OPERATING DATA REPORT DOCKET NO. 50-333 DATE Dec. 9, 1978 COSIPLETED itY E.

'ufelt TELEPHONE r 310 M2-3840 OPERATING STATUS Notes Fit: Patrick I. Unit Name:

781101-781130

2. Reporting Period:

2436

3. Licensed Thermal Power (.\\lWt):

003

4. Nameplate Rating (Gross SlWe):

0#A

5. Design Electrical Rating (Net SIWE):

830

6. 51aximum Dependable Capacity (Gross 51We): 800
7. Maximum Dependable Capacity (Net.\\lWe):

I

8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Gise Reasons:

None None

.9. Power Level To which Restricted,If Any (Net.\\lWe):

10. Reasons For Restrictions,if Any:

This Month Yr to.Date Cumulatise 720 8016 29329 i

11. Hours in Reporting Period 0

5901.1 21482

12. Number Of Hours Reactor Was Critical 0

0 0

13. Reactor Reserve Shutdown Hours 0

5818.1 20790.2

14. Hours Generator on.Line u

0 0

[

!$. Unit Reserve Shutdown Hours 0

12288452 41550116

16. Gross Thermal Energy Generated (SIWH) 0 4140250 14081300
17. Gross Electrical Energy Generated (Slwil) 0 3991615 13620270
18. Net Electrient Energy Generated (MWH) 0 72.6%

70.9%

19. Unit Service Factor 0

72.6%

70.9%

20. Unic Assilability Factor 0

62.2%

66.4%

21. Unit Capacity Factor (Using alDC Nett 0

00.6%

56.6%

22. Unit Capacity Factor (Using DER Net)

U 3.7%

10.5%

23. Unic Forced Outage Rate
24. Shutdowns Scheduled Oser Next 6 Stunths tT pe. Date,and Duration of Eacht:

3 None December 7.

1978

25. If Shut Duan At End Of Report Period. Estimated Date of Startup:
26. Units in Test Status tPrior to Commercial O crationi:

Forecast Achiesed i

INITIA L CRITICA LITY INITIAL ELECTRICITY CO31%IERCI AL OPER ATION 4

\\

. ~.. -

4

~

s AVERAGE DAII.Y UNIT POWER LEVEL DOCKET NO. 50-333 JAFNPP WIT DATE

[

COMPLETED BY E. Zufelt TELEPHONE (315)342-3840 November 1978 MONTH DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe. Net)

(MWe. Net) 0 0

I g7

(

2 0'

33 0

3 0

19 0

4 0

20 0

5 0

23 0

6 0

22 0

7 0

n 0

8 0

24 0

9 0

3 0

10 0

26 0

11 0

27 0

f 12 0

23 0

13 0

29 0

I4 0

30 0

15 0

33 16 0

l SUbNARY: Second annual refueling and maintenance outage continued through the reporting period.

l l

r l

~.,

1 a.

m 5.e

,1 DOCKET NO. 50-333 UNITSIIUTDOWNS AND POWER REDUCTIONS UNIT NAME.IAFNPp DATE Dec. 9_

i979 COMPLETEn t1Y E. Zufelt REPORT MONTil November, 1978 TELEPil0NE [3151342-3840 i

'5 4 3 fi*

Cause & Correceive Licensee E*

g.,

e ce "L

3E g.5 ~4 a-Action to f'3 N' '-

DJte i

3$

r55 Event tr. T SN' 0 Preven Recurrence

$E 5

j;%g Report

  • F 6

\\

1 1

16 780916 S

720 C

2 NA NA NA Refueling Outage (Cumulative hours to date 1819.9) 1 2

3 4

F: Forced Reason:

Method:

Exhibit G Instructiims S: Scheduled A fquipment Failure (Explain) l-Manual for Preparaliim os' Data B-Maintenance of Test 2 Manual Scram.

Entry Sliccas fin I.ieensee C Refueling 3 Automatic Scram.

Event Report (1.1 RI file (NUREG.

D Regulatory Restriction 4-Oiher (Explain) 0161)

E Operator Training & license Examin i

F Administrative 5

Estabii ! - Same Source G-Operational Essur (Emplain) 19/77)

Il-Olher (Explain)

POWER AUT110RITY OF THE STATE OF NEW YORK-JAMES A. FIT PATRICK NUCLEAR POWER PLANT NARRATIVE SUhNARY OF OPERATING EXPERIENCE NOVEMBER 1978 The refueling, maintenance and modification outage that began on September 16, 1978 continued throughout the month of November.

Modification of Reactor Vessel Feedwater Noz:les, replacement of Feedwater Spargers, refueling and Local Leak Rate Testing of containment isolation valves have been completed.

