ML20070G781

From kanterella
Jump to navigation Jump to search
Monthly Operating Repts for June 1994 for Catawba Nuclear Station
ML20070G781
Person / Time
Site: Catawba  
Issue date: 06/30/1994
From: Robert Williams
DUKE POWER CO.
To:
Shared Package
ML20070G776 List:
References
NUDOCS 9407200290
Download: ML20070G781 (10)


Text

.

OPERATINS LATA REPORT DOCKEI NO 50-413' DATE July 15. 1994-0PERATING STATUS COMPLETED BY R.A. Willians TELEPHONE 704-382-5346

1. Unit Nase: Catanha 1
2. Reporting Period: June 1, 1994-June 30, 1994
3. Licensed Thersal Poner (MWti:

3411

4. Nameplate Rating (Bross MWe):

1305*

Notes

  • Nameplate Rating-
5. Design Electrical Rating (Net MWe):

!!45 (Bross NWel calculated as

6. Marieus Dependable Cap. city (Gross MWe):

1192 1450.000 MVA r.90 power

7. Maxisus Dependable Capacity (Net MWe):

!!29 factor per Page iii, 8.' If Changes Occur in Capacity Ratings (Itess Number 3 Through 7) Since Last NURES-0020.

Report. Give Reasons:

9. Pcwer Level To Which Restricted, if Any (Net MWe):
10. Reason For Restrictions, if any:

This Month. Yr.-to-Date Cueulative

11. Hours In Reporting Period 720.0 4343.0 78936.0
12. Number Of Hours Reactor Was Critical 720.0 4316.6-60094.6
13. Reacter Reserve Shutdown Hours

--0--

--0--

--0--

6

14. Hours Generator On-Line 720.0 4305.1

-58958.5

15. Unit ReserYe ShuldOWD HDurs

--0--

--0--

--0--

16. Gross Thersal Energy Generated (MWH) 2349344

'14271179 191513715

17. Gross Electrical Energy Generated (MWH) 829899 5096716 67460851
18. Net Electrical Energy Generated (MWH) 785266 4828981 63373610
19. Unit Service Factor 100.0

.99.1 74.7

20. Unit Availability Factor 100.0 99.1 74.7
21. Unit Capacity Fatter (Using MDC Net) 96.6 98.5 70.8
22. Unit Capacity Factor (Using DER Net) 95.3 97.1 70.1
23. Unit Forced Dutage Rate 0.0 0.9 9.7
24. Shutdown Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

None

25. If Shut Dcwn At End Of Report Period. Estisated Date of Startup:
26. Units in Test Status (Prior to Ccamercial Operation):

Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMERCIAL OPERATION 9407200290 940715 PDR ADDCK 05000413 R

PDR

'l

[

i 0FERATING 2ATA REPORT DOCKET NO 50-413 UNIT Catauba 1 DATE 3uly 15.1994 COMPLETED BY R.A. Williams TELEPHONE 704-382-5346 l

RONTH June,1994 DE AVERAGE DAILY POWER LEVEL DE AVERAGE DAILY POWER LEVEL (MWe-Nett (MWe-Net) 1 1133 17 1130 2

1133 18 1132 3

1113 19 1130 4

1135 20 1127 5

1134 21 1127 6

1131 22 1126 7

1131 23 1125 l

8 1131 24 1125 9

1134 25 1130 i

10 1100 26 1131 l

l-11 534 27 1130 l

12 612 28 1128 13

!!!B 29 1127 14 1131 30 1126 15 1129 l

16 1120

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

50-413 UNIT NAME carantsa 1 DATE v//in/

REPORT MONTH June 1994 COMPLETED BY x.

a.

illiams TELEPHONE tivej-asz-nase (1) 2)

3 (4)

(5)

E HOD T

A OF -

LICENSE N

'Y S

SHUT EVENT SYS-CAUSE AND CORRECTIVE O

P DURATION O

DOWN REPORT TEM COMPONENT ACTION TO DATE E

HOURS N

R/X NO.

