o ATTACHMENT MARKED-UP TECHNICAL SPECIFICATION PAGES Page Specification Change Description 3/4 8-7 Table 4.8-1 Renumber the referenced SR 4.8.1.1.2.d to SR 4.8.1.1.2.f
/6 P
C-TABLE 4.8-1 O!ESEL GENERATOR TEST SCHEDULE Number of Failures Number of failures in in Last 100 Valid Last 20 Valid-Tests
- Tests
- Test frequency 11 14 Once per 31 days 12**
15 Once per 7 days
- Criteria for determining number of f ailures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1.108, but determined on a per diesel generator basis.
For the purposes of determining the required test frecuency, the previous test failure count may be reduced to zero if, in conjunction with the manu-f acturer a complete diesel overhaul to like-new conditions is completed, and if acceptable reliability has been demonstrated.
The reliability crite-rion shall be the successful completion of 14 consecutive tests in a single series.
Ten of these tests shall be in accordance with Surveillance Require-ment 4.8.1.1.2.a.3 and 4.8.1.1.2.a.4; four tests, in accordance with Surveillance Requirement -4.0.11 If this criterion is not satisfied
' 'f b l l' 2 '
during the first~feYlis ofttsks.2.d., -any alternate criterion to be used to
~
transvalue the_ failure count to zero requires NRC approval.
- The essociated test frequency shall be maintained until seven consecutive failure free demands have been performed and the number of failures in the
-last 20 valid demands has been reduced to one.
1 SUMMER - UNIT 1 3/4 8-7 AMENOMENT NO. 77
,-