Integrated Leak Rate Testing of the primary containment structure is in progress on November 30th.

Preparation for plant startup

1 scheduled for December 7th, is also in progress.

i

(

s l

\\

1 i

i e

L

Datos n comh, o

,19 79 l

JAMES A. FITZPATRICK NUCI. EAR POWER PLANT POWER AUTHORITY OF THE STATE OF NEU YORK REFUELING INFORMATION 1.

The date of the next scheduled refueling outage is March

,19 80 2.

The scheduled date for restart following refueling is May

,19 80 3.

Will refueling or resumption of operation thereafter require a technical specification change or other license amendment?

YES X If yes, describe in general what these will be.and go to question 5.

Reload may include pressurized 8XS Retrofit (P8X8R) Fuel NO If no, answer question 4.

4.

ANSWER ONLY IF ANSWER TO 3. ABOVE IS NO.

Has the reload fuel design and core configuration been reviewed by the Plant Safety Review committee to determine whether any unreviewed safety questions are associated e

with the core reload (Ref. 10 CFR Section 50.59)?

YES NO The next scheduled review date is

,19 5.

ANSWER ONLY IF ANSWER TO 3. AB0VE IS YES.

The scheduled date for submitting proposed licensing action and supporting information is Unknown

,19 6.

Answer the following important licensing considerations TES No s

a)

New fuel design?

N/A b)

New fuel supplier?

N/A c)

Are there any unreviewed design or performance analysis methods?

N/A

(

d)

Are there any new operating procedures?.

N/A e)

Other

/

X Specify:

Factors in addition to the possible use of P8X8R fuel Ere unknown at this time.

7.

There are normally 560 fuel assemblies in the core during operation, presently there are 560 in the core.

8.

a) There are 268 fuel assemblies of the licensed allowable 760 in the spent fuel pool.

b) An increase in the licensed storage capacity:

is not being contemplated at this time.

is being planned at this time for an additional fuel assemblies.

X has been requested for an additional _((8[_ fuel assemblies.

9.

Novemb'er

,19 31 is the last possible refueling date that can be projected at this time given the presently licensed spent fuel pool storage capac

1WER Alfil10RITY OF Tile STATE OF

'V YORK JAMES A. FITZPATRICK NUCLEAR POWest PLANT Safety Related Electrical 6 Mechanical Maintenance Summary November 1978 WORK REQUEST #

REPAIR DAT51 SYSTEM COMPONENT #

110W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME Il0URS 8 NOV 02 11393 N/A None Reactor Vessel Disassembled 1464 Reactor Vessel 14 NOV 02 12102 LLRT Excessive Seat Leakage Replaced Valve 30 02-RWR-403 19 WOV 02 12632 N/A Failure Indicating Switches Replaced Failed Components 10 Spare CRD Pl Coils 1 NOV 03 8651 VISUAL Limit Switch Arms Out of Repositioned, Limit Switch 2

Scram Disch.

Position Contact Arms Valve Under Piston Limit Switch (llCU 02-35) i

\\

2S OCf 03 8851 Simultaneous Failed Position Indication Replaced CRD Position Indication Coil 2

CR0 30-11 Full-In and Coil Position Full-Out Indication Indication 16 NOV 03 11661 N/A None Overhauled 10 CRD's 1439.S CRD Overhaul

")WER AUTil0RITY OF Tile STATE OF '~ 't YORK

~

JAMES A. FITZPATRICK NUCLEAR POWt..s PLANT Safety Related Electrical 6 Mechanical Maintenance Summary November 1978 Page 2 WORK REQUEST #

REPAIR DATE SYSTEM COMPONENT #

110W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME Il00RS 6 NOV 03 12884 Air Leaks Failed "0" Ring Seals Replaced Valve's."b"-Rings 1

26-03 6 10-07 Scram Solenoid Valves 18 NOV 03 12937 Stem Packing Failure Repacked Valve 1/2 46-27 Valve i.eak 03-111 16 NOV 03 12980 Frequent Leaking Seals Replaced ilCU Accumulator with Spare 32 IICU 06-15 liigh Water Unit Level Alarms Rebuilt Failed Accumulator 3 NOV 03 13176 Air I.eaks Bonnet Screws loose Tighten Flange Screws 1

26-03 4 i

35-31 Scram Pilot Solenoids

!! NOV 10 11971 Packing Leak Failed Packing Repacked Valve 20 10 MOV 27A

' 1 NOV 10 12068 LI.RT Excessive Seat Leakage Replace 2 Seat Rings, l.apped Disc, 70 10 MOV 31B Replaced Body to Bonnet Gaskets, Repar.ked Valve