CODE CODE PREVENT RECURRENCE 4-P 94-6-11 F

A HC-HTEXCH REPAIR MAIN TURBINE CONDENSER TUBE LEAK (1)

(2)

(3)

(4)

F Forced Reason:

Method:

Exhibit G - Instructions A-Equipment FailureB-Maintenance or test (Explain)

S Scheduled 1-Manual for Preparation of, Data 2-Manual Scram EntW Sheets For Licensee C-Refueling 3-Automatic Scram

. Event Report-(LER)'

D-Regulatory R9striction E-Operator Training & License Examination. 4-Other (Explain)

File (N W EG-0161)

F-Administrative (5)

G-Operator Error (Explain)

Exhibit I - Same Source H-Other.(Explain)

4 DOCKET: 50-413 UNIT: Catawba 1-

.)

i Date: 07/15/94 i

NARRATIVE

SUMMARY

i K NIH: June 1994 i

l Catawba. Unit 1 began the month of June operatirvJ at 100% full power. The unit w=sced decreasing power on 06/10 at 2000 and held at 52% power on 06/11 at 0100 to 06/12 at 1645 to repair main turbine condenser tube leak. 'Ihe unit returned to' 100% full power on 06/13 at 0500 and operated at or.near 100% full power the remainder of the month.

i Prepared by: R. A. Williams Telephone: (704)-382-5346' u

l I

l l

l MONTHLY REFUELING INFORMATION REOUEST 1.

Facility name: Catawba.

Unit 1 2.

Scheduled next refueling shutdown: February 1995 3.

Scheduled restart following refueling: April 1995 THE PROJECT MANAGER HAS BEEN ADVISED BY SEPARATE COMMUNICATION OF ANY T.S.

CHANGE OR LICENSE AMENDMENT. THEREFORE, QUESTIONS 4

THROUGH 6 WILL NO LONGER BE MAINTAINED IN THIS REPORT.

l 4.

Will refueling or resumption of operation thereafter require a technical specification change or other licence amendment?

If yes, what will these be?

If no, has reload design and core configuration been reviewed by l

Safety Review Committee regarding unreviewed safety questions?

5.

Scheduled date(s) for submitting proposed licensing action and supporting information.

I 6.

Important licensing considerations (new or different design or supplier, unreviewed design or performance analysis methods, significant changes in design or new operating procedures).

7.

Number of Fuel assemblies (a) in the core: 113 (b) in the spent fuel pool: dai 8.

Present licensed fuel pool capacity: 1418 Size of requested or planned increase:

9.

Projected date of last refueling which can be accommodated by present licensed capacity: Egntember 2009 DUKE POWER COMPANY DATE:

July 15. 1994 Name of

Contact:

R.

A.

Williams Phone:

(704)-382-5346

l OPERATING DATA EEFDRI DOCirIT NO 50-414 DATE July 15. 1994 OPERATING STATUS COMPLETED BY R.A. Willians TELEPHONE 704-382-5346

1. Unit Nase: Catawba 2
2. Reporting Feriod: June 1, 1994-June 30, 1994
3. Licensed Thersal Power (MWt):

3411

4. Naseplate Rating (Gross MWe):

1305a Notes *Naseplate Rating

5. Design Electrical Rating (Net MWe):

1145 (Gross MWe) calculated as

6. Maxisus Dependable Capacity (Bross NWe):

1192 1450.000 MVA x.90 power

7. Maxisus Dependable Capacity (Net MWe):

1129 factor per Page lii, O. If Changes Occur in Capacity Ratings (!tess Nusber 3 Through 7) Since Last NURES-0020.

I Report. Give Reasons:

L

9. Power Level To Which Restricted, if Any (Net MWe):
10. Reason for Restrictions, if any:,

This Month Yr.-to-Date Cusulative

11. Hours in Reporting Period 720.0 4343.0 68952.0
12. Nusber Of Hours Reactor Was Critical 0.0 2854.2 52795.1
13. Reactor Reserve Shutdown Heurs

--0--

--0--

--0--

14. Hours Generator On-Line 0.0 2010.8 51B98.3

[

15. Unit Reserve Shutdown Hours

--0--

--0--

--0--

16. Gross Thersal Energy Benerated (MWH) 0 9140659 166029698
17. Gross Electrical Energy Gener ted (MWH) 0 3280126 59857385
10. Net Electrical Energy Generated (MWH)

