 94-0015 Applicable M.nufactunt's D.ta Reports to be enached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Reolacement conforms to the rules of the ASME Code, Section XI.

npair or repi.cernene Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed [& /4 r Date . 19 E owner or owner's Designee, Title [/ [ CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's. Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Y Commissions /0 Y.?/, WI 7V. I* N* A / iLpecior. sign.ture

n. tion.i no.rd, Sute, ProviEs, and Endornenwnu Date LY 20 19 VY

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Company Date April 24.1994 Narne 231 W. Michiran Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addreas

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 940536 Address Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Phillins Getschow Type Code Symbol Stamp N/A Nanw Authorization No. N/A 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Address
4. Identification of System Charring
5. (a) Applicable Construction Code ANSI B31.11951 Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Narne of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yea or No) PS Cil-250lR-4-R84 N/A N/A N/A R84 N/A Replacement No I

7. Description of Work Provide shims to whio restraint to make into cine suonort
8. Tests Conducted: Ilydrostatic O Pneumatic O Nominal Operating Pressure O Other SD Pressure psi Test Temp.

'F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet _,1_ of _J_, Form NIS-2 continued

9. Remarks RRM 94-0016 Applicable Manufacturer's Data Repons to be enached 1

CERTIFICATE OF COMPLIANCE We cedify that the statements made in the report are correct and this Reolacement conforms to the rules of the ASME Code, Section XI. repair or replacenwar Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A f 7'>.[ [oc/t< O o >r Date I, 19 Yk Signed /k d lowner k owner's Designee, Tide /- CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions l0 7.7l 1 W/??r INA / ' Inspector's Signature National Board, State, Province, and Endorsements Date kbf $V 19 f

l 1 l FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date April 22.1994 Name 231 W. Michiran Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addresa

2. Plant Point Beach Nuclear Plant Unit I Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 935020 Address Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address

4. Identification of System Component Cooling Water
5. (a) Applicable Construction Code USAS B31.119ft _ Edition, N/A Addenda,_ None Code Case 7

(b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda

6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME i

National

Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. IJentification Built Replacement (Yes or No) CC@777B N/A N/A N/a N/A N/A Replacement No

7. Description of Work Replaced one body-to-bonnet nut on CC-00777B.
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure 29 Other O Pressure 0.8 nsi Test Temp.

54

  • F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbend and the number of sheets is recorded at the top of this form. (12/82) 'nis Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet _2 of __2_. t Form NIS-2 Continued

9. Remarks RRM 94-0019 Applicable Manufacturer's Data Repons to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Renlacement conforms to the rules of the ASME Code, Section XI.

repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A [0erdh f Date L M .19 I Y Signed Owner of Owner's Desipee, Title CERTIFICATE OF INSERVICE INSPECTION I, the unou signed, M~dmg a valid commission issued by the National Board of Boiler and Pressure Vessel r Inspectors and b State or hvvince of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the perion May 6.1993 to May 12.1994 , and state that to the best of my knowledge ar.d belief, the Owner has performed exammations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions [8 7.E/ e W!I

  • W"*

/ [ Inspectors Signature National Board, State, Province, and Endorsernents Date Ly 2'2. 19 9 /

FORh1 NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power ComnanY Date Anril 17.1994 Name 231 W. Michiran Ave.. Milwaukee WI 5320_L Sheet 1

of 2 Addresa ~ 2. Plant Point Beach Nuclear Plant Unit i Name 6610 Nuclear Road. Two Rivers. W1 54241 MWR 915279 Addresa Repair Organization P.O. No., Job No., etc.

3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address 4, Identification of System Chemical and Volume Control Westinghouse Spec 676257

5. (a) Applicable Construction Code N/A 19_ Edition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) CV40257 Crosby DS-C-79232 N/A CV-257 N/A Replaced Y '[ i 1 l

7. Description of Work Renlace CV-257 with a relief valve desiened to relieve a H, and N, atmosphere
8. Tests Conducted: Hydrostatic 0 Pneumatic O Nominal Operating Pressure O Other (E Pressure 70 nsi Test Temp. __*F Leak test in accordance with RMP 198 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is