" lWER AU1110RITY OF lilE STATE OF ' *1 YORK

.,AMES A. FITZPATRICK NUCLEAR POWt... PLANT Safety Related Electrical 6 Mechanical Maintenance Summary November 1978 Page 3 WORK REQUEST #

REPAIR DATE SYSTEM COMPONENT #

ll0W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME Il0VRS 4 NOV 10 12090 Strainer Shaft Bushing Worn Replaced Bushings 8

RIIR-55A Operation Difficult 13 NOV 10 12910 Packing Leak Packing Failure Repacked Valve 30 10 F0V 66A 11 NOV 10 12934 Valve Torqued None Reset Torque Switches 6

10 MOV 17 6 18 Out Before Shutting 16 NOV 10 12979 N/A None Changed Strainers 2

10-S-5A 6 h___

17 NOV 10 12992 Valve would Yoke Bushing Backed out of Tacked Yoke Bushing to Yoke 2

I 10 RilR 22D not Shut Valve Yoke 21 OCT 11

__ 11390 N/A None Performed ST-6E 12 El-24A 6 B 3 NOV 13 11936 I.LRT Excessive Seat 1.eakage 1,apped 6 Cleaned the Valve 157 RCIC 04

0WER Atfl110RITY OF Tile STATE OF

  • W YORK

~

.sAMES A. FITZPATRICK NUCLEAR P0lb.s PLANT Safety Related Electrical 6 Mechanical Maintenance Summary November 1978 Page 4 WORK REQUEST g REPAIR DATE SYSTEM 110W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME COMPONENT #

Il0URS 20 OCT 13 11937 LLRT Excessive Seat Leakage Replaced Disc, Gasket 6 Seat Ring -

72 RCIC 05 Lapped Valve 18 OCT 13 11997 Administra-Improper Motor Insulation Rewound Motor with Proper Insulation 10 HOV-15 tively 27 OCT-1*

11975 Visual Loose Wire in Breaker Taped Wire 2

14-P-1A 8 NOV 14 12105 Associated Seals Worn Changed Seals 23 14-A0V-13B SOV Did Not Work 30 OCT 75 13181 LLRT Excessive Seat Leakage Replaced Gasket, Piston Spring, 28 i

RBC-31 Cleaned Internals

\\

19 NOV 16 11806 N/A None Reinstalled Emergency Access Drywell 464 Emergency llatch Drywel1 Access llatch l

23 NOV 16 12672 LLRT Excessive Leakage Replace Drywell Dome Manway Cover 6

I X-4 1

^ ')WER Alfril0RITY OF Tile STATE OF ' "V YORK o AMES A. FITZPATRICK NUCLEAR POWu., PLANT Safety Related Electrical 6 Mechanical Maintenance Summary November 1978 Page 5 WORK REQUEST 4 REPAIR DATE SYSTEM il0W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME COMPONEKr #

110URS 18 OCT 20 11995 Administra-Improper Motor Insulation Rewound Motor with' Proper Insulation 5

MOV-94 tively 18 OCT 20 11996 Administra-Im1'doperMotorInsulatian Rewound Motor with Proper Insulation 5

MOV-82 tively 22 NOV 20 12661 Valve Wouldn't Solenoid Air Isolated Unisolated Solenoid Air 3

A0V-95 Operate 21 NOV 20 13187 N/A Cooler Failure Installed Mod F1-78-30 164 20-A0V-95 6 20-P-5A 6 B 9 NOV 23 8723 Improper Close Improper Adjustment of Adjusted Barrels for Connect Valve 6

g MOV-15 Indication Limitorque Barrels Position Indication 1

31 OCT 23 11517 Administra-Lights not Fed Thru 23A-F13 Completed Mod F1-76-94 1

IIPCI Graphic tively as Intended Display Lights 4 OCT 23 11935 LLRT Excessive Seat Leakage Lapped 6 Cleaned Valve 90 llPI-65

'24 OCT 23 13146 LLRT Excessive Seat Leakage Lapped Valve 80 llPI-Il I

' ~9WER AUTil0RITY OF Tile STATE OF ' "'i YORK

,,AMES A. FITZPATRICK NUCLEAR POE... PLANT Safety Related Electrical 6 'nechanical Maintenance Susunary November 1978 Page 6 REPAIR WORK REQUEST #

DATE SYSTEM COMPONENT #

110W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME Il0URS 7 OCT 27 12152 LI.RT Excessive Packing I.eakage Tighten Packing Glind 1

VB-3 19 OCT 27 12153 LLRT Excessive Packing Leakage Repacked VB-4, Adjusted VB-3 4

