SEABROOK 5TATION

% OHies:

1671 Worcesser mood Fmndnoham, me chu.en 01701 Pub 5c Son 4ce of New HompeNro (617) - 872 - 8100 February 24, 1983 SBN-478 T.F. B7.1.2 United States Nuclear Regulatory Commission Washing ton, D. C. 20555 Attention:

Mr. George W. Knighton, Chief Licensing Branch No. 3 Division of Licensing

References:

(a) Construction Permits CPPR-135 and CPPR-136, Docket Nos. 50-443 and 50-444 (b) PSNH Letter, dated February 2,1983, "Open Item Response:

(SRP 9.5.4; Power Systems Branch)," J. DeVincentis to C.

W. Knighton

Subject:

Open Item Response:

(SRP 9.5.4; Power Systems Branch)

Dear Sir:

In response to the open item regarding protection of the Fuel Oil Transfer Pump from damage due to inadvertent actuation of the Fire Protection System in the Fuel Oil Storage Tank Room, we have enclosed a commitment to replace the open heads of the Deluge System with closed, low-temperature spray heads.

Please note that the enclosed commitment supercedes that tendered in Reference (b) and will be incorporated in OL Application Amendment 49.

Very truly yours, YANKEE ATOMIC ELECTRIC COMPANY J. DeVincentis Project Manager ALL/fsf Atomic Safety and Licensing Board Service List cc:

I 8303010578 830224 PDRADOCK05000g F

1000 Elm St.. P.O. Box 330, Manchester. NH O3105 Telephone (603) 6694000 TWX 7102207595

L ASLB SERVICE LIST L

Philip Ahrens, Esquire Assistant Attorney General Department of the Attorney General Augusta, ME 04333 Representative Beverly Hollingworth Coastal Chamber of Commerce 209 Winnacunnet Road Hampton, NH 03842 4

William S. Jordan, III, Esquire Harmon & Weiss 1725 I Street, N.W.

Suite 506 Washington, DC 20006 i

j E. Tupper Kinder, Esquire Assistant Attorney General Office of the Attorney General-208 Sts;e House Annex Concord, NH 03301 Robert A. Backus, Esquire 116 Lowell Street

}

P.O. Box 516 Manchester, NH 03105 l

Edward J. McDermott, Esquire Sanders and McDermott Professional Association 408 Laf ayette Road Hampton, NH 03842 Jo Ann Shotwell, Esquire Assistant Attorney General Environmental Protection dureau Department of the Attorney General One Ashburton Place, 19th Floor Boston, MA 02108 s

5

, -. -, - - - -. -, - -,. -,. - -.,. - - + - - - -

_-.,,nn.,.-.n-~,,,--n,-,...n.

-nn

,--nn_,--,,,,,-,_n s.n--,

-nw.

---,-r.----,--nn,

s-43 Based on discussions with members of the Staff in meetings conducted February

-23,.1983, we are modifying our response relative to the protection of the - Fuel.

Oil-Transfer Pump from damage due to inadvertent actuation'of the Fire Protection System in the Fuel Oil Storage Tank Room.

The present design of 'the Fire Protection Deluge Spray System for the Fuel Oil Storage Tank Rooms' consists of redundant trains of open head, dry pipe deluge systems. Seismically qualified deluge valves, located outside the rooms are-actuated by heat and smoke sensors located within the rooms..The deluge piping within the room is all seismically designed.

To preclude damage to safety-related equipment within these rooms due to inadvertent actuation (i.e., seismic event) of the deluge system, the open heads of the deluge system will be replaced with closed-head, low temperature (1350F) spray heads. Although not specifically qualified as Seismic Category 1, this type head has been used extensively in both nuclear and non-nuclear facilities and has demonstrated its ability to withstand actual seismic events without failure or inadvertent actuation.

This proposed modification has been discussed with Mr. John Stang of the Staff (CMEB) and has been found acceptable from a Fire Protection standpoint.

This commitment supercedes commitments made in Reference (b).

>