VIRGINIA ELECTRIC AND PO'm*ER COMPAhi SURRY PO*a'ER STATION MONTELY OPERAnNG REPORT P2 PORT NO. 82-13 f

APPROVED BY:

b JW STATION MANAGER (j;

8301270408 821215 PDR ADOCK 05000200

, R PDR

~

y e

i

' Section Page Operating Data Report Uni fl 1

- ([1.

Unit #2 2

Operating-Data Report Unit Shutdowns and Power Reductions - Unit #1 3

Unit Shutdowns and Power Reductions - Unit #2 5

Load Reductions Due to Envi-testrictions - Unit fl 6

Load Reductions Due to Eny:-

2st ricticns

' - i ^2 Average Daily Unit Power Leve.

1 Average Daily Unit Power Level - Unit F2 9

10 Summary of Operating Experience Amendments to Facility License or Technic?. Specifications 13 1

Facility Changes that-did not r, quire NRC Approval (Corrected Oct. copy) 14 Facility Changes Requiring NRC Approva' 15 Facility Changes That Did Not Require KRC Approval 16 Tests and Experiments Requiring NRC Apprevtl 17

(

Tests and Experiments That Did Not Require NRC Approval 17 Other Changes. Tests and Experiments ig Chemistry Report 19 Description of All Instances Where Thermal Discharge Limits 20

- Were Exceeded Fuel Handling 21 Procedure Revisions That Changed the Operating Mode Described in 22 the FSAR Description of Periodic Tests Which Were Not Completed Within the 23 Time Limits Specified in Technical Specifications Inservice Inspection 24 Reportable Occurrences Pertaining to Any Outage or Power Reductions 25 Maintenance of Saf ety Related Systems During Outage or Reduced Power 26 Periods - Unit #1 - Mechanical Maintenance Maintenance of Safety Related Systems During Outage or Reduced Power 28 L('l Periods - Unit #2 - Mechanical Maintenance

(,)

u.

  • -4 s.,.. -,..

..r.g 3

.y

.s-11

se

'Section-M (C

Maintenance of Safety Related Syste:ns During Outage or Reduced Power 29 Periods - Unit #1 - Electrical Maintenance Maintenance of Safety Related Systems During Outage or Reduced Power 31 Periods - Unit #2 - Electrical Maintenance Maintenance of Safety Related Systems During Outage or Reduced Power 32 Periods - Unit #1 - Instrument Maintenance Maintenance of Safety'Relata.d Systems During Outage or Reduced Power 34 Periods - Unit #2 - Instrument Maintenance 36 Health Physics Summary

- Procedure Deviations reviewed by Station Nuclear Safety and 37 Operating Committee af ter Time Limits Specified in T. S.

M

e

;.h, e, -.,. e.s c.e.c.. c e.

a e

~

..sw

.o.

Ct"CETT i:C. 50-2M T4TF 03 070 82 CfSPLYTFT ?! VIVI @ JONES TRL FPEr CF 804-357-?:84-

~

.^Pt5("it.2'STATUF

-T.

UVI: h4VE SUREY Uill: 1 I,2. h EP& l.1 Z:.

PERIG..

-110182 Et ?130E2 n,

I.v, :

c.3 r

.. 4 4 l------------------------l

~.i -.. c.r. A.. L

.r,,... E

.3.., )

4.- 1. A v? !L A Z ; LATI:1G ' 2E.' SR '.lk'F )

847.5 ~\\NG"EF l^

5. :.iSI i. ELECTRIC AL RAT::13 a. AT Nk =)

788

6. - V4XTVUt D.:PEl :AELT CAP ACI."Y L CECSS h'E)

P11 7

YAXIKU.4 %KPEl.CAFLE CAPACITY.RFT.L'k'T)

.775 8.

F Ch AGEF CCCUR Zii CAPACI"Y RATII;GE NJA lI*I%S 3 TER& UGH 7) FiliCE -LlST

-REPGRT. GIVE REASCOS^

L9. PCOh IRVEL 70 k'EICH RESTRICTED, IF ANY ll/ A (h ?!- Wr)

10..hE ASMS F6R REETRICTIONE, IF A::Y

!!/A TEIS NCNTE YR-TC-DATE CU.t'UL A":Vi 11.-H&URS Ih REPCE"IIlG PNRICD 720.0 8:16.0

'87t44.0

12. -NUVEER TF ECURS REACTC R L'AS CRITICAL 684.0 71?3.2 53167.7 13.~hiACTCE RFSEEVE-FRUTDCh'N HOURS 33.7 33.7

-3765.2

14. HGURS. ENERATOR Cli-LINT 667.5 7035.9 52110.7 i

'U'eIT RESERVE SHU."DCl!N ECURS 0.0

'O.?

3736.2 JRGSS ZaERMAL ENERGY GENERATED (Mk'E )

1515345.7 16561365.0 120S14431.4 2.

17. CROSS ' EL?.CTRICAL ^ ENERGY GENER.tTED (yk'F )

482550.0 5224670.0

?9043883.2 19, ' NET' ELECTRICAL ENERGY SENERATJ: (MWE) 456878.0 4949682.0

?'026916.0

19. UNIT SERVICE FACTCR 92.7 e/o 87.8 e l.
  • 59.8 ele
20. UhZT A?AILABILITY FACT &R 92.7 */*

87.8 ele 64.1 e/o

21. UNI: CAPACITY FACTOR iUSING MCC NET) 81.S.*/c 79.7 ele 54.8 */*
22. UNIT JAPACITY FACTOR (USINC Chh NET) 80.5 e/o 78.4 olo 53.9 */*

23, UXIT ECRCED-CUTAGE RATE 7.3 */*

4.4 */*

23.2 */o

'?4.