VB-3 4 4 7 NOV 27 13166 LLRT Excessive Seat Leakage 1,apped 6 Cleaned Valve 25 CNS-2A 3 NOV 27 13167 LLRT Excessive Seat Leakage Installed New Disc 6 Lapped 30 CNS-2C 23 OCT 27 13168 1.LRT Excessive Seat Leakage Lapped Valve 30 A0V-132B 22 OCT 27 13169 LI.RT Excessive Seat Leakage Lapped 6 Cleaned Valve 30 CNS-2D 9 NOV 27 13193 I.LRT Excessive Seat Leakage Lapped 6 Cleaned Valve 15 A0V-131A 14 NOV 29 8787 Visual Packing 1.eak Repacked Valve 8

A0V-80A

9 WER AUTil0RITY OF Tile STATE OF ! N YORK

~

.sAMES A. FITZPATRICK NUCLEAR POWh., PLANT Safety Related Electrical 6 Mechanical Maintenance Summary November 1978 Page 7 REPAIR WORI' REQUEST #

DATE SYSTEM 110W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME COMPONEffl' #

Il0URS 23 OCT 29 11922 1.LRT Excessive Seat Leakage 6 Lapped Valve, Repa'cked, Replaced 68 MOV-74 Motor Failed Pressure Seal, Rewound Motor 10 NOV 29 12014 ISI Indication in Weld Indication Removed 6 Weld Repaired 70.5 ll29-247 7 NOV 29 13113 Improper Incorrect Alignment Adjusted Operating Arm 1

A0V-86D Valve Position Indication 1 MOV 34 5576 Audio Piston Ring Leaking By Installed Ndw ting, Cleaned Cylinde:

24 NRV-Illa IS NOV 70 12985 Mod Did Not Overload out of adjustment Adjusted Overload 6 Linkage 4

I MOD-102B Operate 6 Fan 6 Bolt Binding on Linkage Wouldn't Start 31 OCT 71 12173 N/A None Scaled Electrical Penetrations in 5

Penetration East Tunnel Sleeves 28 OCT 71 12815 Breaker Improper Breaker Switching Replaced Failed Internal Components 20 INV-3B Tripped Operation

""0WER Alfill0RITY OF TIIE STATE OF ' W YORK

.AMES A. FITZPATRICK NUCLEAR POWu.. PLANT Safety Related Electrical 4 Mechanical Maintenance Summar:' November 1978 Page 8 REPAIR WORK REQUEST 4 DATE SYSTEM COMPONENT #

110W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME Il0URS 26 OCT 71 12820 N/A Demineralized Valve Dried out Motor Starters 4 Replaced 20 MCC-162 f. 143 Failed Spraying MCCs Control Voltage Transformer for 15-MOV-175B 2 NOV 71 12843 Breaker Continuing Problem From Replaced Failed Internal Components 30 INV-3B Tripped f Fus.

12815 (above)

Blew 15 NOV 72 12988 Fan Would not Pfotor was Single Phasing Adjusted Contacts and Contactor 4

FN-31A Start Assembly 28 OCT 72 13190 Visual Fan Belt Cracked in two Replace Fan' Belt 2

FN-46A Places 28 OCT 72 13191 Visual Loose Fan Belt Tighten Fan Belt 2

j FN-46C 20 OCT 76 13031 Visual Packing Leak Repacked Valve 6

FPS-122 f, 123 7 NOV 93 11757 N/A None Performed Preventive Itaintenance 250 EDG A f C 7 NOV 93 11758 N/A None Performed Preventive Maintenance 300 EDG B f D

70WER Alfril0RITY OF Tile STATE OF t'TV YORK

.AMES A. FITZPATRICK NUCLEAR POW.

PLANT Safety Related Electrical 6 Mechanical Maintenance Summary November 1978 Page 9 WORK REQUEST g REPAIR DATE SYSTEM ll0W DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME COMPONENT #

110URS 16 OCT P3 13129 Visual None Removed Bearing Retainer f Inspected 2

EDG D Shaft Governor 2 NOV 93 13172 N/A None Inspected Baffles 12 EDG A, B, C Fresh Water lleat Exchanger 10 OCT MISC 10998 N/A None Perform Operational Test of Ilours liyd rau li c flydraulic Snubbers 1isted Snubbers On WR 10997 16 NOV MISC 10999 N/A None Removed f Reinstalled Insulation 2308.5 Insulation for ISI i

16 NOV MISC 11000 N/A None Performed ISI Ilours ISI Not Yet Submitted By Vendor I

j, p.