  • ~~

numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

) A 1 Sheet 2 of 2 l 1 Form NIS-2 Continued

9. Remarks RRM 94-0020 Applicable Manufacturer's Data Reports to be attached 1

I CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI. repair or replacernent Type Code Symbol Stamp N/A Certificate of Au horization No. Docket 50-266 Expiration Date N/A Signed b b" 'E ate 3 , 19 9Y D W Owner or Owner's Designee, Title l CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBil. CO. of Ilartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. i Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or f property damage or a loss of any kind arising from or connected with this inspection. h Commissions /0 7 ?/, WI7 Tr', k, NZ /' Inspector's signature National Board, State, Province, and Endorsementa l bNF 7 19 N Date L 3 d I J i

l d FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power comoany Date Anril 10.1994 i

Name 231 W. Michigan Ave.. Milwaukee. WI 53201 Sheet 1 of 2 Addnu

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 PO 247390 Addrew Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Crane-Alovco Type Code Symbol Stamp VR Name Authorization No. 262 720 N. Parkwood Dr. Romeoville. IL 60441 Expiration Date 72/02/96 Address
4. Identification of System Main Steam
5. (a) Applicable Construction Code N/A.19 N/A Edition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components i
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Othet Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yea or No) MS-2006 Crosby 50412M-1 N/A N/A N/A Repaind Y I

7. Description of Work Reoair MS-2006
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other(E Pressure osi Test Temp.

'F Leak test is accordance with OM-1,1981 ed. NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is j numbered and the number of sheets is recorded at the top of this form. (12/82) Thia Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet _2_ of._2_ Form NIS-2 Continued

9. Remarks RRM 94-0021 Applicable Manufacturer's Data Reports to be anached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Renair conforms to the rules of the ASME Code, Section XI.

repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed i N Mr Date [N#/Y 19 N Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components dea ribed in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Leport in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or i property damage or a loss of any kind arising from or connected with this inspection. 4 Commissions /0 X N WT-M TM [ Inspectos Signature National Board, State, Province, and Endorsements r Date Lv 0i 19 YY

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comnany Date Antil 10.1994 Name 231 W. Michiran Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addrena

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 PO 247390 Addresa Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Crane-Alovco Type Code Symbol Stamp VR Nanw Authorization No. 262 720 N. Parkwood Dr. Romeoville. IL 60441 Expiration Date 02/02/96 Addreas
4. Identification of System Main Steam
5. (a) Applicable Construction Code N!A,19 N/A Edition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Narne of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Bulk Replacement (Yes or No) MS-2008 Crosby 50412M-1 N/A N/A N/A Repaired Y

7. Description of Work Renair MS-2008
8. Tests Conducted: Hydrostatic O Pneumatic 0 Nominal Operating Pressure O Other (8 Pressure usi Test Terre.

'F Leak test is accordance with OM-1,1981 ed. NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) Thia Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 47th St., New York, N.Y.10017

Sheet _2_ of _2_ Form NIS-2 Continued

9. Remarks RRM 94-0022 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Repair conforms to the rules of the ASME Code, Section XI.

repair or replacerneos Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed 1 Mh 2W (wrA.'udv Date wWL M 19 3Y I/ owner or owner's D..ignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions /d IN, N N / / [ Mector's Sigluture National Board, State, Province, and Endorsements Date u Nci $ 19 Y Y

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date Aoril 27.1994 Nanw 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Address

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 913462 Addreu Repair OrEnnization P.O. No., Job No., etc.
3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp JT/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Addreu

4. Identification of System Chemical and Volume Control System
5. (a) Applicable Construction Code USAS B16.519.21. Edition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaind, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or.

Stamped Componerd Manufacturer Serial No. No. Identification Buik Replacement (Yes or No) CV-00216 Grinnel! N/A N/A CV-216 N/A Replacement N '[

7. Description of Work Replaced bonnet and diaohraem assembly on CV-216.
8. Tests Conducted: Hydrostatic O Pneumatic O Nomina! Operating Pressure N Other O Pressure 14 osi Test Temp. 103

'P NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered arid the number of sheets is recorded at the top of this form. (12/82) 'nia Form (Eo0030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.100t7

Sheet _],_ of 2_ Form NIS-2 Continued

9. Remarks RRM 94-0024 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI.

repair or repiscement J Type Code Symbol Stamp N/A Certificate of Authorization No Docket 50-266 Expiration Date N/A / I A Signed Ah [ h Date 4M / . 19 Owner or Owner's Design'e, Title [ e CERTIFICATE OF INSERVICE INSPECTION 4 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBil. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state l that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, l Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report, Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of ny kind arising from or connected with this inspection. Commissions /O Y]/ i W/' I?> ll1 T Y lb o / Inspector's Signature National Board, State, Province, and Endorsements Date Nef lY 19 fY l

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date April 27.1994 Name 231 W. Michigan Ave. Milwaukee. WI 53201 Sheet 1

of 2 Address

2. Plant Point Beach Nuclear Plant Umt 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWRs 913461 n

Addresa Repair Organization P.O. No., Job No., etc.