SHUT:(W!iS SCEEDULED~CVER NEXT 6^NGtlTES

.2-1-83 74 DAYS-REFUELING-10YR.

(TYPi,tATF,AND DURATION CF EACP)

-25. IF SEUT C&k'N AT ENT GF REP 0RT PERIG:,

26.'iETZYATE DATE CF ETARTUP UAIIS IN TFST STATUS FCRECAS" ACFIEV75 LPRIOR TG CON!4EECIAL 'CPERATION)

TNITIAL CRITICALI"Y.

IhITIAL FLECTRICITY CCWi*?.RCIA: CPERA"Ich m

1 L

7 i:

..- r.n,.e.rl.,

.r.a.n,.. E.v..g.i; Ra e

.. r*

s. CX.re o.e.

r

.e a.,...

xe, a

N

' D A T E 0 6 [?. C 5 2 C6" FIT:XD bY VIVIAN JONES XEiPECNT 604-357-31A4

... h *s s. s.u r., - r.t r

.e,r.,r., e e

eJ

  • snsus 1.' loh t: in ( VF -

SURRY Lbi: 2

2. hEFCRTEl,0 E -:hiGD 110162 TC 113:E2

,,,4 41 l------~~ ---------------l f....,,, )

L t.,1 \\ S.,.

,,r.. r. a... A L.

Pl..,,.. r.

-r.

.a 2

tv n.

a s.

4. ' N 2 \\ *:FEATE EATIN2 rJKGSS NWF) 647.5 l.7C 57' l

5.

.r r.e. <l.

r. r r.e. s,'.e...c n.,u sir.,r r

(.x. 7 % *)

766 a

. nv

6. : FAX E VUV DEFFNCABLE-CA PACITY 'GRGSS !n!E) 81 7.N4XIVUX DEFEN:AELE CAPACI:y (i;F Nk'X )

775

6. 'ZF - CE ANSFS CCCUR IN CAPACITY RATI!!GS C/A i?T W? :ERCUGF 7) SINCE LAS:

RF F., F 7, GIVE LHEAS' tis

9. FCW'h 'FVEL TC WEICE RFSTRICTEi. IF ANY li/A (NE7.4FI)
10. RE45GNS FCR RES:EIC:IGNS. IF ANY N/A THIS VCt;"E YR-:C-DA:n CUNUL ATIY?
11. HC UR' iii REPChTING PERICD 720.0 6016.0.

84024.0

(

2. h0V5ER GF HCURS REAC:CR WAS CRITICAL 720.0 7447.8 52308.5

' 13. RL ACICR RESERVE SEU:DGn'N ACURS 0.0 0.0 0.0

'14. ECUR' JENERA:0R GN-LI!JE 720.0 7374.4 51486.1

15. UNI hrSERVE SEU DOWN ECURE 0.0 0.0 0.0.
16..GECSS TEERNAL ENERGY GENERA:EDNVE) 1751066.6 17092014.2 120360360.1
17. GhGSS ElhC:hICAL ThnhGY GEAFRA:ED t !.VE )

575765.0 552665:.0 39203829.0 18.,hET'ICL.~ EICAL Ei.EEGY GENFRA"Ei 'VVE) 546960.0 5227572.0' 371562S7.0

.19. UNI: ElRVICi FACTCR

.300.0 */*

92.0 */*

63.3 */*

20. UNIT ^ AVAILABILITY FAC:CR 100.0 *J*

92.0 */*

61.3 */*

23. UNEZ CAPACITY FAC:CR (USING

'.*DC liET) 95.0 */*

84.1 *J*

57.1 *)*

22. UhZZ CAFACITY FAC 6h (UcING DER NET) 96.4 */*

82.6 */*

56.1 */*

-23. UNIT F hCET CU:ACT RA:h' O.0 */*

2.5 */*

15.5 *Je

24. SEUTCCVNF SCHEL;ULED C7FR NEX 6 Pril:?S F A L L *.' 2 INT. - CEC. 7,, 1962-8 DAYE

.(

YFi,[47E.AKD CURATICH CF 7 ACE)

N

25. IF SEUT DCd" A EriG OF REPCE: FFRIOD.

AFi1YA7F DATE CF STARTUP

26. Ui/ZTC IN TES: St.t:US FC-RECAFT ACEZEVE:

(P5ICR ZG C 'V','EhCIAL CPEEATICN) r r,r y. r w.c.. - c, ?,r v f.

.14. - e e M 4.-

6e e eb MAde e e a. L' s. (..F *

  • D. ?
  • 7 t'* V

. I.AF.? 8r.? d f r

s t-usss e

nu s f... r,. -.'.. v a r.losnu L l'.t. h.s a,r b s 'r e

n s

h 2

i is..

<E.

_--ms

.._,m m__

.. ~ __...

.--n..

y

' [',

R, -

' W-.

7

=

r, IDOCKIfl NO.

50-280' UNIT SilUTl)OS"NS AND POWER REDUC 110NS UNIT NAME Surry 1 DATE 12-07d 2 HEPORT MONTig November, 1982 COMPLE1 Ell ity ' Vivian II. JQngs I"

'IELEPilONE _ (804) "to-3tg4x477 l

{

.l i

1 O

c

!E 3

$ Y ~4 License:

Eg

  • 4 Cause & Concciive No.

