ML20071E461

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Feb 1983
ML20071E461
Person / Time
Site: FitzPatrick 
Issue date: 03/07/1983
From: Jackie Cook
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
Shared Package
ML20071E443 List:
References
NUDOCS 8303140227
Download: ML20071E461 (6)


Text

<

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE FEBRUARY, 1983 The unit operated at near full thermal power for the first twenty-four days of the reporting period. On 830225 the unit tripped due to procedural inadequacy while performing turbine control valve testing. The unit returned to service on 830226.

At the end of the reporting period the unit is operating at approximately 658 MWe.

1 i

l l

l 8303140227 830309 PDR ADOCK 05000333 R

PDR

-.y

OPERATING DATA REPORT DOCKET NO. _50-333 DATE _ MARCH 1983 COMPLETED BY

_J.

COOK TELEPHONE (315) 342-3840 OPERATING STATUS

1. Unit Name:

FITZPATRICK Notes 830201-830228

2. Reporting Period:
3. Licensed Thermal Power (MWt):

2436

4. Nameplate Rating (Gross MWe):

003

5. Design Electrical Rating (Net MWe):

821

6. Maximum Dependable Capacity (Gross MWe):

830 810

7. Maximum Dependable Capacity (Net MWe):
8. If Changes Occur in Capacity Ratings (Items Number 3 Throt.;h 7) Since Last Report, Give Reasons:

NONE NONE

9. Power Level To Which Restricted,If Any(Net MWe):
10. Reasons For Restrictions,If Any:

This Month Yr.-to.Date Cumulatise

11. Hours In Reporting Period 672 1416 66 ggt
12. Number Of Hours Reactor Was Critical 651.1 1110.5 47366.2 0

0 0

13. Reactor Reserve Shutdown flours
14. Hours Generator On-Line 646.6 1080.6 46095.8
15. Unit Reserve Shutdown Hours 0

0 0

16. Gross Thermal Energy Generated (MWH) 1513656 2402616 95926474
17. Gross Electrical Energy Generated (MWH) 512820 809700 33244480
18. Net Electrical Energy Generated (MWH) 496695 783710 31648095
19. Ur.it Senice Factor 96.2%

76.3%

69.3%

20. Unit Availability Factor 96.2%

76.3%

69.3%

21. Unit Capacity Factor (Using MDC Net) 91.3%

68.3%

62.7%

22. Unit Capacity Factor (Using DER Net) 90.0%

67.4%

57.9%-

23. Unit Forced Outage Rate 3.8%

23.7%

15.9%

24. Shutdowns Scheduled Over Next 6 Months (Type. Date,and Duration of Each):

Refuel outage scheduled to commence May 21, 1983 lasting approximately 75 days.

25. If Shut Down At End Of Report Period. Estimated Date of Startup:

'.. Units in Test Status (Prior to Commercial Operation):

Forecast Achiesed INITIA L CRITICA LITY INITIA L ELECTRICITY COMMERCIAL OPERATION

AVER AGE DAILY UNIT POWER LEVEL

.50-333 DOCKET NO.

UNIT _flTZPlsIR LC K.

MARCH 1983 _

DATE J. COOK COMPLETED BY T ELEPHONE (315) 342:3840 FEBRUARY 1983 gg3ng DAY AVERAGE DAILY POWER LEVEL DAY AVER AGE DAILY POWER LEVEL (MWe Net)

(MWe-Net) 795 738 37 796 792 is 2

718_

799 19 3

793 20 19 1 4

673 796 21 5

796 733 6

22 785 796 23 7

798 796 24 s

741 795 25 9

10 797 26 I

455 793 27 794 658 28 12 794 29 13 14 30 797 3r 15 796 16 2

SUMMARY

The FitzPatrick plant operated at near full thermal power for this reporting period with one outage on 820225 due to procedural inadequacy.

)

S

50-333 UNIT SilUTDOWNS AND POWER REDUCTIONS DOCKET NO.