3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address

4. Identification of System Chemical and Volume Control System
5. (a) Applicable Construction Code USAS B16.519 2LEdition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identificati' n of Components Repaired or Replaced and Replacement Components o

l

Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) CVM12 Orinnell N/A N/A CV-212 N/A Replacement N

7. Description of Work Reolaced bonnet and dischracm assembly on CV-212.
8. Tests Conducted: Hydrostatic O Pneumatic 0 Nominal Operating Pressure M Other O Pressure 42.5 osi Test Temp. 104
  • F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet 2 of1 Form NIS-2 Continued

9. Remarks RRM 94-0025 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Renlacement conforms to the rules of the ASME Code, Section XI.

repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A f Signed _ N4'?, M N 39 (ar WI kr Date dess /Y ,19 kN Owner or Ow ner's Designee, Title ' f CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBil. CO. of Hartford. CT have inspected the components described in this Owner's ' Report during the period May 6.1993 to MaY 12.1994 , and State that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions /0 7J/, W/- W, A, A1, r / ' Inspector's Signature Nadonal Board, State. Province, and Endorsements Date wr e- /4 19 9Y

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date April 23.1994 Name 231 W. Michiran Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addreas

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers WI 54241 MWR 940363 Address Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Phillies Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Addreae
4. Identification of System Main Steam
5. (a) Applicable Construction Code N!% 19Ef% Edition, N/A Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda i
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) EB-1-MS-H1 N/A N/A N/A MSH41 N/A Replacement No l 1 1

7. Description of Work Shim base niate with tubine to orovide corrective action for damared erout nad.
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other E Pressure osi Test Temp.
  • F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

+ x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) nia Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet _2_ of _2_ Form NIS-2 Continued

9. Remarks RRM 94-0026 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Renlacement conforms to the rules of the ASME Code, Section XI.

repair or reptacement Type Code Symbol Stamp N/A Certificate of uthorization No. Docket 50-266 Expiration Date N/A Signed h 7 E I"*d'h*!" Date N 9Y . 19 O'wner or Owner's Designee Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBil. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions /073l. WI 75'. Ir N A / Inspector's Signature National Board, State, Province,'and Endorsements Date W D 19 N

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Company Date Anril 29.1994 Name 231 W. Michinan Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addreas

2. Plant Point Beach Nuclear Plant Unit i Name 6610 Nuclear Road. Two Rivers. WI 54241 MWRs 9401539. 9401540 Address Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Phillins Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Address
4. Identification of System Main Feed Bechtel Spec. M-078, M-081
5. (a) Applicable Construction Code ASA B31.11962 Edition, N/A Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) CS-00466AA Chapman-Crane N/A N/A CS-466AA N/A Replacement No 'f I CS-00476AA Chapman-Crane N/A N/A CS-476AA N/A Replacement No

7. Description of Work Renlace feedwater check valves CS-00466AA and CS-00476AA because ofleak bv.
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other Di3 Pressure _1400.. psi Test Temp. 90 'F Inservice leak test in accordance with Relief Request PTP-3-03 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this repod is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/32) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet _2__ of _2_ Form NIS-2 Continued

9. Remarks __RRht{4-0027 Applicable Manufacturer's Data Reports to be anached CERTIFICATE OF COMPLIANCE

'We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI. repair or replacemers Type Code Symbol Stamp N/A Certificate Autho ' tion No. Docket 50-266 Expiration Date N/A Signed A M N m NR Date M . 19 I Owner or O*mr's Designee, Title Y CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. Cr have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warrang, expressed or implied, concerning the examinations and corrective measures described in this Ownet's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss o any 'nd arising from or connected with this inspection. WL An. Commissions /073/,WIWu 5 " Inspecto/a Signat'uIe Nanonal Board, State, Province, and Endorsementa Date ed Y 2 b 19