OJte

~$

k j$$

' Event

]

3 Attiun to C

. Report #

v1 O V

Pssvent Recustente

$3

= 83 b

}

l 5

l 82-27 11-04-82 F

41.3 A

3 82-110/03L-0 RC

' FUEL XX Loss of "A" Main transformer causing

)

generator trip. Due to initiatics, l

of fire water spray down of trans-former causing a ground fault.

t to 82-28 11-18-82 F

1.5 A

1 82-111/03L-0 RB XXXXXX Generator taken off line to remove 82-112/03L-0 PC PUMP XX disconnect G105 from service due to overheating.

62-29 11-19-82 F

f'. 0 A

1 Generator output reduced to 600 MW due to disconnect G108 overheating.

I I

2 3

4 12: Fmced Reason:

Melhmt:

Exhibit G. Insanectisms l

S: Sdwduled A Equipment Failure (Emplain) 1-Manual fo, recpasation of I)aia Il Maintenance or Test 2 ManualScram.

Entry Sheces fin Licemcc C Refueling 3 Automatic Sciam.

liveni Repose Il 1:R) l'ile INililln D Itegulaiosy Restoiction 4-Othes (linplain) 0161) li Operator Itainmg & License Examination F. Ad nu msit ati-e 5

I:thilos I Same Source G Ope atiimal Einn (Explain) l*3/77)

Il-Othes (E xplain)

7 l

/D Q,

UNIT SilUTDOWNS' AND POWER REDUCTIONS DOCKETNO. 50-280

. UNIT NAME h e rv i DA1E. I 2-O'7-37 MEPORT MONTIl November, 1982 COMPLE1ED nY Vivian II. Junge T ELErito!IE (804) 1s 7-a l sicx4 7 7.

w.

5

~

w

.$E 3

y $'3 Elcensee E e, Cause & Cosacciive No.

Date

.E s &

Event sT T

Aiitun so T. :

3 a f'

,S-3my R.po,i.

so 3v

.ie i,.v.ni R.cu,,.nc.

c5 82-30 11-23-82 F

0.0 A-1 Generator output reduced to'600 MW due co disconnect G108 overheatfag.

82-31 11-29-82 F

9.7 A

3 82-117/03L-0 RC Fl'EL XX Reactor trip due to "A" Reactor "oolant putep. loss of pump was caused by a relay failure (33XC V590) while performing PT-8.3A.

+

3 4

I 1

12: Fenced Reason:

Method:

Eminhis G-Instructhms S: Scheduled A Equipment Failure (Explain) 1 Manual for Pseparasiu.i of Data ll Maintenance ni Test 2 Manual Scrain.

Entry Shecis fin Licensee C. Refueling 3 Automatic Scsaan.

Event Repost (l.ER) File INilRI G-D-Regulatuiy Resiniction 4 Other (Explain) 0161)

E Opesains Training & Eicense Examination F. Adnunisis ative 5

G Ope ational Errus (Emplein)

Eshihis I-Same Source i'8/77)

Il-Othc (Explain)

F n-f.

P.

50-281

. UNIT SilUTl) OWNS AND POWER REDUCTIONS DOCKET NO..Surry 11 UNIT NAME IIA 1E 12-07.-32 REPORT MONTil November, 1982 COMPLETEI) isY laivtan H. Jones 1ELErilONE ' (804) 1s7-1111/x477 3

W.

I?

's EA Licensee Ew Cause A s 'urvective b'1, a

No.

Date

{

3g j{

jg&

. Evens ai Action so H

c5 E E'

5 if, c:

Repost #

Ei0 N

Peevent Reentence 5

u c

6 82-39 11-27-82 S

0.0 H

I Reduced power to load follow on orders of the system operator.

Ut I.

1 I

2 3

4 F: Forced Reason:

Methmt:

Exhibii G. Instrucihms S: Scheduled A.Equipmens Failure (Explain) l-Manual fu, Pseparation of I)ata II. Maintenance of Test

2. Manual Scram.

Em.y Sheets feu I.icensee C. Refueling

3. Automatic Scram.

Even Repose G.l:R)l'ile (NilRI G.

Dellegulaimy Restsiction 4.Other (E mplain)

-0161)-

E Opesaim. Trainmg & License Examinailon F.Adnunnisative 5

G.Opesaiional Eesus (Explain)

Eshibii I. Same Sousu l'8/77) ll Othes (E alilam)

f-LOAD FDUCTIONS DUE TO D;VIROD2NTAL F ST7ICTIONS UNIT NO.1 MONTF.: November, 1982

. 1 DATE T!!E

. HOURS LOAD, L' RIDUCTIONS, ifa' Wd RIASON NONE DURING THIS REPORTING Pr,RIOD.

4 9

e 4

8 i

l

~6 e

b x0 Nrm.rTgTu.

===ene q

Y x.s a

m ns~-

- -'=

4

c' LOAD REDUCTIONS DUE TO ENVIRONMENTAL RESTRICTIONS UNIT NO. 2 MONTH: November, 1962 i

DATE TILE HOURS LOAD, W REDUCTIONS, W WH REASON NONE DURING THIS REPOTTING PERIOD.

( *-.,

6 MONTHLY TOTAL 7

u_

ff

.r.= gs..y *=

.t e., e :4..

