ML20070G585

From kanterella
Jump to navigation Jump to search
Proposed Tech Spec Table 4.8-1 Re Diesel Generator Test Schedule
ML20070G585
Person / Time
Site: Summer 
Issue date: 03/08/1991
From:
SOUTH CAROLINA ELECTRIC & GAS CO.
To:
Shared Package
ML20070G584 List:
References
NUDOCS 9103120216
Download: ML20070G585 (2)


Text

.. '

o ATTACHMENT MARKED-UP TECHNICAL SPECIFICATION PAGES Page Specification Change Description 3/4 8-7 Table 4.8-1 Renumber the referenced SR 4.8.1.1.2.d to SR 4.8.1.1.2.f

/6 P

C-TABLE 4.8-1 O!ESEL GENERATOR TEST SCHEDULE Number of Failures Number of failures in in Last 100 Valid Last 20 Valid-Tests

  • Tests
  • Test frequency 11 14 Once per 31 days 12**

15 Once per 7 days

  • Criteria for determining number of f ailures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1.108, but determined on a per diesel generator basis.

For the purposes of determining the required test frecuency, the previous test failure count may be reduced to zero if, in conjunction with the manu-f acturer a complete diesel overhaul to like-new conditions is completed, and if acceptable reliability has been demonstrated.

The reliability crite-rion shall be the successful completion of 14 consecutive tests in a single series.

Ten of these tests shall be in accordance with Surveillance Require-ment 4.8.1.1.2.a.3 and 4.8.1.1.2.a.4; four tests, in accordance with Surveillance Requirement -4.0.11 If this criterion is not satisfied

' 'f b l l' 2 '

during the first~feYlis ofttsks.2.d., -any alternate criterion to be used to

~

transvalue the_ failure count to zero requires NRC approval.

    • The essociated test frequency shall be maintained until seven consecutive failure free demands have been performed and the number of failures in the

-last 20 valid demands has been reduced to one.

1 SUMMER - UNIT 1 3/4 8-7 AMENOMENT NO. 77

,-