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS l As Required by the Provisions of the ASME Code Section XI I

1. Owner Wisconsin Electric Power Comoany Date Aoril 15.1994 Narne 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet 1

of 2 l Address I

2. Plant Point Beach Nuclear Plant Unit 1 Name 1

6610 Nuclear Road. Two Rivers. WI 54241 MWR 9401614 l Address Repair Organimion P.O. No., Job No., etc.

3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A l Nanw Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Addresa l

4. Identification of System Residual Heat Removal Bechtel Spec 6118-M-002 1
5. (a) Applicable Construction Code E/A,19N/A Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes l or No) f P-010B Pacific Pump N/A N/A N/A N/A Replacement No l

7. Description of Work Replace the rotatine assembly on P-010B.
8. Tests Conducted: liydrostatic @

Pneumatic O Nominal Operating Pressure O Other O Pressure 750 psi Test Temp. Ambient *F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. 1 x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet numbered and the number of sheets is recorded at the top of this form. (12182) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017 l

Sheet 2_ of _jL, Form NIS-2 Continued

9. Remarks RRM 94-0029 Applicable Manufacturer's Data Reporta to be attached 4

CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A 3 ,19 iV Signed A b M C@RhtMATCA Date I Owner or Owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspecton, and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to Mav 12.1994 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss. f any 'nd arising from or connected with this inspection. / Commissions N 7U, M 7 ~ ' [ 6 Inspec1 r's Signai6re National Board, State, Province, and Endorsementa Date

u. C 6,3' 196

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date April 25.1994 Name 231 W. Michinan Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addreas

2. Plant Point Beach Nuclear Plant

'init 1 Nams 6610 Nuclear Road. Two Rivers. WI 54241 iWR 9401938 Addresa Repair Organization P.O. No., Job No., etc.

3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. X'A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Dau N/A Addnas

4. Identification of System Safety Iniection
5. (a) Applicable Construction Code USAS B31.1 1962 Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Narne of Manufacturer Board Othe Year or Stamped Component Manufacturer Serial No.

No. Identificadon Built Replacement (Yes or No) Piping $1250lR43 N/A N/A N/A SIS-02-SI-1003-22 N/A Repaired No l

7. Description of Work Buff out rounded indication 3

)

8. Tests Conducted: Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure O l

Other IQ Pressure osi Test Temp. ' *F PT NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. ] 4-I (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet 1 of 2 Form NIS-2 Continued

9. Remarks RRM 94-0030 Applicable Manufacturer's Det. Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Renair conforms to the rules of the ASME Code, Section XI.

repair oc replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A ?b Date. 6 . 19 IV Signed o' ner or owner's Designee, Tiu. w CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 ..and state that to the best of my knowledge and belief, the Owner has performed exammations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of an kind arising from or connected with this inspection. dad / Commissions /073/a W/ 7E. $Y ~" /~ io./utocs siiwo.

u. tim.i so.re, si ie, erovince,.na soaor emeni, Date LY 27 19 W

.= i FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wiwonsin Electric Power Company Date Anril 27.1994 Name 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet I

of 1 AJdress

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 9401615 Address Repair Organization P.O. No., Job No., etc.

I

3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address

4. Identification of System Reactor Coolant
5. (a) Applicable Construction Code ASME See III 196J_ Edition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components 4
Repaired, ASME National Replaced,-

Code Name of Name of Manu facturer Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Replacement (Yes or No) Pressurizer Westinghouse 16A6256-1 NB 0685 T-001 1986 Replacement Y 't

7. Description of Work Replace one stud on pressurizer manway i
8. Tests Conducted: Hydrostatic d Pneumatic 0 Nominal Operating Pressure O Other J( Pressure 2085 nsi Test Temp.