~

e'

. Lp u..= se

.s;py. r,

.T.

s.,A.P. **

e,,<.

d e.e ps CcrcLFT7f "Y VIVIAN 2. JONES

.c

,.....,.,...,.,.Yb..,.P._...n

- ~.?

i........1,

.n-?

n z.

s. ;. --

4' ? V 7 # :

56" AilDF5 -. 5 2 t.. :h w'.T

." n* *.*. Y r*'

  • k*.S.'a'

.?. "..T '.

n

.,..?R.f *,r.** '- *

  • T. Y

.D.*. L

  • 3* C..

f.t* "..Y.T.

i SAY_

- ( L'L'X - !,*E T )

. /Y

.T? -k?2 )

1 742.3 26 74u.2 2

741.a 17 653.5 3

740.7 18 329.3 4

601.1 19 694.3 5

0.0 20 599.0 6

104.9 21 737.9 e5..

s..a.e r

a s.

s 8-7?4.5 23 7?1.5 9

737.8 24 592.0 10 741.0 25 738.8 11

-742.2 26 740.6 12 745.3 27

~44.8 13 745.2 28-743.8

'14 745.2 29 361.4 15 743.4

?O 304.*

C4ILY UNIT PGs'ER LE"iL FORT INSTRUCTIONS

-00 THIS FORY, L:ST TEE AVERAGE CAILY UNIT POWER LEVEL IN NVE-RET FGh FAC? SAY IN TEE h5ECETihG NCI.TE. THESF FIGURFE L':LL BF USL. TG PLCT A GRAPH FCR FACE REPCRT-TR'i VCNTE. NCTE ZEAT BY USING PAXINUV [FPEN:ABLE CAPACITY FCR THE NET ELECTRICAL E AZE1C CE THE UN:7,. THERE L'AY BE CCCASICNS VEEN TEE DA:LY A;*VEAGE ?OVFR XXCEFDS TFV 100 */* L:RE (GE THE RESTRICTRE PCVER LEV?L L:hn). TN SUCE CASES, TEK GTRAGE \\

DAILY U3i: PGVEh CUTPUT SEXETIF=CULD LE TCGTHCTED TG EXPLA:N TEF AP*AhXil? 'NC A L Y. l 1

k..*

8

e--

t-I.

T CCFFT *. f.

50-292 e b.......

-+

v v..,

,. r. :..

'ATY 12-2~67 l

c s.. F r..,., r.y VIVIAN H. JONES e a.u JVFFACy.'l7:Y U:l.'T D"V=F i=77.'

w YCSTF:

/,f ? % 5 7 F '82 A7EF GT Z A:LY - PCs =R L77EL 4"7CA.?? t/ZLZ ?6VVR CFVFL TAY~

(NVF-NET)

DAY

( A:VT-CT) 1 754.4 26 759.6 2

755.8 17 755.8 3

761.6 18 756.0

~

4 759.8 19 760.7' 5

755.5

'20 766.9 6

756.9 21 766.2 7

759.4 22 764.0 8

761.6 23 763.0 9

762.5 24 766.9 10 763.1 25 763.3 i

11 763.5 26 764.4 12 763.5 27 710.9 13 761.8 28

-762.4 14 762.1 29 763.?

15 762.1 30 "59.8 RAIL) UNIT PCVE* Lh?EL F&RN ZuSTRUCTIGNF

% ZS:S FCRX, LIST THE AVERAGE CA:LX UNIT FCVFR LTVEL IN VWF-lift FCP EACE

  • DAY Iri
9%-REPORTINS NCNTH. THESE FIJURES WILL BE UCE: TC PLCT A GRAPE FCR FACF REF:RT-IH7 40NTE. NGTE THAT 97 UEIhG MAXIMUE EXPENDABLE CAPACITY FCR TFE NET ELECTh: CAL RAZING GF THF UNIT, THERE MAY BE CCCASICNS VEEN THE PAILY AVERACE PCVER EXCEEDS
EF-100'e/o L:ME (CR THE REFTRICTED PCWEE LEVEL LINE). IN SUCH CASES, THE A7EEAGF CAILY UNIT PCVER CUTPUT SEEE5 EPCULD EF FCOTNCTFE TG EXPLAIN TPE APPAE?il? ANCMALY.

_ ~

9 e

w=

~.... -_,

~.

.. ~

1

./ -

SUMMARY

OF OPERATING EXPERIENCE NOVEMBER, 1982 Listed below in chronological sequence by unit is a summary of operating experiences for this month which required load reductions or

resulted in sC3nificant non-load related incidents.

UNIT 1 November 1 0001 - Reactor at 100%, 785 MW 2052 - On excess letdown, off normal letdown to check non-regenerative heat exchanger for tube leak.

November 2 0315 - Back on normal letdown, no' leaks found in heat exchanger.

~

0730 - Isolated component cooling to. excess letdown to check for leaks.

1730 - Reduced turbine load 15 MW's due to losing

.f>

level in high pressure drain tank, expecting pump to

(.. -

trip.

1755 - Returned to full power, high pressure drain tank level conirol normal.

November 4 1930 - Reactor trip caus;d by loss of "A" main transformer.

November 6-Ofil -. Reactor Critical. Replaced lighting arrestor l

bushing on "A" phase main traisformer.

I 1247 - Generator on line.

l 1400 - Reactor at 35% power, controls in automatic, increasing at 3%/Hr.

l 1900 - Reactor at 50% power.

November 7 1400 - Reactor at 100% power, 785 MW.

j November 9 1750 - Established component coot.ng flow thru l

excess letdown heat exchanger.

November 10 0948 - Emergency drill commenced.

1705 - Emergency drill completed.

Cl.

l 10

[.

