ML20072C302
| ML20072C302 | |
| Person / Time | |
|---|---|
| Site: | Browns Ferry |
| Issue date: | 06/16/1983 |
| From: | Mills L TENNESSEE VALLEY AUTHORITY |
| To: | Harold Denton Office of Nuclear Reactor Regulation |
| References | |
| NUDOCS 8306210014 | |
| Download: ML20072C302 (2) | |
Text
'
TENNESSEE VALLEY AUTHORITY CHATTANOOGA. TENNESSEE 374o1 400 Chestnut Street Tower II June 16, 1983 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C. 20555
Dear Mr. Denton:
In the Matter of the
)
Docket Nos. 50-259 Tennessee Valley Authority
)
50-260 50-296 In my June 13, 1983 letter to you, we provided you with Browns Ferry TS 189 dealing with the Standby Gas Treatment (SBGT) System surveillance testing and requested that this be handled on an emergency basis.
In discussions with your staff, we have reached the following agreement regarding the interpretation of the requirements of the presently approved subject technical specification (4 7.B.3.a).
Technical specification 4.7.B.3.a does not require a logic functional test from the primary sensor to system actuation and will be satisfied by our commitment to actuate the SBGT blowers from the appropriate relay in each unit's primary containment isolation system logic (16A-K-23) on a once per year interval.
Based on this agreement TS 189 is still needed, but not on an emergenof basis j
to preclude a forced shutdown of unit 3 on July 3, 1983 Your cooperation in this matter is greatly appreciated.
Very truly yours, TENNESSEE VALLEY AUTHORITY
@ m.
l L. M. Mills, nager l
l' Nuclear Licensing sworn to before Subscribeda]"n me this /6 day of JoA/C 1983 YA d'Cbh/
l Notary Public 7
My Commission Expires o
cc: See page 2 g
y,,c. L 1-DR O
9 8g* g I
P PDR An Equal Opportunity Employer m._
o
/* Mr. Harcld R. Denton June 16, 1983 00:
U.S. Nuclear Regulatory Commission Region II ATTN: James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303 Mr. R. J. Clark Browns Ferry Project Manager U.S. Nuclear Regulatory Commission 7920 Norfolk Avenue Bethesda, Maryland 20814 i