UNIT N A3t E FITZPATRICK DATE MARCH 1983 COMPLETED IlY J. COOK REPORT MONTil FEBRUARY 1983

_ 315) 342-3840

(

TELEPilONE e.

E E

m

.$?

"s

$Yi licensee E r, j%

Cause & Correctiva No.

Date g

3g i

,3 g e Event

{?

c-3 Actsun to

$~

55g Repori a in U

!O Prevent Recurrente v

O 4

830225 F

20.9 8

3 N/A HA N/A inadequate turbine control valve test procedure i

I 2

3 4

F: Forced Reason:

Method:

Exlubit C -Instructions S: Scheduled A Equipment Failure. Explain) 1 Manual for Preparation of Data B Maintenance of Test 2 Manual Scram.

Entry Sheets for Licensee C Refueling 3 Automatic Scram.

Event Iteport (LElt) Fife INUREG-D Regu!atory Restriction 4-01her (Explain) 01611 E Operator Training & License Examination F Administra ise 5

r G Operational Error (Explain)

Estuba 1 Same Source Il Other ( E xplain)

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES - A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL a MECHANICA'_ MAINTENANCE

SUMMARY

FEBRUARY 1983 O 3 DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN 10 PRECLUDE RECURRENCE

'/2/83 88 16387 Operation of Worn Mechanical Leak-Replaced door latch.

24 CR-2 Crane age 2/3/81 46 19781 Pump would Overcurrent trip de-Adjusted overcurrent trip devices.

24 P-2B not start vices out of adjust-ment 1/13/33 93 18095 Visual Burned out lamp Replaced lamp.

1 ECPB 2/7/8 s 10 16210 N/A N/A Inspected valve - found eroded 12 RHR 14C disc nut - Replaced disc nut &

cotter pin.

1/18/ 33 70 18088 OPS Actuator arm out of Adjusted actuator arm.

16 MOD 108A adjustment causing no shut indication 2/16/ 33 10 18170 OPS Vibration due to flow Replaced cap screws & welded a 76 RHR 42B caused hanger cap keeper on.

screws to loosen 2/16/ 33 27 221502 OPS Worn actuator o-rings Replaced 0-rings.

18 A0V-129B 2/26/ 33 29 19850 OPS Position indication Readjusted switch.

16 AOV-36C switch out of adjust-ment l

2/23/ 83 24 16259 Visual Door latch linkage Straightened linkage.

6 i

EOD 1 & 2 bent by misuse 2/28/ 83 10 21644 Visual Worn packing Adjusted packing.

4 MOV-25A

s POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRlCK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

t&C MARCH 1983 WORK REQUEST #

CAUSE OF RESULTS OF ACTION TAKEN REPAIR DATE SYSTEM CTED COMPONENT #

MALFUNCTION MALFUNCTION TO PRECLUDE TIME RECURRENCE HOURS 2/10 07 19860 OPS Bk pen hanging up Black pen st;ckint Check clearance 2

PR-46B on red pen and calibrated 2/25 07 2165i OPS Old age indicator lights Replaced bulbs 9

TIP-A,B,C,D not working 2/07 10 19798 OPS Out of calibration Did not alarm Adjusted gain for 12 LS-103 upon draining control unit i

2/14 10 21507 OPS Defective relay Indicates dry Replaced relay and 14 LIS-104 ca l i b ra ted 2/16 17 19655 OPS Defective switch Source will not Replaced parts and 89 Vent Mon and drive motor insert adjusted 2/23 17 20541 JIC Defective connector inspect and repair Replaced connector 7

RM-150A J1 input con J1 2/10 20 19785 OPS Clutch slipping Black pen broke Adjusted clutch, 7

F R-528 on recorder zero & span 2/15 20

__9943 OPS Change in volt from Doesn't shut on Adjusted to new 30 1

A0V-95 transmitter lo level in procedure 2/08 76 19766 OPS De fec t i ve 15-250VDC Alarms spuriously -Replaced converter 8

Z-2 converter