November-J12 15'S.- MOV-CS-102A isolated due.to leakage. Start 24

'* v hour clock.-

2330 - MOV-CS-102A returned to service.

November 13 0129 - Chemical addition tank level 96%, below tech.

spec. minimum.. Start 6 :our clock.

0146 - Isolated component cool'ng to excess. letdown i

heat exchanger.. suspect tube leak.

0350 - Chemical addition tank level 97%, stop 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />

~

clock.

November 17 1845 - Commenced ramp down due to-disconnect G105 Overheating.

2130 - Holding reactor power at 50%.

2240 - Commenced ramp down to get disconnect at of service.

November 18 0032 - Generator off the line.

0200 - Generator on the line, disconnect G105 removed from service.

0310 - Holding power at 35% for chemistry.

0415 - Commenced power increase at 3%/Hr.

1720 - Holding power at 69% to evaluate disconnect

.G108 temperature increase.

1930 - Commenced power incrasse at 3%/Hr.

November 19 0605 - Reactor at 100% power - 780 MW.

854 - Commenced power decrease at 150 MW/HR.

Disconnect G108 overheating.

l 2015 - Holding powei at 7EX to evaluate disconnect G108.

November 20 1518 - Start power increase at 3%/Hr. Disconnect G105 returned to service with jumper installed.

2315 - Reactor at 100% power, 785 MW.

November 23 27.25 - Commenced power decrease at 150 MW/Hr.

Disconnect G108 overheating.

J 2335 - Holding et 80% power - 600 MW.

4 11

n

.a 1

November 2l 1645 - Commenced-power increase at 3%/Br. Jumper installed on disconnect.'

November 2.5 0100 - Reactor at 100% power 780 MW.

November 29 1022 - Reactor trip on loss of "A" Reactor coolant pump. Pump tripped due to. faulty relay wi lle

. performing.PT 8.3A.

1238 - Reator critical.

2007 - Generator on-line.

2155 - Holding at 46.5% power. Delta flux out of band ior over'two houts.

November 30 2100 - Commenced slow power increr'e due to boron recovery tank volume.

UNIT II November 1 0001 - Reactor at 83% power, increasing power.

012 - Reector at 100% power.

November 9 0845 - Vrt t vent, gas release. Component cooling

- (,

hcad tanh level column hose blev off'- 30% tech.

specs.

November 10 0948 - Emergency drill commenced.

1705 - Emergency drill completed.

' November 22 1715 - Feedwater PH 8.24 action level.I. Stact 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> clock.-

1815 - Feedwater PH 8.85 (in~ spec.). Stop clock.

November-27 0032 - Power decrease - load follow.

0214 - Stop decrease - 72% power, 580 MW.

0553 - Power increase - 150 MW/Hr.

0748 - Reactor at 100% power.

12

..m

[

AMENDMENTS TO FACILITY LICENSE OR TECHNICAL SPECIFICATIONS NOVEMBER,'1982.

4

None during this reporting period.

4 O

p--.

e L

4-4

-d 13

f --

l YACILITY CHARGES REQUIRING

?

NRC APPROVAL NOVDiBER, 1982 None during this reporting period.

L I

I

(~

t i

t 15

- ~

FACILITY CHANGES THAT DlD NOT REQUIRE NRC APPROVAL NOVEMBER, 1982

.?

UNIT DC 81-36 Replacement of Restricting Orifice 4303 & 3303 1&2 The noise from the restricting orifices was above acceptable noise-limits when a condensate

, olisher is recycled (prior to service) to a condenser connection. This design. change installed a series of three orifice plates tnat will cause a more gradual drop in system pressure to reduce the noise.

SUMMARY

OF SAFETi ANALYS!S There tre no safety implications as a result of this design change. The modification will bring the noise down to an acceptable limit for station employees.

3

.(~:

16 k

e s-NOVEMBER, 1982 TESTS AND EPERIMENTS REQUIRING NRC APPPOVAL None during this reporting period.

TESTS AND EXPERIMENTS THAT DID NOT REQUIRE NRC APPROVAL None during this reporting period.

1

.(

17

OTHER CHANGES, TESTS AND EXPERIMENTS NOVEMBER, 1982 None during this reporting period.

(.

l l

l s..

18

'StiRRYPOSER'STATIbN.

o 12:

I' 7

-CnEMISTRy REroRr

~

~

m.

November

'19'82-a-

. se T.S. 6.6.3.d il 4

~ PRIMARY COOLANT :

UNIT NO..1 UNIT NO. 2

  • s-

-ANALYSIS-MAXIMUM:

MINIMUM AVERAGr.,

MAXIMUM

. MINIMUM

- AVEPJ.GE.

-(A)

(A)

(A)

Gross'Radioact., UCi/ml-6.04 1.15 3.11

-4.39 1.69 2.52-Suspended Solids, ppa 0.1 0.1c

-0.1 0.1 0.1

-0.1 Gross' Tritium,'UCi/ml 1.07-1 2.81-2 5.25-2.

1.96-1

-1.55-1 1.80

-1 (A) 5.13-2 ( A) 9,77-1(A) 3.57~3 5.92 1.57

-3 Iodine-131,UCi/ml 4.71 I-131/I-133

.7599

.3999

.5557 1.7500

.2131;

.6947 3}

Hydrogen, cc/kg 37.1 25.3 29.7.

