ML20070R316
| ML20070R316 | |
| Person / Time | |
|---|---|
| Site: | Surry |
| Issue date: | 12/15/1982 |
| From: | VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.) |
| To: | |
| Shared Package | |
| ML20070R302 | List: |
| References | |
| NUDOCS 8301270413 | |
| Download: ML20070R316 (1) | |
Text
..
CORRECTED COPY *
' FACILITY CHANGES THAT DID NOT REQUIPI NRC APPROVAL
('
0"lTOBER, 1982 Unit
. DC SI-05 Fuel Buildir.g Television Monitoring System 1&2 This design. change 5c;alled two closed circuit television cameras in the Fuel Building. 'This system would enable the-shif t supervisor in the control room to monito: activity in the Fuel Building.
SUMMARY
OF SAFETY ANALYSIS Installation of a closed circuit television system does not affect the operation of any safety related equipment.
DC 81-46 RWST Narrow Range Level Monitoring System 1*
This design change replaced the existing non-safety related RWST level switches with a non-safety related RWST Narrew Range Level Monitoring, System. The new system monitors the span just below the dome bend line and the bottom of the overflow line. This change will aid the operators in maintaining the RWST within
(-
"lechnical Specifications.
SUMMARY
OF CAFETY ANALYSIS This modification doer not affect system operations or the operation of the RWST. The margin of safety is incrkased by alerting the operator to a potential violation of the Technical Specifications.
DC 82-17 Auxiliary Feedwater Motor Driven Pump Bypass lodication 1
This design change modified the Auxiliary Feedwater Motor Driven. Pump Circuitry so that the green indicating light located on the benchboard in the' Main Control Room is on when the pumps are locked out. Also, the Auxiliary Feed-water' Pump overload trip annunciator was modified to include a pump lockout condition.
SUrtMARY OF SAFETY ANALYSIS The implementation of the Auxiliary Feedwater Motor Driven Pun.p bypass indication package does not affect the operation of any safety-related equipment. This modification will
~
provide the operator with indication and alarm when the pumps are locked-out or taken out of service in the pull-
. p( y to-lock position.
4
~
8301270413'821215
14 r---.
e
+ -,
..y a
w
.e a
g-
---2
-w e
-.y
,w
.