+

JAttES A. FITZPATRICK NUCLEAR POWER rLANT Y

f:

Hafntenance Summary INSTRlRIENT 6 CONTROL 1978 Work Request #

Cause of Results of Action taken to Repair Date System Component f flow Detected Malfunction Malfunction Preclude Time Recurrence (llours) 11-6-78 02-3 12830 OPS Torus Drained Low Readings Filled Water Leg 7

02-3-LI-201A i

11-19-78 02 12890 IGC Broken T/C No Reading Replaced T/C 12 02-TE-112A 11-18-78 02-3 11931 OPS N/A Changed Recorder Speed For 36 02-3-LR-98 Sparger Work 11-24-78 02-3 12647 IGC Open/Short T/C No Reading Repaired T/C 24 02-3-TE-67A 11-15-78 03 12982 OPS Age Rod Block Replaced K23A/B 4

IU1CS 11-15-78 03 12983 OPS Drift Rod Block Adjusted SV 10 RSCS Power Supply 11-22-78 03 12643 N/A N/A N/A Check for SIL 20 RSCS 282 11-11-78 07 12931 '

OPS Op Amp Bad Downscale Replaced Op Amp 10 IIBI-D 11-16-78 07 12977 OPS Loose Connector Downscale Replaced Conn.

22 "A" SRM

~

s jar:ES A.

FITZPATRICK NUCLEAR POWER rIANT

~.

'ik Maintenance Summary 1

INMTilNFNT F. CONTROL

\\

1978 Work Request #

Cause of Results of Action taken to Repair Date System Component i llow Detected Halfunction Malfunction Preclude Time i

Recurrence (llours) l 11-16-78 07 13124 HOD.

N/A N/A N/A 420 Thennal Power I

Monitor F1-78-23 11-17-78 07 13109 OPS Loose Conn.

Eratic Readings Cleaned; Reass-6 IRM "F" embled 11-20-78 07 13110 OPS Bad Amp Low Readings fleplacedAmp 10 IRM "G" l

Recorder i

11-25-78 07 11873 N/A N/A N/A Replaced TIP 680 TIP Tubing Tubing 11-28-78 07 12712 OPS Loose End Conn.

Drift Tightened Conn.

3 SRM-D 11-3-78 08 12861 OPS Age /Use N/A Replaced Load 32 Load Cell Cell 11-6-78 11 12859 OPS N/A N/A N/A 1

11-LA-070 11-24-78 11 12660 OPS Line Plugged Ili Readings Blew Out Lines 8

11-LI-66 1

1

Jeu ES A.

FITZPATRICK NtJCI. EAR POWER cl. ANT

'il Maintenance Sunnary

~

INSTRINENT f, CONTROL 1978 Work Request I Cause of Results uf Action taken t o Repair Date System Component #

Ilow Detected Malfunction Halfunction Preclude Time 1

Recurrence (llours) 11-19-78 14 13091 OPS Loose Screws Air Laakage Tightened Screws 9

14-A0V-13A 11-25-78 20 12661 OPS Bad SOV Valve Does Not Replaced SOV 8

20-A0V-95 Operate N/A N/A N/A N/A 150 11-14-78 23 886 HOD F1-76-59 ISP-22 Age liard to Adj.

Replaced 14 11-14-78 23 12895 23-PS-85C 11-28-78 23 12686 OPS Torus Drained /

Low Readings ISP-24-2 8

23-LT-201C Refilled 11-14-78 24 12908 OPS Age /lise Air Leaks Replaced Reg.

18 Door Seals 11-27-78 27 11487 OPS Unknown liigh Readings ISP-30 8

27-MAZ-101A 11-10-78 29 11553 '

OPS Unknown 10% LS Did Not Found OK 2

29-A0V-86C Reset 11-10-78 29 11538 OPS Dirty Speed Slow to Close Replaced 2

29-A0V-86D Control S1ncr.

h Jar ES A. FITZPATRICK NilCI. EAR l'OWER rl. ANT

- /;

Maintenance Sununary INSTRIDiENT f, CONTROI.

1978 Work Request I cause of Results of Action taken to Repair Date System Component #

llow Detected Malfunction Malfunction Preclude Time Recurrence (llours) 11-11-78 29 12817 OPS Unknown Unknown None 1

29-A0V-86C 11-17-78 70 12987 OPS Binding Bad Bellows Replaced 6

70-H00-108/109 11-1-78 71 13199 OPS N/A N/A Dper. Error 6

A Batt Charger 11-10-78 93 12928 OPS Drift A/C Failed to Re-caled.

3 93-AC-A2 Start 11-22-78 93 11834 N/A N/A N/A Cals.

250 EDG-A,B,C 6 D

.