45.8~

31.0 37.6 (C)

(D)

Lithium, ppa-1.00

.34

.68 1.25 1.05

1.18 Baron-20. ppa +

88.98 20.78 39.18 95.26 79.97 85.76

,. [C

.000

.000

.000

.000-

.000 0xygen-16, npa

.000 Chloride,' ppa

<.05

<.05

<.05

<.05

<.05

<.05-7,

._pH e 25 C 7.40 ~

'6.60 7.16 6.91 6.79 6.85-

'+. Boron-10 = Total Boron x 0.196 4

(E)

NON-EADI0 ACTIVE CHEMICAL RELEASES. POUNDS T.S. 4.13.A.6 f

Phosphate -

Boron 915 y.

3 Sulfate; Chromate 0.0

- 50% NaOH Chlorine 0.0 REMARKS: (A) Values reflect suspected failed fuel.(B) low hydrogen concentration following unit ramp 11/79. increase ir vcI pressure recommended. (C) LiOH added to increase Li concentration: 390 gas on 11/4,1070 gas on 11/8, 470 gas on 11/12 ' 390 gas on 11/16 ana 300 gas on 11/19.(D)Cition bed pfaced.iaJai41ce 11/ tyto lower Li concentration. (E) The i

. levels of these chemicals should create no environmental impact.

]

l 19-

)

I

-..... ~.,.

...?t?,-*. S,T. fl:7 M 1_,...,..._.,__.._7'

~I_U,7.i.'7". _ i C.1 ~ " '

.[.

.___.,_im.__,

,__m.,_U

~

=.

7

. 4

<({V i

DESCRIPTION OF ALL INSTANCES WHERE THERMAL DISCHAGE LIMITS WERE EXCEEDED I

NOVEMBER, 1982 Due to the impairment of the circulating water system on the

.following' days, the thermal discharge limits ware exceeded as noted.

November 1, 1982 Exceeded 15'F AT across station November 2. 1982:'- Exceeded 15*F AT across station

-November 3, 1982 - Exceeded 15*F AT acrcss station Novexber 4, 1982

' Exceeded 15'F AT across station November 7, 1982 Exceeded 15'F AT across station

-Noiember 8, 1982 Exceeded 15'F AT across station November 9, 1982 Exceeded 15'F AT across station November 10, 1982 - Excee'ded 15'F AT across station

, November 11, 1982 - Exteeded 15'F AT access station November 12, 1962 - Exceeded 15'F AT across station November 13,1982 - - Exceeded 15*F AT across station November 14, 1982 - Exceeded 15*F AT across station

+

November 16, 1982 - Exceeded 15'F'AT across station November 22, 1982 - Exceeded 15'F AT across station November 23, 1982.- Exceeded 17.5%F AT across station

./-

November 24, 1982 - Exceeded 17.5%F AT across station November 25, 1982 - Exceaded 17.5'F AT across station November 26, 1982 - Exceeded 15'F AT across station November 27, 1982 - Exceeded 15'F AT across station November 28, 1982 - Exceeded 15*F AT across station November 29, 1982 - Exceeded'15'F AT across station

  • lndicates dates where station AT was less than or equal to 15.0*F across station for some time during the day.

The AT excursions were allowable under Technical Specifications 4.14.B.2.

There were no reported instances of adverse environmental impact.

The temperature change at the station discharge exceeded 3** per hour on November 4 due to a Unit il reactor trip.

The temperature change at the station discharge exceeded 3*F per hour on November 29 dos to a Unit #1 reactor trip. The two associated wi.h the reactor trip were allowable in accordance with Technical Specification 4.14.B.1.

There were no reported instances of adverse environmental impact.

_?

a 20

-. ~. _

-~

l FliEI, IW:0 LING N5VEMBER, 1982 Units One and Two None during th G reperting period.

G

[

i I

I 1

<('.

21 t

~

{_

-_.u

.)

.: PROCEDL7I REVISIONS TruJ CHANGFD THE OPERA *ING MODE DESCRIBED IN THE FSAR

..s November, 1982 r '-

None during this reporting period..

J 9

1.

e 4

1 l

j f.

A

- z 5

22 79

+

  • $4g 9

--h--We-899y*-W-v4r t v'-Tvp r#pq

  • y-

'w-p-y y-e*-eg--.=

M-r'=

9r Y-F

$y---<

IP W

--2g-f ww e as-u-+=-mpg eTw

-e y---=pr--@=t93C'

~=v 1

vvr

&-=

4

--M-

-W D

[_i DESCRIPT;0N OF PERIODIC TESTS WHICB WERE NOT

\\

COMPLETED WITHIN THE TIME LI"ITS SPECIFIED IN TECHNICAL SPECIFICATIONS

-NOVEMBER, 1982 None during.:this reporting period.

s t

h 4

4 i

i L

i.

I l

l l

." 3

JJgER1* ICE INSPECTION

.=

NOVEMBER, 1982

. Units One and Two None during this reporting perind s

l 24

e--.

a

. RE*a.)RTABLE OCCURRENCES PERTMNING TO

. ANY OUTAGE OR POWER EDUCTIONS NOVDL.2R,' 1982 None during this reporting peritG.

s,.

O A.

d E

25

  • +

we y

-, - ' =

-e-

=A

+

m MAINTENANCE OF S AFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIO';S UNIT NO. 1 MECHANICAL MAINTENANCE 9

4 4

t

<*e 4

a 26 w.