'F VT-1, RCS leak test iaw IT 230. Technical Specs NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x !I in., (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet 2 of1 Form NIS-2 Continued

9. Remarks RRM 94-0031 Applicable Manufacturer's Data Reports to be attached j

i s CERTIFICATE OF COMPLIA.NCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A L Certificate of Authorization No. Docket 50-266 Expiration Date N/A 6u/n.,dr h'e

  • 7

,19 W Signed t Date Owner or Owner's Designee, Title CERTIFICATE OF INSER'VICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBil. CO. of Hartford. CT have inspected the components described in this j Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions /07 I/ @ 77, A,/f/ T / inspector's Signature National Boa'rd, State, Province, and Endorsements Date uNr /J 19 W 4 e

l l l l FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comoany Date April 25.1994 Name 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addren

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road Two Rivers. WI 54241 MWR 9401518. 9401519 Address Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Phillins Getschow Type Code Symbol Stamp N/A Name Authorization No. N/A 2860 Glenmore Road. Green Bay. WI 54311 Expiration Date N/A Address
4. Identification of System Safety Iniection Westinghouse Spec G676262
5. (a) Applicable Construction Code ATSC fth Edition, N/A Addenda, None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National Replaced.

Code Name of Name of Manufacturer Board Other Year or Starnped Component Manufacturer Serial No. No. Identification Bulk Replacement (Yes or No) 1-SI 844A N/A N/A N/A N/A N/A Replacement No l-51-844B N/A N/A N/A N/A N/A Replacemera No

7. Description of Work Modify valve sunoorts on SI-844A/SI-844B to orovide seismic restraint.
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other 2 Pressure esi Test Temp.
  • F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E 47th St., New York, N.Y.10017

Sheet,,,2_ of1 Form NIS-2 Continued

9. Remarks RRM 94-0032 Applicable Manufacturer's Data Reports to be attached

) l CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this _ Reolacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A r Signed Ap dert#44% Date M / 19 I dwner obner's Designee, Title [ CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to MaY 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions 82f/, W# [ Insp4ctor's Signature National Board, State Province, and Endorsements Date us. I 19 9Y

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comnany Date April 27.1994 Name 231 W. Michican Ave.. Milwaukee, WI 53201 Sheet I

of 2 Address

2. Plant Point Beach Nuclear Plant Unit 1 Narne 6610 Nuclear Road. Two Rivers. WI 54241 MWR 9401366 Address Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address

4. Identification of System Reactor Coolant Westinghouse Spec 676258
5. (a) Applicable Construction Code N/A 19_ Edition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME National
Replaced, Code Name of Name of Manufacturer bard Other Year or Stamped Component Manufacturer Serial No.

No. Identification Built Replacement (Yes or No) RC-00427 N/A N/A N/A RC-427 N/A Replacement N

7. Description of Work Renlace studs and nuts on RC-427 because of boric acid corrosion l

1

8. Tests Conducted: Hydrostatic 50 Pneumatic 0 Nominal Operating Pressure O Other Q Pressure 2085 usi Test Temp.
  • F VT-1 of studs, RCS leak test iaw IT-230, Technical Specs j

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

Sheet 2 of _2_ Form NIS-2 Continued

9. Remarks RRM 94-0033 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI.

repair or repiecenwn: Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A M I"'$ d Date i 19 U Signed Owner or Owner's Designee Title Y CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to _ _ May 12.1994 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective rneasures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his cmployer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions /073/ Vf-7 E, A, d) i 1. i [ Inspecto'r's Signature National Board, State. Province, and Endorsements Date d e-O 19 9Y

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsjr Electric Power Company Date Acril 27.1994 Name 231 W. Michiean Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Address

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 9401371 Address Repair Organization P.O. No., Job No., etc.
3. Work Preformed By Wisconsin Electric ComoanY Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address
4. Identification of System Chemical and Volume Control
5. (a) Applicable Construction Code ANSI B31.1 2957 Edition, None Addenda, None Code Case

{ (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda

6. Identification of Components Repaired or Replaced and Replacement Components
Repaired, ASME Nat;onal Replaced.

Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Replacement (Yes or No) FIC-00179 N/A N/A N/A FIC-179 N/A Replacement No 'f'

7. Description of Work Replace studs and nuts on flance of FIC-179.
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure E Other O Pressure 2085 psi Test Temp.

