Text
_..
VERMONT YANKEE
. NUCLEIR POWER CORPORATION
- MD.
P.O. Box 157, Governor Hunt Road
( %xy.
Yq 'N / ')
W vernon, vermont 05354-0157 d-'
/
(802) 257-7711 m.
,s May 10,1994 VY-RCE-94-012 BVY 94-50 U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Attn:
Document Control Desk
Reference:
a)
License No. DPR-28 (Docket No. 50-271)
Dear Sir:
Submitted herewith is the Monthly Statistical Report for the Vennont i
Yankee Nuclear Power Station for the month of April.1994.
Very truly yours, 2
Vennont Yankee Nuclear Power Corp.
N i.
V-y 1-Donald A. Reid Vice President, Operations cc:
USNRC, Region I USNRC Resident inspector, VYNPS
.c 9405200290 940430 Y
I PDR ADOCK 05000271
- l#
'g '
.R PDR W OUUUd
1 VERMONT YANKEE NUCLEAR POWER STATION MONTIIIJ STATISTICAL REPOl(T 94-04 FOlt TIIE MONTil OF APRIL 1994 DP 0411 Rev. 5 Page 1 ofI
w OPERATING DATA REPORT F
DOCKET NO 50-271 DATE 940510 COMPLETED BY G.A. WALLIN TELEPHONE (802)257-7711 OPERATTELETATHS 1.
Unit Name:
yfrmont YalDlLQ2 2.
Reporting Period:
April NOTES:
- 3. Licensed Thermal Power (MWt):1593
- 4. Nameplate Rating (Gross MWe) : 51Q 5.
Design Electrical Rating (Net MWe) :
114 (oc) 504(cc) l
- 6. Maximum Dependable Capacity (Gross MWe) :
111 7.-Maximum Dependable Capacity (Net MWe):
1Q4 8.
If changes, occur in capacity ratings (Items Number 3 through 7) since last report, give reasons:
N/A t
9.
Power level to which restricted, if any(Net MWe):
N/A
- 10. Reasons for restrictions, if any:
N/A This Month Yr-to-Date Cumulative
- 11. Hours in Reporting Period 719.00 2879.00 187703.00 a
- 12. Number Of Hours Reactor was Critical 678.12 2838.12 154055.53
- 13. Reactor Reserve Shutdown Hours 0.00 0.00 0.00
- 14. Hours Generator On-Line 667.82 2822 17 150937.79
- 15. Unit Reserve Shutdown Hours 0.00 0.00 0.00
- 16. Gross Thermal Energy Generated (MWH) 1955857.00_
4455498.00 225161169.50 17 Gross Electrical Energy Generated 357363.00 1509118.00 75028500.00 i
- 18. Net Electrical Energy Generated (MWH) 343697.00
_1451057.00 71298081.00
- 19. Unit Service Factor 92.88 98.03 79 62
'2 0. Unit Availability Factor 92.88 98.03 79.69
- 21. Unit Capacity Factor (Using MDC Net) 94.85 100.00 74.69
- 22. Unit Capacity Factor (UJing DER Net) 133.00 98.06 73.23
- 23. Unit Forced Outage Rate 7.12 1.97-5.12
- 24. Shutdowns scheduled over next 6 months (Type, Date, and Duration of Each:
N/A 4
- 25. If shut down at end of report period, estimated date of startup:N/A
- 26. Units In Test Status (prior to commercial operation): N/A Forecast Achieved
,]
INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION VYDPF 0411.01 DP 0411 Rev. 5 Page 1 of 1 RT No. 13.F01.19F
. ~. _ _..
_.m..m__.-.__
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 50-'271 UNIT Vermont Yankee DATE 240510 COMPLETED BY G.A.
WALLIN TELEPHONE
_(802)257-7711 MONTH Apr,il__
l i
DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL I
(MWe-Net)
(MWe-Net) l 1.
519 17, 520 2.
519 18.
520
- 3.
496 19.
520 4.
518 20.
520 5.
518 21.
520 6.
517 22.
520 7.
517 23.
520 8.
51.&
24.
519 9.
518 25.
520 10.
29 26.
519 11.
0 27, 520 1
12.
308 28.
519 l
13, 516 29.
518 14, 518 30.
519 15.
520 31.
16, 52.0
- 23 hour day INSTRUCTIONS On this format, list the average daily unit power level in MWE-Net for each day in the reporting month.
Compute to the nearest whole megawatt.
VYDPF 0411.02 DP 0411 Rev. 5 Page 1 of 1 RT No. 13 F01.18V 1
.,,.. -. ~.. -.. _., _.. -,.. -.... _ _. _ _. _.. _. _.. -,. - - -
,- I
~
- l UNIT SHUTDOWNS AND POWER REDUCTIONS f
REPORT MONTH APRIL DOCKET NO 50-271 UNIT NAME Vermont Yankee F
DATE 940510 4
1 COMPLETED BY G.A. Wallin TELEPHONE (802)257-7711 1
2 3
4 5
4 No.
Date Type Duration Reason Method of License System Component Cause and Corrective E
(hours)
Shutting Event Code Code Action to Prevent i
Down Report #
Recurrence Reactor 94-04 940410 F
51.18 A
3 94-04 HA VALVEX "C" moisuture separator high level.
i Turbine tripped and j
a reactor scram.
I Replaced a faulty level cont]oller.
}
1 F: Forced 2 Reason:
3 Method:
4 Exhibit G-Jnstructions S: Scheduled A-Equipment Failure (Explain) 1 - Manual for Preparacion of Data B-Maintenance or Test 2 - Manual Scram Entry Sheets for License j
C-Refueling 3 - Automatic Scram Event Report (LER) File
[
D-Regulatory. Restriction 4 - Other (Explain)
E-Operator Training and l
License Examination 5 Exhibit I - Same Source
.VYDPF 0411.03 F-Administrative.
DP 0411 Rev. 5 G-Operational Error (Explain) f Page 1 of 1 H-(Explain) j s
i 1
,y-
~ -. -. -..
DOCKET'NO. 50-271
.DATE 230510 d
COMPLETED BY G.A. WALLIN TELEPHONE (802)257-7711
[
REPORT MONTH April
- SJJMMARY OF OPEBATING EXPEFJEE.CfES Highlighte Vermont Yankee operated at 92.2% of rated thermal power for the' month.
' Gross electrical generation was 357.363 MWHe or 92.0% design electrical capacity.
i Operating Summary i
-The following is a chronological description of plant operations including other pertinent items of interest for the month:
At the beginning of the reporting period the plant was operating at 99.9%
of rated thermal power.
940410 At 0122 hours0.00141 days <br />0.0339 hours <br />2.017196e-4 weeks <br />4.6421e-5 months <br />, turbine tripped and reactor scrammed, caused by a high level signal in the "C" moisture separator.
(See Unit 4
Shutdowns and Power Reductions) 940411 At 1815 hours0.021 days <br />0.504 hours <br />0.003 weeks <br />6.906075e-4 months <br />, the reactor was critical following repairs; 940412 At 0433 hours0.00501 days <br />0.12 hours <br />7.159392e-4 weeks <br />1.647565e-4 months <br />, the turbine-generator was phased to the grid, and a return to full power was initiated.
3
-f
.i i
l 1
i At the end of the reporting period the plant was operating at 99.9% of.
rated thermal power.
VYDPF 0411.-04 DP 0411 Rev. 5
)
Page 1 of 1 RT No. 13.F01.18X
. ~
-