.w.*

W-T-

a c

n.

o pgpr.MgCg 9 O T 82.* '9:35 AN PACK 1 LAFIT1-12/09/82 V

(MAINTENAMcK OF SAFRTT RELATM0 SYSTMS 90 RIM Ot!T4CK OR RK0tCK0 nwKR PERE 005) ll h,,

RATU RV0T STS CONP MARoe StM84 ART

'WKPERP U

MR NT:WR199 11/04/82 AM NOMINR MS-tS9 INSTAlf, QUICK OIK0MM t PABRICATKO AMO INSTALLED AS 1 2050T12%6 0

P l-11/0%/82 GC VALVK 1-0C-t%

VALVK MAS MDT N BOMMET LKAK TKim TO TI@TKM 00VM CM B00T 1 210191%57 0

11/0%/82 hC VALVK 1-RC-68 ANUCT PACKIM CLAMO

. ANUWKD YnREGUS PACKING 1 2102%12%b 0

11/04/82 MS B01TLK 1

CMAMCK OUT MITR0;TM BCTTLE CatPLATKO t 2102801l6 0

tt/0%/82 MS VALYK N't-MS*102A OVEMAUL CHANGAD CASKKT SET t 211011501 0

5, '

11/0%/82 MS VAlvK M'Y-MS-1028 GVERMAUL CPAMCK0 CASKMT SET 1 211011502 0

11/0%/82 CP VALVK 1-CR=101 R m 0VK BORIC MID PLUG UNCLCCCK0 LEME IM5 TALL 1 211031516 0

11/04/82 KM PIPIMC M/A TNRK40KO E2TTIMC BT t=Nt=15 APPLIKO 2RRKA0 CGN NIIMO t 21103215%

0 11/05/82 CS MMP 1-CS-T-3A*38 IMPLwKMT EMC $11107 81-11 REW1.*K0 34 + 38 1

10%28110%

0 11/05/82 MS VALVK 1-MS-t%5 VALVK RAS BOOT 10 BQMMKT LKAK FlflMAMITKO NOT 70 1 210210130 0

11/06/82 MS VALVK 50V-MS*t028 VALVK LKA! BT REPLACKD CASKAT SAT 1 2110512%3 0

g 11/06/92 NS VALVK

- 30V-MS-102A

. VALYK LEAKS BT -

REPLACFB CASKMT SAT t 2110512%%

0 ft/11/82 VS PIDC 1-VS-K-%B REPLACK ZINC PLUG REPLACK ZIMC AMO PLUC.

t 211150511 0

11/10/82 N BOTTUS W-P-2 CHANCK 007 MITR0 801TLKS RKPLACK0 M2 BOTTLK L 2110%1801 0

11/29/82 80 VALVK TV-80=100A REPAIR N ORICIMAL MAS BERM PtimAMIT QVK WAULKO VALVK 1 206221536 0

it/29/82 VS PtMP t-VS-P-1A REPACK KMP RKPACKKO MMP USKO to t 211110132 0

1 11/29/02 VS PIMP t-VS-P-28 RKP4CK CISA 5MNRLK0 KINF + IMSPKLTKO INTKRR 1 2111201%0 0

11/29/82 CS VALVK CS-51 VALYK NAS PIPK BMKKM GPP RAMAWED PIFK MIPPLK 1 211162300 0

-11/29/82 N FlMP t-N-P-tA CLKAM M ION STRAERKR M OUPACTURKO MFW STRAIMER 1 211230 ROT 0

11/29/82 W A0TTLK t-N-P-2 CH4Mn ?2 M1TLK RAPLACK0 M2 BOTTLK AM0 t 211280901 0

11/30/82 N PtMP t-N-P-10B A0JUST MMP PACKING A0JUSTKO PACKINC t 2tt290330 0

9-0 OKIT TOTAL ls t

4 g

e e-I i-i t

e-1 MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO. 2 MECHANICAL MAINTENANCE

+

None during this reporting period.

1 4

h a

(.I 28 L-

1 s,

MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO. 1 ELECTRICAL MAINTENANCE I

t i

O e

29

==-g-w e

3

=,

b. l j

.f, j4 4

e

, DEPT =ALRC

  • ~ '

~

t 9X 82 e 9s3$ AN TACK 2.

1*

WIT 1-12/09/92

(",

-'(MAIRTFRAKK Of SATRTT RELATED SISTntS 0*)RIAC Ot! TACK OR REvKKO NVER TF.RICOS).

's R.WDtkVOT STS CMP MMKR0 Sl0PtART WUTRF U

MR TGTtNW1M

,4 11/0n/n2 04 INSTR

. CS=0A=104 8 EH KL N I1CR STICKS STRAIM TTRx9 h00 CR 1 208312359 0

g* -

11/0S/82. EPH TRMSFQR RfA CMXK A M4IR TRMSNWM REPLACE 0 U 3 7J0VIRC 2

2110%2100 tt/C6/02 MS SCV MV-MS-102A ant /ST 'IMIT MI1CRTS OR S0V-MS-tota ant 1STTO UMETS M0 1 211051831 0

(l 11/06/82 MS S0Y SOV-MS-102R ant!ST DIT WI1CRES}

FCURO AIR ISCLATTO 10 1 211051838 0

i 11/11/82 CS MCV N0V-CS-107A WCRK WITH GPS CRANCKO fvRQVM ?21TIRC t 211121900 0

11/11/82 N VALFK-NOV-N-1024 A.#-N-tC2A CLASK0 801W 4A+8 TKROFT MW N 102A CYNKKO CE 1'

211160227 0

6 tt/11/82 N M ITCR LS-N-1028 PRXESS VERT WATER ALKRT AE,AJ9t CR XKKO 0FKRATICK 0F

'1 211161112 0

.?

l 11/11/82 M

MCV NOV-N -1020 ANUST UNITS AS RRCESSART ANVSTT) LIMITF 30 1 211110906 0

11/2%/82 EPOC BA1TERI 1 KOC REPLACK BATTERE REPLACE 0 bat 1Ltl ARO 1 2112%0100 0

11/30/82 SS IRSTR sv-SS-106s Cwszo IROICATIRC UcRr crxRATx0 VAva SAT MO 1 2 n26110s 0

1

,,,T,,T,,,

O f

i I.