'F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in. x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017

l Sheet _,2_, of _1., Form NIS-2 Continued

9. Remarks RRM 94-0034 Applicable Manufacturer's Data Reports to be anached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Replacement conforms to the rules of the ASME Code, Section XI.

npair or nplacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed N M bdMt-Date ,19 f V ' Owner or Owner's Designec, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBII. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period MSV 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed exammations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. '^ [. Commissions l0Yll, WI l[('r 5' Y Indector's Signature National Board, State, Province, and Endorsements bf A 19 VY Date l

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS 1 As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Comnany Date Aoril 25.1994 Name 231 W. Michican Ave.. Milwaukee. WI 53201 Sheet 1

of 2 l Address

2. Plant _foint Beao's Nuclear Plant Unit 1

) Narne 6610 Nuclear Road. Two Rivers. WI 54241 MWR 9401960 Address Repair Organization P.O. No., Job No., etc.

3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No. N/A 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address

4. Identification of System Comnonent Cooline Water
5. (a) Applicable Construction Code USAS B31.1 1961_ Edition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components l
Repaired, ASME National
Replaced, Code j

Name of Name of Manufacturer Board Other Year or Stamped Cornponent Manufacturer Serial No. No. IJentification Built Replacernent (Yes or No) PS AC 152N-1-ii313 N/A N/A N/A H.313 N/A Repaired N l l

7. Description of Work Tichten unner and lower locknuts on tension bar.
8. Tests Conducted: Hydrostatic O Pneumatic O Nominal Operating Pressure O Other O Pressure osi Test Temp.
  • F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form. (12/82) This Form (E00030) may be obtained from the Order Dept., ASME,345 E. 47th St., New York, N.Y.10017 L

Sheet 2 of 2._ Form NIS-2 Continued

9. Remarks RRM 94-0037 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Repair conforms to the rules of the ASME Code, Section XI.

repair or replacement Type Code Symbol Stamp N/A y Certificate of Authorization

o. Docket 50-266 Expiration Date N/A Signed A

Ul bd Date f-/1-9'/ , 19 N bwner or Owner's Designee, Title l 1 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wisconsin and employed by HSBil. CO. of Hartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or 1 implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. 2 Commissions /C X7/ V/* 7P', _TA/4 i /~ 1/ispector'lSignature National Board, S' tate Province, and Endorsements Date d4 y /2-199/

i FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI

1. Owner Wisconsin Electric Power Company Date Anril 23.1994 Name 231 W. Michiean Ave.. Milwaukee. WI 53201 Sheet 1

of 2 Addreas l

2. Plant Point Beach Nuclear Plant Unit 1 Name 6610 Nuclear Road. Two Rivers. WI 54241 MWR 940509 Address Repair Organization P,0. No., Job No., etc.
3. Work Preformed By Wisconsin Electric Power Co.

Type Code Symbol Stamp N/A Name Authorization No, N/A ~ 6610 Nuclear Road. Two Rivers. WI 54241 Expiration Date N/A Address

4. Identification of System Safety Iniection System - Westinghouse Spec E 676262, Studs AISI C1050 Nuts SAE 1995 gr. 8
5. (a) Applicable Construction Code N/A 19,_ Edition, None Addenda,None Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1986. no addenda
6. Identification of Components Repaired or Replaced and Replacement Components Repaired.

ASME National

Replaced, Code Name of Name of Manufacturer Board Other Year or Stamped Component Manufacturer Serial No.

No. IJentification Built Replacement (Yes or No) 115-12 N/A N/A N/A N/A N/A Repaired N

7. Description of Work Replace tie rods on snubber HS-12
8. Tests Conducted: Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure O Other H Pressure nsi Test Temp.
  • F VT-3 NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8% in.

x 11 in., (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is. numbered and the number of sheets is recorded at the top of this form. (11/82) This Fonn (E00030) may be obtained from the Order Dept., ASME. 345 E. 47th St., New York, N.Y.10017 l

( l Sheet 2 of 2_ Form NIS 2 Continued

9. Remarks __ RRM 94-0038

) Applicable Manufacturst's Data Reports to be suached l CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this Repair conforms to the rules of the ASME CoJe, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. Docket 50-266 Expiration Date N/A Signed '49 TO f(tWbdr h@d b Date , 19 7 Owner or Owner's Designee, Title / CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Wie.consin and employed by HSBil. CO. of liartford. CT have inspected the components described in this Owner's Report during the period May 6.1993 to May 12.1994 . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions /D 7,.7/, 1+T - 7 F, Z 4, 4 [' ' Inspectors Signature ' National Board, State, Province, and Endorsements f Date _ wL- / O / 19[/ l}}