-11144 3093363 55383420

19. Unit Service factor 0.0 64.9 75.3
20. Unit Availability Factr,r 0.0 64.9 75.3
21. Unit Capacity Factor (Using MDC Net) 0.0 43.1 71.0
22. Unit Capacity Factor (Using DER Net) 0.0 62.2 70.2
23. Unit Forced Dutage Rate 0.0 1.2 9.2
24. Shutdown Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

Currently Refueling

25. If Shut Down At End Of R, port Period. Estinated Date of Startup: Jul_y 04, 1994
26. Units In Test Status (Prior to Commercial Operation):

Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION i

e OPERATINS IATA REPORT f

l DOCKET NO 50-414 l

UNIT Catawba 2 DATE July 15. 1994 COMPLETED BY R.A. Williams TELEPHONE 704-382-5346 00 NTH June 1994 t.fl AVERABE DAILY POWER LEVEL D.,Al AVERAGE DAILY POWER LEVEL (MWe-Net)

(MWe-Net) l i

1 0

17 0

2 0

18 0

l 3

0 19 0

l 4

0 20 0

l t

5 0

21 0

l 6

0 22 0

7 0

23 0

8 0

24 0

9 0

25 0

10 0

26 0

11 0

27 0

12 0

28 0

l 13 0

29 0

l 14 0

30 0

l' 15 0

16 0

l

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

50-414 UNIT NAME caranca e DATE viflo/39 REPORT MONTH

-June 1994 COMPLETED BY x.

a.

williams TELEPHONE (evej-auz-oa40 (1) 2)

(4)

(5)

E HOD T

A OF LICENSE N

Y S

SHUT EVENT SYS-CAUSE AND CORRECTIVE O

- P DURATION O

DOWN REPORT TEM COMPONENT ACTION TO DATE E

HOURS-N R/X NO.

CODE CODE PREVENT RECURRENCE 2

94 1 S

720.00 C

RC FUELXX END-OF-CYCLE 6 REFUELING OUTAGE Y

(1hForced (2

(3 (4

eason:

ethod:-

xhibit G - Instructions A-Equipment FailureB-Maintenance.or test (Explain)-

.1-Manual for Preparation of, Data S Scheduled 2-Manual Scram EntW Sneets For Licensee C-Refueling 3-Automatic Scram Event Report (LER D-Regulatory Restriction 4-Other (Explain)

File (NWEG-0161))

erator Training & License Examination E-Og$ brE oh xhibit I - Same Source H-O her (Explain) (Explain)

G

t t

DOCKET: 50-414 UNIT: Catawba 2 Date: 07/15/94 L

i NARRATIVE SCPHARY i

ITNIH: June 1994 i

Catawba Unit 2 began the month of June in end-of-cycle' 6 refueliry outage. 'Ihe unit.

was in the refueling outage.for the entire month, e

i

(

I l

l I

i l

l i

i i.

I Prepared by: R. A. Williams Telephone: (704)-382-5346 l

l l

l l

MONTHLY REFUELING INFORMATION REOUEST 1.

Facility name: Catawba.

Unit _2 2.

Scheduled next refueling 4hutdown: Currently Refuelina 3.

Scheduled restart following refueling: July 1994 THE PROJECT MANAGER HAS BEEN ADVISED BY SEPARATE COMMUNICATION OF ANY T.S.

CHANGE OR LICENSE AMENDMENT..THEREFORE, -QUESTIONS 4

THROUGH 6 WILL NO LONGER BE MAINTAINED IN THIS REPORT.

4.

Will' refueling.or resumption of operation thereafter require a technical specification change or other licence amendment?

If yes, what will these be?

If no, has reload design and. core configuration been reviewed by Safety Review Committee regarding unreviewed safety questions?

5.

Scheduled date(s) for submitting proposed licensing action and supporting information.

6.

Important licensing considerations (new or different design or l

supplier, unreviewed design or performance analysis methods, significant changes in design or new operating procedures).

7.

Number of Fuel assemblies (a) in the core: 113 (b) in the spent fuel pool: AAA 8.

Present licensed fuel pool capacity: 1418 Size of requested or planned increase:

9.

Projected date of last refueling which can be accommodated by present licensed capacity: September 2011 l

DUKE POWER COMPANY DATE:

July 15. 1994 l

l Name of

Contact:

R.

A. Williame Phone:

(704)-382-5346 i

~

l i

.