.g' g

t' t

9. -

l-I

,d e+

1 l

7-i

n 4

'S 7,,

..i MAINTFNANCE OF SAFET) RELATED SYSTEMS DURING OUTAGE OR REDUC D POWER PERIODS UNIT NO. 2 ELECTRICAL MAINTENANCE None dt. ting this reporting pe.riod.

4 t

4 fe e, 8

O:..

s 31

.-~.

._a

~

-g,,

4 m

?_

LW..

~ MAINTENANCE OF SAFETY RELATED SYSTEMS DURING-OUTAGE.OR REDUCED POWER PERIODS

- UNIT NO. 1 INSTMUMENT MAINTENANCE e

. O n

f.

t w

+

l 32 I

,O O

ft e

. ggry.Tgs?

g pKC 32 e 3:35 m TMK 3 EMITt=12/03/82 (MAINTEMARCK OF SAFFT! RKLATED STS*9tS 9tMinC OVTMK OR RKotKK9 NVKR PTRICOS) 3:

l RAT:3 WOT SES CONP MARUC SIN 9 ART VKrKRF U

MR TVTUbNtN L

i t1/H /92 JiC INSTR CA6 R00 CCRTCOL %S IMCERT TAILDRK RMPLACR0 MSK ARV 1 2110%0105 0

11/05/83 BC NOMINE Kt-nC-1000 C&RK COOLING N0 nit 0R KRRATIC RAN PT 2.27 CHWK SAT 1 2ttn1s2%

0 tt/05/82 M MCMENR RI-W-101 CHCK $0tIKK Ntit0E Bl6VS TV.WS SKUKED BR10CK CIKUIT 1 211051%20 0

f 11/01/82 M NCMITOR M-CC-LOS RKSAT L9K D0.'SFT VCRK RRTLACK9 C1 H CFFCRED SAT t 211051%s1 0

11/07/82 RM NOMENR RZ-CC-105 CRAnCK AL4M SRTNINTS CMAGED SRTNINTS t 2110606ss 0

11/11/82 RP INSTR F-8 IMOTCATION RRRATEC INVKSTICATR RFPLACKB SXCMAL NCDULK L titt61%ts O

1t/11/92 M DETwNR 91-M 5-151-SPIKING RMCALIBRATEV VRTACTOR 1 2111705t5 0

11/19/02 M PtMtP M-VC-103/t%

EXCKSSIVK TLOV R.4TE A0JUSTKO TLOV TO WItWIR 1 211151s%S 0

4 1t/90/82 M RXORDER RR-175 REPLACK N LLKTS RECORvkR CMECRK9 CK 1 111210350 0

11/30/02 W IhTR FR-t-nes RRCCRDER NESMT ROTATK Cl!AME9 AMO INSPFCTKO 1 111210125 0

e 0.07 19TAL 0

W W

.. - ~

4 k

s t

't 1

P 1

w

a-e

(..

..s MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO. 2 4

INSTRUMENT MAINTENANCE A

f d

d 34 5-M-N t

my p.*%-'T, hha

'e

>fWC 4

e a

w 4

9

k

~,-

L.

e,.

54Pf=T#57 9 PAC 42

  • 9:41 Alt PEK 1

-a 8

- fMIT2-12/09/02 -

(MAERTRNANCK 07 SAWT1 MLAt!2 STSTARS 90 RING OVTKK H MDtfD NVER PWR10M) 4 E

li RRT2ER99T STS CNP MAK90 Sl000eRT

. WWWRF.

U Mir flit %1F1N 11/21/82 59' IRSTR ^

' T' '06

  • C5FrK LALEBRATE0W AEM arc InoTCA10R 2 1112705s1

.. d 4.

4 s

=

1 e

t

)

w' g,.

I b

k

(

L 7

[

P, i

t if tl G

4 b

t 1

w L

+

...o r :.

o.

HEALTH PHYSICS.

..c NOVEMBER, 1982 i

There was n. single re. lease of radioactivity or radiation expos'.re specifically associated with an outage that accounted for more than.10%

of the allowable annnual values in 10CFR20.

t P

e L

i 36

!~

L-

= l-o.

e W' s

4 FROCDURE DEVIATION 3 REVIEWED _ BY STATION 1:UCLEli SAFETY AND OPERATING COTiITTEE AFTER TI!!E LDiIT' SPECIFID IN TECDsICAL SPECIFICATIONS L[,

/

November, 1982 Date SNSOC Title Date Deviated Reviewed Pr*cedure No.

Unit

.MMP-C-G-061.2 1

Repairs to Cast Vacuum Pumps 10-20-82 11-12-82 0MP-C-G-84 1-Repair or Replacement of Worn 09-13-82 11-12-82 or Defective Pump Internals Ingersoll-Rand Inliner pumps EMP-C-FP-43 1

Sealing of Fire Stops using 10-28-82 11-12-82 Dow Corning Q3-6548 Silicone RTV Foam

/

t I

37

--+,w-w-,

w

~mo sp..

.w.%.

..,,