Interim Deficiency Rept Re Contact Leads on Hma Relays Supplied by Ge.Initially Reported 820818.All Relays Affected Will Be Inspected for Lead to Terminal Spacing.Also Reported Per Part 21
ML20071L950
Person / Time
Site: Perry  
Issue date: 09/17/1982
From: Davidson D
CLEVELAND ELECTRIC ILLUMINATING CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
REF-PT21-82 10CFR-050.55E, 10CFR-50.55E, RDC-61(82), NUDOCS 8209240188
Download: ML20071L950 (2)


Text

.

' THE CLEVELAND ELECTRIC ILLUMIN ATING COMPANY P O DOX 5000 e CLEVELAND, Ohio 44101 s TELEPHONE r216) 622-9800 m ILLUMINATING BLDG e 55 PUBLIC SOUARE Serving The Best Location in the Nation Dalwyn R. Davidson VICE PRESIDENT SVSTF M [NGINEERING AND CONSTHUCTION September 17, 1982 Mr. James G. Keppler Reglonal Administrator, Region III Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 RE:

Perry Nuclear Power Plant Docke t Nos. 50-440; 50-441 Contact Leads on HMA Relays Fupplied by General Electric

[RDC 61(82)]

Dear Mr. Keppler:

This let ter serves as an interim report pursuant to 10CFR50.55(e) on the potential signif Lcant def tciency concerning HMA relays supplied to Perry Nuclear Power Plunt by the General Electric Company (GE).

Mr. E. Riley of The Cleveland Electric Illuminating Company (CEI) notified Mr. P. Pelke of your of fice on Augus t 18, 1982, that this potential deficiency was being evaluated by CEI.

This letter contains a description of the deficiency and the method planned for comple tion of the evaluation.

Description of Deficiency This potential significant deficiency concerns HMA relays supplied by GE which were manuf actured between January 1976 and June 1981.

The length of the uninsulated flexible leads connected to the movable contacts of the relays may exceed the allowable dimensions which could result in reduced spacing be tween the lead and co L1 clecuit te rminals.

This condition was reported to the NRC by GE under' 10CFR21 in a le tter da ted April 1, 1982.

8209240188 820917 PDR ADOCK 05000440 S

PDR

-g SEP 2 0 082

Mr. James G. Keppler September 17, 1982 I

Method - Planned for Comple tion of Evalua tion Field Disposition Ins tructions (FDI) WNQB and WRMM were issued February 20, 1982, by GE for inspection and correction of any defective HMA Relays. All relays manuf actured during the-referenced time period will be inspected for lead to terminal-spacing. If it is determined that the leads can touch the coil circuit terminals, the condition will be corrected by assembling a heat shrinkable insulating tubing over the contact terminals according to procedures j

set forth in the referenced FDIs. Evaluation for Unit I should be completed by October 29, 1982, and for Unit 2, by October 31, 1983. We will then file our next report on this subject.

I j

Sincerely, Is4 9

Dal R. Davidson l

Vice President System Engineering and Construction DRD:pab l

cc: _Mr. M. L. Gildner l

NRC Site Of fice l

Director I

Of fice of Inspection and Enforcement U.S. Nuclear Regulatory CommissLon Washington, D.C.

20555 l