Text
.
Southern California Edison Company
$5 P. O. BOX 800 2 2 44 W ALN UT GROVE AVEN UE ROSEM EAD. C ALIFORNI A 917 70 J. G. H AY N E S TELE MONE June 3, 1983 o..... o, ~ u c a.. o,.....o ~,
U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region V 1450 Maria Lane, Suite 210 Walnut Creek, California 94596-5368 Attention: Mr. John B. Martin, Regional Administrator
Dear Sir:
Subject:
Docket Nos. 50-361 and 50-362 San Onofre Nuclear Generating Station Units 2 and 3 As requested, this letter provides our response for San Onofre Units 2 and 3 to IE Bulletin No. 83-03: Check Valve Failures in Raw Water Cooling Systems of Diesel Generators.
The diesel generator cooling water systems at San Onofre Units 2 and 3 have been reviewed, and it has been determined that there is no check valve in the these systems.
The diesel generator cooling water systems are corrosion inhibited closed loops which reject heat through fan cooled radiators. As these systems are not raw water cooling systems, and do not utilize check valves, IE Bulletin 83-03 is not applicable to San Onofre Units 2 and 3 and no further action related to this Bu?letin is being taken.
Subscribed on this 8#
1983.
day of W
Respectfully submitted, SOUTHERN CALIFOR IA EDISON COMPANY 8306070029 830603 By-Ah PDR ADOCK 05000361 J. G. Haynes/
0 PDR Manager of Nuclear Operations Subscribed and sworn tp before me this J&
day of U m 1 9 9.B
[
1_^ 1 ^.
^^^^3 OFriclAL SEAL AGNES CRABTREE f
.h Notapf Public in and for the County of l
t notaav rusuc - cauro==ia Los' Angeles, State of California